- Open Access
- Total Downloads : 336
- Authors : Sharanabasappa H Biradar, Prof. G. S. Hiremath
- Paper ID : IJERTV4IS080679
- Volume & Issue : Volume 04, Issue 08 (August 2015)
- DOI : http://dx.doi.org/10.17577/IJERTV4IS080679
- Published (First Online): 27-08-2015
- ISSN (Online) : 2278-0181
- Publisher Name : IJERT
- License: This work is licensed under a Creative Commons Attribution 4.0 International License
3D RC Multistorey Building Seismic Assessment with User Defined Hinges
Sharanabasappa H Biradar
PG Student
Civil Engg. Dept. BEC Bagalkot Bagalkot, India
Prof. G. S. Hiremath
Civil Engg. Dept. BEC Bagalkot Bagalkot, India
Abstract Earthquake causes the random ground motions because of which most of the structures subjected to infrequent loading. Seismic behavior of structure is analyzed by Static pushover method of analysis. Static pushover method analyzes the structure based on the formation of hinges. In present study is done assigning user defined hinges for beams and columns we given calculated moment curvature relations as input. Nonlinear static pushover analysis is performed in SAP 2000 based on FEMA 365 and ATC 40 guidelines to get the results using user defined hinge properties. The parametric results such as hinge states at performance point and ductility ratio, are compared with low rise and medium rise building model with varying percentage of central openings in brick masonry infill wall.
Keywords User Defined Hinges, Infill Wall, Pushover Analysis, Performance Levels, And Ductility Ratio.
-
INTRODUCTION
Earthquake causes the random ground motions in all directions, radiating from epicenter. These ground motions causes structure to vibrate and induces inertia forces in them. Since inelastic behavior is intended in most structures subjected to infrequent earthquake loading, the use of nonlinear analyses is essential to capture behavior of structures under seismic effects. Due to its simplicity, the structural engineering profession has been using the nonlinear static procedure (NSP) or pushover analysis, described in FEMA-356 andATC-40. It is widely accepted that, when pushover analysis is used carefully, it provides useful information that cannot be obtained by linear static or dynamic analysis procedures.
The implementation of pushover analysis, modeling is one of the important step. The model must consider nonlinear behavior of structure/elements. Such a model requires the determination of the nonlinear properties of each component in the structure that are quantified by strength and deformation capacities. In practical use, most often the default properties provided in the FEMA-356 and ATC-40 documents are preferred. Due to convenience and simplicity. These default properties can be implemented in well-known linear and nonlinear static and dynamic analysis program such as SAP2000. The use of this implementation is very common among the structural engineering profession and researchers. Although there may not be significant differences in the modeling of steel structures, the use of guidelines requires special care for reinforced concrete (RC)
structures. As mentioned above, the deformation capacity of reinforced concrete components depends on the modeling assumptions. FEMA-356 and ATC-40 guidelines are prepared on the basis of some assumptions related to typical reinforced concrete construction in the United States. While the documents provide the hinge properties for several ranges of detailing, the programs (i.e. SAP2000) may implement averaged values .Also, there may be some differences in construction techniques and detailing in other countries. If the user knows the capability of the program and the underlying assumptions, then people can take advantage of the feature provided to avoid an extensive amount of work. In some cases, the default hinge properties are used without any considerations due to simplicity. The definition of user- defined hinge properties requires momentcurvature analysis of each element. For the problem defined, building deformation is assumed to take place only due to moment under the action of laterally applied earthquake loads. Thus user-defined M (moment hinge) hinge for beam and PMM(axial force and moment hinge) hinges for columns are assigned at member ends where flexural yielding is assumed to occur. Moment-curvature relationship was assigned in SAP2000 for both confined and unconfined cases to represent the flexural characteristics of plastic hinges at the ends.
This study aims to the Three-dimensional (3-D) modeling pushover analysis is employed. The SAP2000 program is used for pushover analysis.
-
BUILDING DESCRIPTION.
