Reliability Analysis of Circuit Breakerin the Nigerian 330-kV Transmission Network.

DOI : 10.17577/IJERTV3IS030541

Download Full-Text PDF Cite this Publication

Text Only Version

Reliability Analysis of Circuit Breakerin the Nigerian 330-kV Transmission Network.

1Ademola Abdulkareem, 2C. O. A. Awosope, 3A. U. Adoghe, 4Okelola. M. O

1,2,3Electrical and Information Engineering Department, School of Engineering, College of Science and Technology, covenant University, Ota, Nigeria

4Ladoke Akintola University, Ogbomosho, Nigeria.

Abstract This paper is concerned with using the fault analysis to establish the requirements for the proper selection of circuit breaker; A Case Study of Power Holding company of Nigeria (PHCN) 330-kV Transmission Grid System. The work is modelled for Fault Analysis and it is written in a flexible MATLAB programs to accommodate addition or reduction in the Transmission Grid System. It aimed at establishing the Circuit Breaker Capacity at any point in the system. The result is then compared with the existing circuit breaker capacity of PHCN 330-kV system. The short-circuit fault is simulated by combining a solution of algebraic equations describing the changes in the network with a numerical solution of the differential equations. Two MATLAB programs were written and simulated; one for Lord Flow study to know the pre-fault bus voltages based on Gauss-Seidel Method; the other for Short Circuit Studies which made use of Thevenins theorem application. The highest Circuit Breaker Capacity established by the result of this study is relatively lower and the investments needed for this are smaller compared with the normal practice with PHCN system. This reveals that PHCN system can be protected with this low capacity circuit breaker with a reduced cost effectiveness and equal sensitivity which is a break-through in terms of Circuit Breaker Capacity in the field of power system protection.

Keywords Fault studies, circuit breaker, 330kV transmission grid, MATLAB program, Gauss Seidel load flow solution

  1. INTRODUCTION

    The current trends of erratic power supply and system collapse in Nigeria have made this study a paramount importance to the nations power industry. The purpose of an electrical power system is to generate and supply electrical energy to consumers with reliability and economy. The operation of a power system is affected by disturbances that could be due to natural occurrences such as lightning, wind, trees, animals, and human errors or accidents. These disturbances could lead to abnormal system conditions such as short circuits, overloads, and open circuits. Short circuits, which are also referred to as faults, are of the greatest concern because they could lead to damage to equipment or system elements and other operating problems including voltage drops, decrease in frequency, loss of synchronism, and complete system collapse. There is, therefore, a need for a device or a group of devices that is capable of recognizing a disturbance and acting automatically to alleviate any ill effects

    on the system element or on the operator. Such capability is provided by the protection system. The protection system is designed to disconnect the faulted system element automatically when the short circuit currents are high enough to present a direct danger to the element or to the system as a whole. The objective of the system will be defeated if adequate provision for fault clearance is not made. The installation of switchgear alone is insufficient, discriminative protective gear, designed according to the characteristics and requirements of the power system must be provided to control the switchgear [1]. Security of supply, therefore, can be better by improving plant design, increasing the spare capacity margin and arranging alternative circuits to supply loads. Majority of the faults are unsymmetrical. However, the circuit breaker rated MVA breaking capacity is based on 3phase fault MVA. Since a 3phase fault inflicts greatest damage to the power system, except in a situation where a single line to ground fault is very close to a solidly grounded generators terminal. In this instance the severity of single line to ground fault is greater than that of 3phase balance fault.

  2. BRIEF REVIEW OF SHORT-CIRCUIT ANALYSIS

    Fault studies form an important part of power system analysis. In the context of electrical fault-calculation, a power system fault may be defined as any condition or abnormality of the system which involve the electrical failure of the primary equipment, the primary equipment implying equipment such as generators, transformers, busbars, overhead lines and cables and all other items of plant which operate at power system voltage (330kV for this case).

    Faults on power system are divided into three-phase balanced faults and unbalanced faults. The different types of unbalanced faults are single line-to-ground fault (LG), line-to-line fault (LL), and double line-to-ground fault (LLG). The problem consists of determining the voltages and currents during various types of faults. The information gained from fault studies are usedfor proper relay setting and coordination. The three-phase balanced fault (LLL) information is used to select and set phase relays.

