Identification of Power Quality on EAF using Wavelet Transform based on Actual Recorded Data

DOI : 10.17577/IJERTV4IS070937

Download Full-Text PDF Cite this Publication

  • Open Access
  • Total Downloads : 239
  • Authors : Wahyuni Martiningsih, Mochamad Ashari, Adi Soeprijanto, Rocky Alfanz
  • Paper ID : IJERTV4IS070937
  • Volume & Issue : Volume 04, Issue 07 (July 2015)
  • DOI : http://dx.doi.org/10.17577/IJERTV4IS070937
  • Published (First Online): 31-07-2015
  • ISSN (Online) : 2278-0181
  • Publisher Name : IJERT
  • License: Creative Commons License This work is licensed under a Creative Commons Attribution 4.0 International License

Text Only Version

Identification of Power Quality on EAF using Wavelet Transform based on Actual Recorded Data

Wahyuni Martiningsip,2, Mochamad Ashari1, Adi Soeprijanto1, Rocky Alfanz2

1 Departement of Electrical Eng.,Sepuluh Nopember Institute of Tech. Surabaya, Indonesia

2 Departement of Electrical Eng, Sultan Ageng Tirtayasa University, Cilegon, Indonesia

Abstract This paper presents disturbance voltage identification based on actual data recorded of electric arc furnace load. The identification of disturbance used wavelet transformation. The proposed method can precisely identify disturbance caused by operation of an electric arc furnace (EAF). The identification procedure consists of 4 steps: measurement of voltage eaf, normalization of actual data recorded, transformation wavelet and wavelet energy calculation. The result of transformation wavelet analyzed for identification of disturbance which occurrence. The types disturbance detected are unbalance voltage. From calculation of energy wavelet, shown the wavelet energy average Va, Vb and Vc are 0.14842, 0.04884, and 0.09926 respectively.

Keywords- Power Quality; Disturbance of Voltage; Wavelet Transform; Wavelet Energy; Eaf

  1. INTRODUCTION

    Electrical disturbance problem often occurs on the distribution system, especially in industrial areas. The disturbances can disrupt the production process internally or outside sources. Electrical disturbances associated with power quality, which include blackouts, power factor, harmonics, sags, swells, and unbalanced conditions [1][2][3][4]. A satisfied quality of power is required for sensitive equipment to work normally. When the quality of power reduced below the standard, the circuit breaker opens so can reducing the power factor [5]. The importance disturbances that are considered include voltage stabilization, continuity, and waveform. The voltage stability is identified such as under-voltage, over-voltage, voltage sag, voltage swell, phase shift, flicker and frequency. The continuity problems terms the momentary interruption, temporary interruption, and sustained interruption, transient, three phase voltage unbalance, harmonic voltage, current notch [6]. Voltage sags are reduction the rms value of voltage with short duration, it can be characterized by residual voltage and duration[4]. IEEE Standard 1159 defines voltage sag as reduction in the rms voltage between 0.1 and 0.9 p.u. of the nominal voltage, for duration of 0.5cycle to 1 min.[7]. Power quality problems causes equipment damage, under and over voltage. The under voltage and over voltage occurs in long duration voltage variation or in short-duration voltage variation. Electric arc furnace (eaf) is a typical furnace used

    in many steel making company. The furnace is fed by sponge steel, scraps steel, or recycled steel to form steel processed [8]. Three fundamental changes in the operation of electric arc furnace, which can produce disturbance voltage in the power system, like short-circuit, open circuit condition, and normal operation [9]. The operation of the eaf causes electrical short circuit internally between phase and scrap. This process can decrease the quality of electricity. Voltage sags and swells frequently occur. The harmonic distortions also appear due to the process in EAF. Power transformers become overheating, dips on lighting systems, and failure if the dip voltage is deeper than 35% . To identify the internal short circuit process in EAF become very interesting topics, followed by action for compensation. Researchers have published topics in improvement of power quality in weak grid system and weak grid characteristics [10][11]. This paper discusses a method to identify power quality due to Electric Arc Furnace operation. It analyses the power quality characteristics using wavelet transformation. The WT approach prepares a window that simultaneously gives proper resolutions in both the time and the frequency domain [12]. The wavelet transforms disturbance signals into approximate signal and detail signal [13]. The wavelet method is suitable for transforming event which occurs in a short duration.

