Modeling of Transformer DGA using IEC & Fuzzy Based Three Gas Ratio Method

DOI : 10.17577/IJERTV3IS091128

Download Full-Text PDF Cite this Publication

Text Only Version

Modeling of Transformer DGA using IEC & Fuzzy Based Three Gas Ratio Method

Mr. Hemant V. Waghmare

Assistant Engineer, Public Works Department Government .of Maharashtra

Pune, India

Prof. Mrs. Haripriya H. Kulkarni

Associate Professor, Electrical Department,

    1. Society's Modern College of Engineering Pune, India

      Abstract Monitoring of incipient faults taking place in the transformers is very helpful to avoid the accidents, shut downs or financial loss associated with it. Dissolve gas analysis is the method which is widely used for this purpose. The DGA is carried out on the insulting oil of transformer. Various diagnosis methods are available for DGA as per different standards. And with the aid of Artificial intelligence techniques the accuracy of diagnosis can be improved. This paper presents a survey that has been done to collect the DGA samples. An Intelligent fuzzy based analysis is done using MATLAB. Validation of the software model is found to be satisfactory in comparison with IEC standard & actual survey report

      Keywordsdga, IEC three ratio method,Fuzzy based three ratio method.

      1. INTRODUCTION

        Transformer plays vital role in Power industry

        .Operation of transformers free from faults is important for safety and economy. Most of power transformers used in industries is oil filled, and primary insulation used in it is Kraft paper, wood, porcelain and mineral oil. A failure occurs in the transformer when the insulation system becomes weak to extent that it can no longer act as an insulator to the high voltage to which it is subjected.

        The various factors involves in degradation of insulation are overvoltage, overheating, ageing, environmental conditions etc. Due to this electrical & thermal stresses certain gases are produced. Hydrogen (H2), methane (CH4), acetylene (C2H2), ethylene (C2H4) and ethane (C2H6) are the gases produced due to oil decomposition, whereas carbon monoxide (CO) and carbon dioxide (CO2) are the gases produced due to paper decomposition.

        Dissolve gas Analysis is a very efficient method for monitoring the gases in early stage which helps to identify the incipient faults developing in transformer. Concentrations, gas ratios & gassings rates of various gases are useful in concluding the type of fault present or developing in the transformer. In order to carry out DGA, Oil Sample from transformer are taken and sent to laboratory for analysis with the help of gas chromatography. Oil samples can be taken without de-energizing the transformer. With the advent of technology some transformer monitoring devices are developed which enables the maintenance person to take the corrective decisions with the help of real time readings of various parameters associated with transformer. In classical

        method the interpretation of the result to diagnosis the fault in power transformer depends upon the experience of human experts. Some time a high degree of deviations and vagueness have absorbed regarding interpretation of result by different human experts.

        This paper presents various processes involved with gas generation related with faults, various DGA Diagnosis methods. Further this project presents an effective method for accurate diagnosis of various faults in transformer with the help of Fuzzy logic in coordination with the conventional IEC three ratio method.

      2. TRANSFORMER FAULTS AND GASES ASSOCIATED WITH IT ASE OF USE

        Gases are generated in insulating oil due to breaking of chemical bonds present in hydrocarbon molecules. The energy required for breaking the chemical bonds is obtained from the energy present in transformer faults.

        Four basic types of faults in the transformer are:

        1. Arcing or high current break down.

        2. Low energy sparking or partial discharges.

        3. Localized overheating or hot spots and,

        4. General overheating due to inadequate cooling or sustained overloading

          Above listed faults are responsible for thermal degradation of oil or combination with paper insulation. Different amount of gases are evaluated like hydrocarbons, hydrogen, carbon, oxides as per the fault type.

          TABLE I. TRANSFORMER FAULTS & ITS ASSOCIATED GASES

          Type of Fault

          Gases Evaluated

          Heavy current arcing

          Hydrogen and Acetylene

          Arcing involving paper

          insulation

          oxide of carbon

          Partial discharge

          hydrogen and lower order

          hydrocarbons

          Localized heating or hot spot

          methane and ethane

          Prolonged overloading or

          impaired heat transfer

          Carbon monoxide and

          Carbon dioxide

          below.

      3. METHODS OF DISSOLVE GAS ANALYSIS Various methods of diagnosis available are listed

        1. Key Gas method

          In this method the concentration and gassing rates of the key hydrocarbon gases are monitored. The concentrations are expressed in ppm (parts per million). The normal operating concentration of these key gases according to IEC 60599

        2. Total Dissolved Combustible Gases (TDCG)

          It is the sum of concentrations of all the combustible gases. It indicates the insulation deterioration. The typical limits are defined for the diagnosis of the faults in transformer insulation.