    Majority of the faults are unsymmetrical and the current which a breaker must interrupt is usually asymmetrical since it still

    contains some of the decaying dc component [2]. However, the circuit breaker rated MVA breaking capacity is based on three-phase balanced fault MVA. Since a three-phase fault inflicts greatest damage to the power system, except in a situation where LG fault is very close to a solidly grounded generators terminal. In this instance the severity of single line to ground fault is greater than that of three-phase balanced fault.

    The condition of the power system during the fault condition can be explained from the equation for short circuit studies. The equation for the short circuit uses the sequence

    components theory in the method of calculation.

    Vp

    =

    GenIpo

    Bus p

    ypo

    In an attempt to establish short circuit studies, various forms

    Figure 1: A typical fault model at bus P

    of faults were simulated to obtain the current which the

    breaker must interrupt and comparison was made between LLL fault and LG fault either of which is likely to cause

    I po

    Pp jQ

    p

    *

    (3)

    greater damage to a power system. This current is properly called the required symmetrical interrupting capacity or simply the rated symmetrical short-circuit current. [3]

  3. PROBLEM FORMULATION (LOAD REPRESENTATION)

    During sub-transient period, power system loads, other than motors are represented by the equivalent circuit as static impedance or admittance to ground.The symmetrical three phase fault current in per unit is given by

    V p

    Where; Pp and Qp = the scheduled bus load.

    VP = the calculated voltage which can only be determined if Qip is given or known

    The injected current Ipo flows from bus P to ground, that is, to bus 0.

    The magnitude and power factor angle of Ipo remain constant.

    y I po .

    = 0

    (1)

    po V p

    Where 0 is the per unit Perfault bus voltage and =

    the p.u reactance to the point of Fault

    (4)

    The base current

    = ×103

    3

    (2)

  4. NETWORK PERFORMANCE EQUATION

    Where SB is the base MVA and VB is the line to line base voltage in kV

    The interrupting rating of a circuit breaker was specified in

    The Gauss-Seidel Method of solution used for the load flow

    equation can be applied to describe the performance of a network during a su-transient period, using the bus

    KVA or MVA.

    admittance matrix with ground as reference. The voltage

    From (2), it implies that the interrupting KVA equal 3 times

    equation for bus P is given by:

    the kV of the bus to which the breaker is connected times the current which the breaker must be capable of interrupting

    Pp

    jQp Lp

    p1

    k 1 '' k

    when its contact part. This current is of course, lowers than the momentary current and depends on the speed of the breaker [2].

    V p

    * YLpqV q q1

    V

    p

    1

    YLpqV q ….(5)

    q p1

    Also, for the purpose of short circuit analysis in order to select appropriate circuit breaker to clear a fault instantly before transient condition on a power system, pre-fault condition of the system (i.e, pre-fault voltages and currents) should be

    where;

    YLpq Y pq Lp ; Lp

    Pp jQ

    Y pp

    known and this can be obtained from the load flow solution for the power system. Detail of the initial value of the current for a constant current representation is obtained from model of

    Theterm

    p in equation (5) represents the load current at bus P.

    V

    *

    p

    fig 1.

    for the cons tantload current representation,

    Pp jQp k

    k

    | I po | p p…………………………………(6)

    V p *

    where;

    p

    the power factor angle,

    p

    and k the angle of voltage with respect to the reference.

    When the constant power is used to represent the load, (Pp jQp) Lp will be constant but the bus voltage Vp will change in

    o

    f

    V

    jX

    I ' '

    f

    ……………………………………………………..(9)

    Z

    any iteration [4]. When the load at bus P is represented by a

    static admittance to ground, the impressed current at the bus is TH

    zero and the

    Pp

    jQp Lp

    V

    *

    0

    p

    (7)

    1. COMPARISON OF SLG FAULT AND THREE- PHASE FAULT (LLL) CURRENTS

      This comparison[5]is necessary because of the earlier

      For a sub-transient analysis in short circuit studies, the parameters of equation (5) must be modified to include the effect of the equivalent element required to represent synchronous, induction and loads. The line parameters YLpq must be modified for the new elements and additional line parameter must be calculated for each new network element.

      V. METHOD OF SOLUTION

      The methods and concepts employed to implement this work includes:

      • Developing an algorithm and hence a programme for fault level calculation at the location of fault in a 330-kV transmission Grid system.

      • Determine the fault current for various types of fault simulation.

      • Recommend the appropriate circuit breaker capacity to clear any detected fault.