In the present study 3D RC multi-storeyed of the five and eight storeyed building models are considered. The plan and elevations of the building models considered are shown in Fig 1 to Fig 5, the all storeys height is 3.5m kept for all the building models. The building is considered to be located in the seismic zone III region and intended for office use. In the seismic weight calculations, only 25% of the live load is considered. Slabs loads are applied on the beam. Masonry brick walls are modeled by considering equivalent diagonal strut. M (moment hinge), PM (axial force and moment hinge) hinges with hinge properties are assigned at both ends of beam and column elements by using user defined hinges. Input data given for all the buildings are detailed in below. Four analytical models are considered as below,
-
Plan and Elevation of the Building models
The plan of the building is shown in the Fig.4 and elevation of the building models are shown in Fig 1 to Fig 5.
Fig.1: Plan of building
Fig 2: Elevation of the five storeyed bare frame building model
Fig 3: Elevation of the five storeyed building models with openings (10% to 30%)
Fig 4:Elevation of the eight storeyed bare frame building model
Fig 5: Elevation of the eight storeyed building models with openings (10% to 30%)
-
Modeling infill panel as equivalent diagonal struts (without openings)
It is evident from most of the studies that the infill wall panels fail due to increasing intensity of lateral loads by corner crushing in the infill at least one of its loaded corners associated with strong infill surrounded by a strong frame in which the diagonal compression strut mechanism is fully developed that converts the frame system into the truss, increasing the lateral stiffness of the frame manifold. And the masonry infill wall is modeled as pin-jointed single equivalent diagonal strut (SEDS), carrying axial compressive force only.
Investigators
Formula
Stafford Smith and Hendry (1963)
Table 1: Width of equivalent diagonal struts given by various researchers
=(ECAC)(GmAm)is a dimensionless parameter, Ac is the gross area of column and
-
User defined hinges
The definition of user-defined hinge properties requires momentcurvature analysis of each element. For the problem defined, building deformation is assumed to take place only due to moment under the action of laterally applied earthquake loads. Thus user-defined M3 hinge was assigned at member ends where flexural yielding is assumed to occur. Moment-curvature relationship was assigned in SAP2000 for both confined and unconfined cases to represent the flexural characteristics of plastic hinges at the ends.
h
E I
4 F c
2 2EM t sin 2
h
4
EF I b L
EM t sin 2
Am=(Lmt)
-
Moment curvature analysis for RC sections
Under flexure forces, internal strain in a member varies along the depth of cross section; the slope of strain with depth is the curvature. For linear materials, the moment of resistance increases linearly with increase in strain in the extreme fiber. However, for nonlinear materials, the moment curature relationship becomes nonlinear.
Table 2: Moment curvature values for beam (300X450)
Points
Moment/SF
Curvature/SF)
A (Origin)
0
0
B (Yeilding)
1
0.009129132
C (Ultimate)
1.744049258
0.012838225
D (Strain hardening)
0.2
0.012838225
E (Strain hardening)
0.2
0.136936984
h is length of the contact between wall and column and l is the length of contact between all and beam where, Em and Ef are Elastic modulus of the masonry wall and frame material, t, h and L are thickness , height and length of the infill wall .
The comparative analysis carried out for the models with wall as a membrane and wall modeled as equivalent diagonal strut shows the similar results, therefore in the present study width of strut is calculated as per the formula obtained by Stafford Smith and Hendry .
Reduction factor for infill walls with central opening
The unreinforced masonry infill walls with central openings are modeled as pin-jointed single equivalent diagonal strut of reduced width, by applying the reduction factor for the width equivalent diagonal strut, modeled for infill wall without opening. And the reduction factor, given in the clause 7.10.2.3 of Proposed Draft Provision and Commentary on Indian Seismic code IS 1893 (Part 1), [Jain and Murty] is considered and given as below.
w 1 2.6xao . Where,
w Reduction factor.
Fig.6: Moment Curvature curve for beam.