        3. Duval Triangle

          The Triangle is graphical method of representation and is used to visualize the different cases and facilitate their comparison .

        4. Ratio method

          This method is the most widely used method for the fault interpretation. In this method ratios of gas concentrations are used for the interpretation purpose. Roger ratio method, Dorrenburg ratio method, and IEC ratio methods are used by the utilities.

          1. IEC Three Gas Ratio Method-

        .

        IEC Three ratio is the most commonly used Industry standard method. The ratios of certain gases are used for diagnostic techniques. These techniques were standardized by IEC in 1978 in Guide for Interpretation of the Analysis of Gases in Transformer and Other Oil Filled Electrical Equipment in Service .The individual gases used to determine each ratio and its assigned limits are shown in Tables 3. Codes are then allocated according to the value obtained for each ratio and the corresponding fault characterized.

        TABLE II. CODING FOR GAS RATIOS

        Sharply defined ranges of the gas

        ratio

        Codes of different gas ratios

        R1

        R2

        R3

        C2H2/C2H4

        CH4/H2

        C2H4/C2H6

        <0.1

        0

        1

        0

        0.1-1

        1

        0

        0

        1-3

        1

        2

        1

        >3

        2

        2

        2

        TABLE III. GAS RATIOS & ITS ASSIGNED LIMITS.

        No.

        Fault type

        C2H2/C2H4

        CH4/H2

        C2H4/C2H6

        1

        No fault

        0

        0

        0

        2

        Partial discharges of low energy density

        0 (but not significant)

        1

        /td>

        0

        3

        Partial discharges of high energy density

        1

        1

        0

        4

        Discharges of low energy density

        1 or 2

        0

        1 or 2

        5

        Discharges of high energy density

        1

        0

        2

        6

        Thermal fault of low temperature <150C

        0

        0

        1

        7

        Thermal fault of low temperature 150-300

        C

        0

        2

        0

        8

        Thermal fault of medium temperature 300 -700C

        0

        2

        1

        9

        Thermal fault of high temperature >700 C

        0

        2

        2

        This method is generally based on the empirical experience and sometimes fails to give accurate diagnosis of faults. Sometimes the results do not match with existing codes; also in case of multiple faults confusion is created in ratios between different gases due to mixing of gases which leads toward unsuccessful diagnosis.

      4. ARTIFICIAL INTELLIGENCE TECHNIQUES FOR DGA Fault interpretation from DGA is relayed on the

        human expertise & past experience. To improve the interpretation accuracy of DGA, Artificial intelligence techniques are applied. This technique makes use of collection of data including DGA results, past fault and some standard methods used for diagnosis.

        Various AI techniques used for DGA are Artificial Neural Network (AAN), Fuzzy Interface System (FIS), Genetic Algorithm (GA),Bayesian Network (BN), Self Organizing Map (SOM), Extended Relation Function (ERF) and Discrete Wavelet Network (WNs) etc which improves the accuracy of diagnosis of DGA.

        1. Fuzzy Three Ratio Method

          Through the combination of fuzzy logic and IEC Three Ratio method, this paper puts forward Fuzzy Three Ratio Method. It fuzzifies the coding boundary, thus overcomes the drawbacks of coding boundary sharp changing.

          Fuzzification of The Three Ratios

          According to Table2, three gas ratios, R1 = Acetylene (C2H2) / Ethylene (C2H4), R2 = Methane (CH4) /

          Hydrogen (H2), and R3 = Ethylene (C2H4) / Ethane (C2H6); can be coded as 0, 1, and 2 for different ranges of ratios.

          In this method, IEC codes 0, 1, 2 are replaced by fuzzy sets ZERO, ONE, TWO, each gas ratio can be represented by a fuzzy vector [ ZERO (R), ONE (R), TWO

          1. ], where ZERO (R), ONE (R), TWO (R)are the membership function of the fuzzy set ZERO, ONE, TWO.

            In the following, R1 is taken as an example to explain how to transfer IEC codes 0, 1, 2 into fuzzy set ZERO, ONE, and TWO.