        Note that it is necessary to do a load flow calculation before one can proceed on fault analysis. This is important so as to know the pre-fault voltages and currents necessary for further calculation. The network representation for the short circuit studies includes among other things, the Grid components parameter i.e the generators system buses, transmission lines and transformers. Modification of the admittance matrix to impedance matrix is done on the load flow calculation [4] to reflect fault analysis.

        These pre-fault conditions can be obtained from the result of

        statement in this project study that single line-to-ground fault is more severe than that of 3-phase fault if the fault is located very close to the terminal of a solidly grounded generator.

        The fault impedance can be assumed to be zero because of the enormous effect of the fault current. In addition, if the impedances Z1, Z2 and Z0 are assumed to be pure reactances (X1, X2 and X0), then for a 3-phase fault.

        Ia

        E ………………………………………………………………….(10).

        1

        jX

        and that of sin gle line to ground fault is given as;

        I

        3E …………………………………………….(11).

        1

        2

        0

        a jX jX jX

        The three practical possibilities are as follow;

        1. Fault at the terminals of neutral solidly grounded generator, (for generator X0<< X1), and it is assumed that X1 = X2 for sub-transient condition which is the case for the short circuit studies. At this instance single line to-ground fault is more severe than a 3-phase fault

        2. If a generator is grounded through a reactance Xn, this does not have any effect on a 3-phase fault current, but a single line-to-ground fault will have a fault current:

          load flow solution by Gauss-Seidel iteration method using YBUS, the flowchart of which is illustrated in Fig.2.

          The pre-fault machine currents are calculated from load flow

          I a jX X

          3E

          2 X

          0 3X n

          1

          by Gauss-Seidel iterative method from:

        3. to this end the relative severity of 3-phase fault

          V

          I Pki

          jQ

          ki ;i 1,2,………., m…………………………………(8)

          and single line-to-ground fault will depend on the value of Xn.

          ki *

          ki

          where;

        4. For a fault on a transmission line (which is the case study) X0>> X1 so that for a fault on a line

        Pki

        Q

        and

        ki

        the scheduled

        or calulated

        machine real and

        sufficiently far away from the generator

        retaercmtiivnealst,er3-mphinasae l fapuoltwceurrsr.ent is more than single line-to-ground fault current.

        V

        ki

        * the last iteration

        voltage.

        m the number of machines in the system.

        The network is then modified to correspond to the desired representation for short circuit studies. Being a linear network of several voltage sources, further calculation can be computed by application of Thevnins theorem [5].

        Figure 2: Flow Chart for Load-Flow Solution: Gauss-Seidel Iteration

        Figure 3: Flow Chart for 3-Phase Symmetrical Fault

        3

        5

        14

        Beni

        Omotos

        120

        0.0

        0.0

        0.228

        n

        ho

        04

        36

        3

        5

        5

        18

        Beni

        Oshogb

        251

        0.0

        0.0

        0.954

        n

        o

        08

        76

        9

        3

        10

        8

        Sape

        Aladja

        63

        0.0

        0.0

        0.239

        le

        02

        19

        3

        11

        8

        Delta

        Aladja

        32

        0.0

        0.0

        0.239

        02

        19

        3

        12

        5

        Ikeja

        Benin

        280

        0.0

        0.0

        1.162

        10

        77

        0

        9

        12

        9

        Ikeja

        Aiyede

        137

        0.0

        0.0

        0.521

        04

        41

        9

        6

        12

        13

        Ikeja

        Papanlat

        30

        0.0

        0.0

        0.057

        o

        01

        09

        1

        1

        12

        14

        Ikeja

        Omotos

        160

        0.0

        0.0

        0.304

        ho

        05

        48

        7

        6

        12

        15

        Ikeja

        Akangb

        18

        0.0

        0.0

        0.257

        a

        02

        17

        2

        2

        12

        17

        Ikeja

        Egbin

        62

        0.0

        0.0

        0.257

        02

        17

        2

        2

        12

        18

        Ikeja

        Oshogb

        252

        0.0

        0.0

        0.521

        o

        04

        41

        9

        6

        13

        9

        Papa

        Aiyede

        60

        0.0

        0.0

        0.114

        lanto

        02

        18

        1

        2

        17

        16

        Egbi

        Aja

        14

        0.0

        0.0

        0.257

        n

        02

        17

        2

        2

        18

        9

        Osho

        Aiyede

        115

        0.0

        0.0

        0.437

        gbo

        04

        34

        1

        9

        18

        27

        Osho

        Jebba(T

        157

        0.0

        0.0

        0.597

        gbo

        S)