Table 3: Moment curvature values for column
ao
Points
Moment
Curvature
A (Origin)
0
0
B (Yielding)
1
0.00123
C (Ultimate)
1.044
0.01623
D (strain hardening)
0.2
0.01623
E (strain hardening)
0.2
0.01845
Percentage of central opening, i.e. the ratio of area of
opening to the area of infill.
Fig.7: Moment Curvature relations for Column
-
-
RESULTS AND DISCUSSIONS
-
Performance Evaluation of Building Models.
Performance based seismic evaluation of all the models is carried out by nonlinear static pushover analysis (i.e Response spectrum pushover analysis).
-
Performance Point and Location of Hinges
The base force, displacement and the location of the hinges at the performance point, for various performance levels along longitudinal direction for all building models are presented in the Table 2 and Table 3.
Table 2: Performance point and location of user defined hinges for brick masonry infill for five storeyed building models by response spectrum pushover analysis
Model No.
Performance Point
Location of Hinges
Displacement mm
Base Force kN
A-B
B-IO
IO – LS
LS-CP
CP to E
Total
1
Yield
34.857
2067.023
828
132
0
0
0
960
Ultimate
224.31
3386.545
598
26
16
136
184
960
2
Yield
16
11021.146
890
70
0
0
0
960
Ultimate
80.6
25837.975
837
51
45
6
21
960
3
Yield
20.88
8873.335
878
82
0
0
0
960
Ultimate
83.36
20763.605
775
107
35
13
30
960
4
Yield
21.146
8540.246
883
77
0
0
0
960
Ultimate
87.46
19984.176
767
97
49
12
35
960
Table 3: Performance point and location of user defined hinges for brick masonry infill for eight storeyed building models by response spectrum pushover analysis
Model No.
Performance Point
Location of Hinges
Displacement mm
Base Force kN
A-B
B-IO
IO – LS
LS-CP
CP to E
Total
1
Yield
41.618
2568.347
1342
194
0
0
0
1536
Ultimate
233.1
4852.016
958
62
64
66
386
1536
2
Yield
24.55
15410.14
1451
85
0
0
0
1536
Ultimate
83.76
36059.73
1375
85
57
2
17
1536
3
Yield
21.64
13910.15
1451
85
0
0
0
1536
Ultimate
89.366
32551.17
1391
65
38
17
25
1536
4
Yield
23.07
12501.56
1459
77
0
0
0
1536
Ultimate
95.28
29039.73
1376
79
17
16
48
1536
The base force is more in soft storey building compared to the bare frame building models. As the stiffness of the building decreases with increase in the percentage of central openings for brick masonry infill, the base force at performance point decrease.
As the percentage opening increases from 10% to 30% the base force decreases at yield and ultimate state. For five storeyed building models, there is decrement in the base force at the ultimate state from model 2 to model 4 is 1.17% and 0.96% for brick masonry infill by response spectrum
pushover analysis. For eight storeyed building models, there is decrement in the base force at the ultimate state from model 2 to model 4 is 2.15% and 2.11% for brick masonry infill by response spectrum pushover analysis.
The locations of te hinges formed at the performance point, displacement and base force at ultimate state are shown in the Table 2 and Table 3. In most of the buildings, plastic hinges are formed in the first storey because of open ground storey. The plastic hinges are formed in the beams and columns.
For five storeyed building models, from the above Table 2 it can be observed that, the hinges are formed within the life safety range at the ultimate state is 80.83%, 97.81%, 96.87%, and 96.35% for infill as brick masonry infill by response spectrum pushover analysis method. We can also observed that, the hinges are formed beyond the CP range at the ultimate state is 19.16%, 2.18%, 3.12,and 3.65% for as brick masonry infill by response spectrum pushover analysis method.
For eight storeyed building models, from the above Table 3 it can be observed that, the hinges are formed within the life safety range at the ultimate state is 74.86%, 98.89%, 98.37%, and 96.87% for infill as brick masonry by response spectrum pushover analysis method. We can also observed that, the hinges are formed beyond the CP range at the ultimate state is 25.13%, 1.1%, 1.62%, and 3.12% for as brick masonry infill by response spectrum pushover analysis method.