            1. The membership function of fuzzy set ZERO is:

              ZERO (R1) = 1 R1 0.08

              = e-50 ( R1 – 0.08 ) R1 > 0.08 (1)

              Fig.1 The fuzzification process of code 0 for R1

            2. The membership function of fuzzy set ONE is

              ONE (R1) = 0 R1 0.08

              = 0.5 + 0.5 sin (25 (R1 – 0.1)) R1 (0.08, 0.12)

              = 1 R1 (0.12, 2.9)

              = 0.5 – 0.5 sin (5 (R1 – 3)) R1 (2.9, 3.1)

              = 0 R1 > 3.1

              (2)

              Fig. 2 The fuzzification process of code 1 for R1

            3. The membership function of fuzzy set TWO is

          TWO (R1) = 0 R1 2.85

          = e-12 ( R1 – 2.85 ) R1 > 2.85 (3)

          Similarly, the three fuzzy membership functions for R2 can be obtained as follows:

          The membership function of fuzzy set ZERO is:

          ZERO (R2) = 0 R2 0.08

          = 0.5 + 0.5 sin (25 (R2 – 0.1)) R2 (0.08, 0.12)

          = 1 R2 (0.12, 0.9)

          = 0.5 – 0.5 sin (5 (R2 – 1)) R2 (0.9, 1.1)

          = 0 R2 > 1.1 (4)

          The membership function of fuzzy set ONE is:

          ONE (R2) = 1 R2 0.08

          = e-50 ( R2 – 0.08 ) R2 > 0.08 (5)

          The membership function of fuzzy set TWO is:

          TWO (R2) = 0 R2 0.85

          = e-12 ( R2 – 0.85 ) R2 > 0.85 (6)

          Similarly, the three fuzzy membership functions for R3 can be obtained as follows:

          The membership function of fuzzy set ZERO is:

          ZERO (R3) = 1 R3 0.85

          = e-50 ( R3 – 0.08 ) R3 > 0.85 (7)

          The membership function of fuzzy set ONE is:

          ONE (R3) = 0 R3 0.9

          = 0.5 + 0.5 sin (25 (R3 – 1)) R3 (0.9, 1.1)

          = 1 R3 (1.1, 2.9)

          = 0.5 – 0.5 sin (5 (R3 – 3)) R3 (2.9, 3.1)

          = 0 R3 > 3.1 (8)

          The membership function of fuzzy set TWO is:

          TWO (R3) = 0 R3 2.85

          = e-12 ( R3 – 2.85 ) R3 > 2.85 (9)

        2. The Diagnosing Steps Involved in Fuzzy Three ratio Method-

        Step1: From the DGA report input values of gas concentrations of key gases from oil sample in ppm.

        Step 2: Calculate three ratios R1 = Acetylene (C2H2) / Ethylene (C2H4), R2 = Methane (CH4) / Hydrogen (H2), and

        R3 = Ethylene (C H ) / Ethane (C H ).

        2 4 2 6

        Fie.3 The fuzzification process of code 2 for R1

        Figure 1,2,3 are the representation of fuzzification process of code 0, 1 and 2 for R1.

        Step 3: Calculate the three fuzzy membership functions of each ratio based on equations listed in above section.

        Step 4: As for the conventional logic AND and OR used in the conventional IEC diagnosis, replace AND by

        "min", OR by "max", the fuzzy diagnosing vector F(i) where i = 1,2,,9 represent ith fault in Table.3 is

        determined by the following equations:

        F (1) = min [ ZERO (R1), ZERO (R2), ZERO (R3) ]

        9

        1599

        651

        81.2

        998.9

        421

        5

        5

        5

        10

        346

        114

        29

        49.9

        60

        4

        4

        4

        11

        57

        58

        74

        29

        31

        3

        N

        3

        12

        54.6

        38.2

        4.98

        54.8

        49.4

        5

        5

        5

        13

        173

        341

        169

        814

        41

        9

        9

        9

        14

        35.01

        19.98

        3.4

        45

        20

        5

        5

        5

        15

        114

        36

        8.4

        24.2

        43

        4

        4

        4

        16

        33.9

        25.98

        6.1

        5.4

        0.2

        1

        1

        1,2

        17

        198

        703

        249

        745

        2

        8,9

        8

        8,9

        18

        1270

        3450

        520

        1390

        8

        8

        8

        8

        F (2) = min [ ZERO (R1), ONE (R2), ZERO (R3) ]

        F (3) = min [ ONE (R1), ONE (R2), ZERO (R3) ]

        F (4) = max ( min [ ONE (R1), ZERO (R2), ONE (R3) ]

        min [ TWO (R1), ZERO (R2), ONE (R3) ]

        min [ TWO (R1), ZERO (R2), TWO (R3) ] )

        F (5) = min [

        ONE

        (R1),

        ZERO

        (R2),

        TWO

        (R3) ]

        F (6) = min [ ZERO (R1), ZERO (R2), ONE (R3) ]

        F (7) = min [ ZERO (R1), TWO (R2), ZERO (R3) ]

        F (8) = min [ ZERO (R1), TWO (R2), ONE (R3) ]

        F (9) = min [ ZERO (R1), TWO (R2), TWO (R3) ]

        Step 5: ault type out of the 9 listed faults is determined.