        05

        47

        6

        7

        20

        21

        Kadu

        Kano

        230

        0.0

        0.0

        0.874

        na

        08

        69

        2

        9

        20

        23

        Kadu

        Jos

        197

        0.0

        0.0

        0.748

        na

        07

        59

        0

        9

        20

        24

        Kadu

        Shiroro

        96

        0.0

        0.0

        0.364

        na

        03

        29

        4

        2

        23

        22

        Jos

        Gombe

        265

        0.0

        0.0

        1.01

        09

        81

        5

        24

        25

        Shiro

        Katamp

        144

        0.0

        0.0

        0.598

    2. RESULT OF SYSTEM MODELING

      There is a necessity to have the knowledge of pre-fault voltages and currents in order to proceed with the calculation of the fault currents and hence achieving the aims of the research study. Hereunder are one-line diagram of the existing National 330-kV Network (Fig.4) and the systems data(Table) employed in the load flow calculation:

      Figure 4: The 28-Bus System of the Nigerian Transmission 330-kV Grid as a Case Study [6]

      Table 1: Transmission line data on 33kV, 100MVA base (All values are in per unit) [7]

      BU S – NO FR O M

      B U S

      – N O T O

      FRO M BUS

      TO BUS

      LENG

      TH(km

      )

      R(

      pu)

      X(

      pu)

      ADMIT TANCE

      (b/2)

      1

      2

      Alao

      ji

      Afam

      25

      0.0

      09

      0.0

      07

      0.104

      1

      4

      Alao

      ji

      Onitsha

      138

      0.0

      49

      0.0

      42

      0.524

      3

      4

      New

      Have n

      Onitsha

      96

      0.0

      03

      0.0

      29

      2

      0.365

      4

      6

      Onits

      ha

      Okpai

      80

      0.0

      09

      0.0

      07

      0.104

      5

      4

      Beni n

      Onitsha

      137

      0.0

      04

      9

      0.0

      41

      6

      0.521

      5

      7

      Beni

      n

      Ajaokut

      a

      195

      0.0

      07

      0.0

      56

      0.745

      5

      10

      Beni n

      Sapele

      50

      0.0

      01

      8

      0.0

      13

      9

      0.208

      5

      11

      Beni

      n

      Delta

      107

      0.0

      02

      0.0

      19

      0.239

      ro

      e(Abuja

      )

      05

      2

      40

      1

      24

      27

      Shiro

      Jebba(T

      244

      0.0

      0.0

      0.927

      ro

      S)

      06

      70

      7

      2

      26

      28

      Beni

      Kainji

      734

      0.0

      0.0

      1.178

      n

      11

      94

      Kebb

      1

      2

      i

      27

      19

      Jebb

      Jebba(T

      8

      0.0

      0.0

      0.0322

      a(GS

      S)

      00

      02

      )

      3

      2

      28

      27

      Kain

      Jebba(T

      81

      0.0

      0.0

      0.308

      ji

      S)

      02

      24

      9

      6

      16

      IKEJA-WEST

      -5.1500

      -2.2900

      17

      AJAOKUTA

      0.0000

      0.0000

      18

      BENIN

      -2.4000

      -1.1200

      19

      ONITSHA

      -1.0200

      -0.4400

      20

      ALADJA

      -1.5600

      -0.8500

      21

      ALAOJI

      -2.1600

      -1.0400

      22

      NEW-HAVEN

      -1.1000

      -0.1800

      23

      AKANGBA

      -3.0750

      -1.5400

      24

      AJA

      0.0000

      0.0000

      25

      KATAMPE

      (ABUJA)

      0.0000

      0.0000

      26

      AIYEDE

      0.0000

      0.0000

      27

      PAPALANTO

      0.0000

      0.0000

      28

      OMOTOSHO

      0.0000

      0.0000

      Table 2; Voltage-Control Bus Data

    3. LOAD FLOW RESULTS

      BU

      S NO.