From the above results it can be concluded that, as the stiffness of infill wall is considered in the soft storey buildings, base force is more than that of the bare frame building. The stiffness of the building decreases with the increase in percentage of central openings from 10% to 30%. The performance of all the building models is within the life safety range at the ultimate state for response spectrum pushover analysis method. These results reveal that, seismically designed multi storeyed RC buildings are safe to earthquakes. And as the collapse hinges are few, retrofitting can be completed quickly and economically without disturbing the incumbents and functioning of the buildings.
-
Ductility Ratio (DR)
Ductility ratio means it is the ratio of collapsed yield (CY) to the initial yield (IY) [23]. Ductility ratio (DR) of all the five, eight and storeyed building models are tabulated in the below Table 3 and Table 4.
The ductility of a structure is a one of the most important factors affecting its earthquake performance. One of the primary tasks of an engineer designing a building to be earthquake resistant is to ensure that the building will possess enough ductility to withstand the size and types of earthquakes it is likely to experience during its lifetime. In present study the ductility parameter is studied in order to know the behavior of the building under seismic loading.
Reinforced concrete structures for earthquake resistance must be designed, detailed and constructed in such a way that ductility factor will be at least 4 up to the point beginning of visible damage and even greater , to point of beginning of structural damage and limitation.
The structures can be classified depending on the different design ductility levels
-
Elastically responding structure, =1
-
Structures responding in ductile manner, >1 They can be further divided as,
-
Fully ductile structures with 4<<8
-
Structures with restricted ductility with 1.5 << 4
-
Table 3: Ductility ratio for five storeyed building models by response spectrum pushover analysis
Model No. |
Brick masonry infill |
||
IY |
CY |
DR |
|
1 |
34 |
229.31 |
6.74 |
2 |
16 |
80.60 |
5.03 |
3 |
20.88 |
83.36 |
3.99 |
4 |
21.14 |
87.46 |
4.13 |
Table 4: Ductility ratio for eight storeyed building models by response spectrum pushover
Model No. |
Brick masonry infill |
||
IY |
CY |
DR |
|
1 |
41.62 |
233.1 |
5.6 |
2 |
24.55 |
83.76 |
3.41 |
3 |
21.69 |
89.36 |
4.10 |
4 |
23.07 |
95.28 |
4.13 |
The lateral stiffness of the building increases the lateral strength, but reduces the energy absorption capacity of the building, hence ductility ratio decreases. From above result it is clear that the ductility ratio of the bare frame is larger than that of the soft storey building models.
For five storeyed building models, the ductility ratio are found more in bare frame building (model 1) compare to soft storey building (model 2) by 25.37% for brick masonry infill by response spectrum method. As the percentage of openings increases from 10% to 30% the ductility ratio increases from model 2 to model 4 by 17.89% for brick masonry infill by response spectrum method.
For eight storeyed building models, the ductility ratio is found more in bare frame building (model 1) compare to soft storey building (model 2) by 39% for brick masonry infill by response spectrum method. As the percentage of openings increases from 10% to 30% the ductility ratio increases from model 2 to model 4 by 17.43% for brick masonry infill by response spectrum method.
The ductility ratio is more in bare frame compare to the soft storey building models. And also from the above results reveal that, increase in openings increases the DR nearer or slightly more than the target value.
CONCLUSIONS
Based on the results obtained from different analysis for the various building models, the following conclusions are,
-
As the stiffness of the building decreases with the increase in the percentage of central opening varies from 10% to 30% from model 2 to model 4, the base shear decreases.
-
As the percentage of central opening increases, the lateral displacement increases.
-
For the response spectrum method, the storey drift is found to be within the limit for all building models.
-
The base force at performance point decreases with increases in the percentage of central openings from 10% to 30%.