        Step 6: Results are displayed in graph window for gas content in ppm, and Fuzzy Three Ratio Method decision.

      5. RESULTS AND ALANLYSIS

DGA results of 18 different oil samples are taken, and these values are applied to MATLAB Scripts that are programmed separately for Conventional IEC Three Ratio Method and Fuzzy Three Ratio Method and results are presented below.

From these 18 samples 3 results give no diagnosis, 2 results Fails to diagnose correct fault and 1 result fails to diagnose multiple faults using IEC Three Ratio Method, Hence provides 66.67 % accuracy. Whereas Fuzzy Three Ratio Method provides 1 fault which fails correct diagnosis, and one fault in which wrong multiple faults out of the 18 results hence provides 88.89 % Accuracy Therefore it shows that this proposed method is more appropriate.

TABLE IV . COMPARATIVE ANALYSIS OF RESULTS OF IEC THREE RATIO & FUZZY THREE RATIO METHOD WITH ACTUAL FAULTS RECORDED.

CONCLUSION

This paper proposes transformer fault diagnose method which is an improvement of IEC three ratio Method with the help of Fuzzy logic. This method proves its accuracy by diagnosing the correct fault or multiple faults which conventional IEC method fails to diagnose. The programming associated with this fuzzy logic is comparatively simple and easy for modification.

REFERENCES

  1. CS Chang, CW Lim, and Q Su, Fuzzy-Neural approach for Dissolved Gas Snalysis of Power Transformer Incipient Faults, in Australasian Universities Power Engineering Conference (AUPEC 2004), 26-29 September 2004, Brisbane, Australia.

  2. Hongzhong Ma, Zheng Li, P.Ju, Jingdong Han, and Limin Zhang, Diagnosis of Power Transformer Faults Based on Fuzzy Three-Ratio Method, in The 7th International Power Engineering Conference, IPEC 2005, Nov 2005.

    Sr no.

    Hydrogen (H2)

    Methane (CH4)

    Ethane (C2H6)

    Ethylene (C2H4)

    Acetylene (C2H2)

    Actual fault Type

    BY IEC

    Three Ratio

    By Fuzzy based Three

    1

    154

    149.71

    113.94

    76

    6.08

    7

    1

    3,4

    2

    9340

    995

    60

    60

    7

    3

    N

    3

    3

    305

    100

    33

    161

    541

    4

    4

    4

    4

    183

    259

    209

    531

    0

    8

    8

    8

    5

    134

    134

    157

    45

    0

    4

    7

    4

    6

    94

    76

    43

    61

    3.7

    6

    6

    6

    7

    69.9

    70

    29.03

    139.9

    9.98

    9

    9

    9

    8

    298

    498

    179.6

    358

    94

    8

    N

    8

  3. Naveen Kumar Sharma, Prashant Kumar Tiwari, and Yog Raj Sood, Review of Artificial Intelligence Techniques Application to Dissolved Gas Analysis on Power Transformer, in International Journal of Computer and Electrical Engineering, August 2011, vol. 3, No. 4, pp. 577582.

  4. Rahmatollah Hooshmand, and Mahdi Banejad, Application of Fuzzy Logic in Fault Diagnosis in Transformers using Dissolved Gas based on Different Standards, in Proceedings of World academy of science, engineering and technology, Dec. 2006, vol. 17, ISSN 1307-6884, pp. 157161.

  5. Nandkumar Wagh and D.M.Deshpande, Performance Assessment of Supervised and Unsupervised Neural Networks as Applied to Transformer Fault Diagnosis in International Journal of Advanced Research inComputer Science and Software Engineering Volume 3, Issue 10, October 2013, ISSN: 2277 128X.

  6. R. Naresh, Veena Sharma, and Manisha Vashisth, An Integrated Neural Fuzzy Approach for Fault Diagnosis of Transformers, IEEE transactions on power delivery, October 2008, vol. 23, no. 4, pp. 2017 2024.

Leave a Reply