      BUS NAME

      QG

      QD

      QMI N

      QMA X

      VSP

      SLAC

      K BUS

      1

      KAINJI

      0.0000

      0.000

      2.790

      1.050

      0

      2.790

      0

      0

      0

      2

      JEBBA

      0.0000

      0.240

      3.230

      1.000

      0

      3.230

      0

      0

      0

      3

      SHIROR

      0.0000

      0.180

      2.000

      1.000

      O

      0

      2.000

      0

      0

      0

      4

      SAPELE

      0.0000

      0.000

      4.670

      1.000

      0

      4.670

      0

      0

      0

      5

      DELTA

      0.0000

      0.370

      3.430

      1.000

      (IV)

      0

      3.430

      0

      0

      0

      6

      AFAM

      0.0000

      0.000

      36700

      1.000

      (IV)

      0

      3670

      0

      0

      7

      EGBIN

      0.0000

      0.000

      5.820

      1.000

      0

      5.820

      0

      0

      0

      The bus-bar pre-fault voltage, pre-fault current and pre-fault powers, which flow out of the bus bars, are tabulated in Table 4 hereunder

      Table 3: Load Bus Data

      BUS NO

      BUS NAME

      ACTIVE

      REACTIVE

      POWER (PG)

      POWER (QG)

      8

      JEBBA (T.S)

      -0.7200

      -0.4300

      9

      BIRNIN- KEBBI

      -0.3900

      -0.1800

      10

      KADUNA

      -1.6100

      -0.8200

      11

      KANO

      -2.0400

      -0.8000

      12

      JOS

      -0.9800

      -0.3460

      13

      GOMBE

      -1.5300

      -1.0800

      14

      OSOGBO

      -1.5600

      -0.8800

      15

      IBADAN

      -1.8000

      -0.9300

      Table 4; Output of Load-Flow Results (in p.u )

      BUS NO.

      VOLTAGE

      POWER ANGLE

      POWER FLOW

      CURRENT

      1

      1.0500

      0.0000

      2.4787

      2.3605

      2

      1.0000

      -0.4060

      7.2392

      7.2394

      3

      1.0000

      -8.1200

      3.6954

      3.6954

      4

      1.0000

      12.9979

      7.0150

      7.0150

      5

      1.0000

      13.9877

      3.6998

      3.6998

      6

      1.0000

      18.2990

      4.4075

      4.4075

      7

      1.0000

      2.0316

      4.3869

      4.3869

      8

      1.1219

      -3.8503

      0.8403

      0.7443

      9

      1.0081

      -0.6090

      0.4238

      0.4208

      10

      1.0173

      -12.9984

      1.8070

      1.7760

      11

      1.0050

      -21.0013

      2.1898

      2.1982

      12

      1.0601

      -21.4268

      1.0387

      0.9522

      13

      1.0599

      -27.4552

      1.8735

      1.7563

      14

      1.0220

      -0.5700

      1.7934

      1.7518

      15

      1.0042

      -2.3010

      2.0273

      2.0202

      16

      0.9899

      -0.1259

      5.6455

      5.6960

      17

      1.0417

      10.4510

      0.0022

      0.0020

      18

      1.0201

      10.6305

      1.1065

      1.0860

      19

      1.0340

      11.9994

      0.4296

      0.4068

      20

      0.9980

      13.3385

      1.8026

      1.8015

      21

      1.0005

      17.3005

      2.4028

      2.4018

      22

      1.0350

      10.2956

      1.1223

      1.0764

      23

      0.9875

      -0.5500

      3.4326

      3.4798

      24

      1.0002

      2.0225

      0.0164

      0.0168

    4. RESULT OF SHORT CIRCUIT STUDIES

      In the short circuit studies, a base current of 174.9546A and a base voltage of 330kV are computed together with the load flow output result of the pre-fault condition in the input data for the various fault current calculations using the Power System Matlab Programming.[9].

      Simulations were made for different types of short circuit faults i.e, 3-phase fault; single line-to-ground fault, line- to-line fault and double line-to-ground fault. The summary of is shown in Table 5.

      MVAsc 3 phase 3 Vpf 1 I sc .

      where;

      MVAsc 3 phase 3 phase short circuit MVA.

      VALUE)

      Fault Current Result (IN ACTUAL

      Vpf 1 Pr e fault line voltage in kV.

      BASE CURRENT = 1,749.546kA BASE MVA = 100MVA

      BASE VOLTAGE = 330kV

      TABLE 5: TYPE OF FAULT (SUMMARY)

      I sc Short circuit current in kA.

      If voltages and currents are in per unit values on a 3-phase basis, then,

      MVAsc (3-phase) = |V|pre-fault x |I|sc xMVAbase

      BUS NO.

      3- PHASE

      SLG.

      LL.