-
Most of hinges are found within the life safety range at the ultimate state by response spectrum pushover analysis.
-
Ductility ratio are found more in the bare frame compare to the soft storey building models by response spectrum pushover analysis.
ACKNOWLEDGMENT
I feel words are not adequate to express gratitude to all our teacher, friends and family members. Lastly, I thank all those who directly or indirectly helped us to successfully complete this project.
REFERENCES
-
Mehmet Inel, Ozmen, H.B. (2006). Effects of plastic hinge properties in nonlinear analysis of reinforced concrete buildings. Engineering Structures-28, (ELSEVIER), p1494-1502.
-
K Rama Raju, A Cinitha and Nagesh R Iyer (2012), Seismic Performance Evaluation of Existing RC Buildings Designed as per Codes of Practice, Indian Academy of Sciences, Sadhana-Vol. 37, Part 2, April 2012, pp. 281297.
-
Cinitha A, Umesha P K,Iyer N R. (2012), Nonlinear static analysis to assess seismic performance and vulnerability of code-conforming RC buildings. Wseas Transaction on Applied and Theoretical mechanics. E-ISSN: 2224-3429, Issue 1, Volume 7, January 2012.
-
Das and murty. Brick masonry in eismic design of RC building: Behavior part 2, The Indian Concrete Journal, August 2004.
-
IS 1893 (Part 1): 2002 Indian Standard Criteria for Earthquake Resistant Design of Structures, Bureau of Indian Standards, New Delhi 110002.
-
6.Applied Tehnology Council, ATC 40,(1996),Seismic Evaluation and Retrofit of Concrete Buildings, Vol.1 and 2, California.
-
FEMA 356, 2000 Pre-standard and commentary for the seismic rehabilitation of buildings, ASCE for the Federal Emergency Management Agency, Washington, D.C.
-
IS 456-2000 Indian Standard Code of Practice for Plain and Reinforced Concrete,Indian Standards Institution, New Delhi110002.
-
Reinforced concrete design Limit State Book- Pillai and Menon.Published by abiravi on Sep 12, 2011
-
B P Annapurna and H SharadaBai Effect of Size of Openings within the Infill on the Member of Multistoreyed Infill Frame, Structure Engineering Convention, an International meet, IJARSE, Vol. No.3, Issue No.7, Dec 2006.
-
Mondal, G., and Jain S.K., Lateral Stiffness of Masonry Infilled Reinforced Concrete (RC) Frames with Central Opening, Earthquake Spectra, Vol 24, No3,page701-723august2008.
-
Praveen Rathod, Dr. S. S. Dyavanal. , Non-Linear Static Analysis of G+6 Storeyed RC Buildings with Openings in Infill Walls, IJERA, ISSN : 2248-9622, Vol. 4, Issue 9( Version 5), September 2014, pp.51- 58.
-
Syed Farooquddin, Renuka Devi M.V , K Madhavi and Manjunath.S, Lateral stiffness of infilled frame with door and window openings for varying modulus of masonry. International Journal of Advanced Engineering Technology (IJAET ), Vol.III, Issue IV, Oct.-Dec., 2012, p123-125.
-
Nikhil Agrawal, Prof.P.B Kulkarni, Pooja Raut, Analysis of infilled masonry R.C.frame with and without openings including soft storey by using equivalent diagonal strut method. International Journal of Scientific and Research Publications, Volume 3, Issue 9, September 2013, ISSN 2250-3153.
-
Dr. S. N. Tande, Reshama M. Karad Performance Based Inelastic Seismic Analysis of Buildings International Journal of Latest Trends in Engineering and Technology (IJLTET), Vol. 2 Issue 4 July 2013, ISSN: 2278-621X.
-
Neena Panandikar Hede, K.S.Babunarayan, Effect of variation of plastic hinge length on the results of non-linear analysis International Journal of Research in Engineering and Technology (IJRET), IC-RICE Conference Issue, Nov-2013, eISSN:2319-1163, pISSN: 2321-7308.