      DLG

      1

      21878

      11296

      19335

      19684

      2

      11688

      4321

      9897

      10369

      3

      12082

      6345

      9879

      9802

      4

      15568

      8442

      12680

      12582

      5

      9157

      4913

      7723

      7675

      6

      2312

      1382

      2255

      2196

      7

      24989

      13021

      21958

      22013

      8

      2228

      1180

      2012

      2032

      9

      10012

      5014

      9146

      8887

      10

      5826

      2798

      4988

      5102

      11

      1895

      894

      1687

      1698

      12

      1768

      852

      1485

      1551

      13

      1062

      598

      986

      993

      14

      8896

      4140

      7734

      7984

      15

      28984

      13982

      24968

      25437

      16

      21787

      9603

      18475

      19004

      17

      5719

      2870

      4970

      5042

      18

      20593

      10143

      18042

      18275

      19

      3678

      1830

      3234

      3290

      20

      9006

      4367

      7911

      7960

      21

      2218

      1150

      2019

      2050

      22

      2462

      1146

      2203

      2239

      23

      25432

      11951

      22204

      22597

      24

      20998

      10246

      18269

      18804

      For example: The Short Circuit Current from the output result of the program for the short circuit studies is 29036A with a pre-fault voltage of 331.4520kV.

      MVAsc 3 phase 3 Vpf 1 I sc .

      3 330kV 28,971kA

      16,559MVA

      From the summarized result in Table 5 above, it can be inferred that 3-phase fault causes greatest magnitude of fault current to the system and hence, should be a point of reference upon which the circuit breaker to clear faults on 330kV transmission line is based.

    5. CONCLUSION AND RECOMMENDATION

      To select the most appropriate size of Circuit Breaker for the Grid System, it has to be borne in mind that rated momentary current and rated symmetrical interrupting currents are required for the computation of circuit breaker ratings. Symmetrical current to be interrupted is computed by using sub-transient reactance for synchronous generators. Momentary current (rms) is then calculated by multiplying the symmetrical momentary current by a factor of 1.6 to account for the presence of D.C. offset current.

      The 3-phase short circuit MVA to be interrupted can be computed as in the following equation [8]

    6. CONCLUSION

      From the above, and as a result of the research study, it can be concluded that the Circuit Breaker capacity for PHCN 330kV Transmission Grid should be 20,000MVA. The research result is a break-through in terms of Circuit Breaker Capacity in the field of Power System Protection.

      The Birnin-Kebbi bus (B8) on which the receiving end voltage is higher than the sending end voltage, it is agreed upon and confirmed that the line is an open-ended one. This is what causes the abnormality. The solution to it is to connect a reactor to the line.

    7. RECOMMENDATIONS

From the Nameplate of a Sf6 Gas Circuit Breaker (manufactured by GEC ALSTHOM T & D) on 330kV Transmission Line at the Area Transmission station in Osogbo:

Line Voltage VL = 362kV, Frequency f = 50Hz,

Short Circuit Current Isc = 40kA Line Current IL = 400A,

Current Interruption Capacity = 3,150A.

From the above data, the capacity of the Circuit Breaker is calculated to be 25,080.09569MVA. This is too high compared with the result of this project (i.e, 20,000MVA capacity) and it will be expensive in term of cost. The higher value of 25,080.09569MVA apart from cost, it will be more insensitive to any fault detected.

It is therefore recommended that the result of this paper should be of value to PHCN in the daily operation of the National Grid.

REFERENCES

  1. W. D. Stevenson, Element of Power System Analysis, McGraw-Hill New York, 1982.

  2. J. J. Grander, and W. D. Stevenson, PowerSystem Analysis, New York.

    McGraw-Hill, 1994

  3. H. Saadat Power System Analysis Published by McGraw-Hill publishing company limited, New

    York 2006.

  4. Braess, D. and Grebe, E. A. Numerical Analysis of load-Flow Calculation Methods, .IEEE Trans,

    1981 July, No. 7, Vol. Pas-100, pp. 3642-3647.

  5. B. R. Gupta, Power System Analysis and Design, Revised Edition, 2011

  6. PHCN National Control Centre Oshogbo, 2010, one line diagram of the 28 bus systems of Nigerian

    Transmission 330-kV Grid

  7. PHCN Line Parameters for 330-kV Circuits, 2011.

  8. I. J. Nagrath and D. P. Kothari, Power System Engineering, Fifth Print, 1998

  9. Brown, H. W., et al, Digital Calculation of Three-Phase Short Circuits by Matrix Method, AIEE Trans, 1960, Vol. 79, pp. 1277

Leave a Reply