  2. IDENTIFICATION METHOD

    The short circuit, which occurs inside the EAF, is identified applying 4 steps: measurement of voltage in eaf system using power quality analyzer, normalized data recorded, discrete wavelet transformation, calculation wavelet energy. The flowchart is illustrated in Figure 1.

    B. Wavelet Transformation

    Wavelet transformation has the objective to detect any disturbance. This paper used discrete wavelet transform (DWT) with wavelet daubechies as mother wavelet. Transformed signal is voltage V (positive sequence phasor). Original signal is decomposed into approximation and detail signals [7][9]. Wavelet orthogonal consist scaling function (x)) and wavelet function (( (x)) in equation (2)

    ak

    (x) J 1

    t 0

    (x) J 1

    (2x t)

    (2x t)

    (2)

    bk

    t 0

    Fig. 1. Flowchart System

    A. Recorded Data

    The data which use in this study obtain from measurement at the PCC using power quality analyzer.

    (a0 aJ-1) is scaling sequence and (b0 bJ1) is wavelet sequence. Scaling function is assosiated with low-pass filterswith coefisient h(n),n z, and wavelet function is

    asssosiated with high-pass filter with coeficient

    g(n),n z,(Figure 4 )

    Fig. 4. Wavelet Decomposition 2 Levels

    Some important traits for low pass filter and high pass filter are:

    1. h(n)2 1 and g(n)2 1

    (3)

    Fig. 2. Electrical Circuit Of Electric Arc Furnace

    The Electric Arc Furnace in this study has a capacity 130 tons, 50 MW, 30 kV [14]. The melting process of

    n

    2. h(n)

    n

    n

    2 and g(n) 0

    n

    (4)

    steel inside the EAF is due to the heat generated from short circuit among the electrodes. .

    3. Filter g(n)is alternative from filter h(n), which is an odd

    integer N so:

    g(n) (1)n h(N n)

    (5)

    Based on implementation from figure 4, correlation of approximation coefficient with detail coefficient defined as:

    cAj (k) h(2k n)cAj 1 (n)

    n

    cD j (k) g(2k n)cAj 1 (n)

    n

    (6)

    (7)

    Fig. 3. Recorded Data of Voltage EAF

    Data obtained in raw form corresponding read on power quality analyzer. to simplify the simulation process, the data should be in the range of 0 and 1.Therefore, it is necessary to process the raw data by:

    (1)

    cA j and cD j represent approximation coefficient and detail coefficient from signal to the level-j.

    C. Wavelet Energy

    The wavelet energy is the sum of square of detailed coefficients. To distinguish the disturbance signal can be viewed by the energy distribution of the wavelet transform. Energy values for each detail signal and approximation signal can be calculated by equation(8) and (9).[15]

    Edj

    n d

    2

    j (n)

    (8)

    ai

    n

    i(n)

    E a 2

    (9)

    Edj is energy of detail signal to-j and Eai is the energy of approximation signal to-i for n-level decomposition.

    Scales of the wavelet energy coefficients varying depending on the input signal. The distorted signal has energy can be partitioned at different resolution levels and in different ways depending on the power quality problems [16].

  3. RESULT AND DISCUSSION

    Data obtained from the voltage measurement, normalized using equation (2) and the results are as shown in figure 5.

    Fig. 5. Result Normalized of Measurement EAF Voltage

    <>Data normalization as shown in Figure 4 is then transformed using wavelet transform. Discrete Wavelet Transformation divides the original signal into two parts, namely the approximation and detail. Approximation has the same shape of the signal with the original signal are signal Va, Vb and Vc. In this research, the wavelet transform up to 5 levels, the results can be seen in Figure 6 and Figure 7.

    Details are observed signal, detail generate shape of the signal corresponding to the mother wavelet when fault occurs.

    1. (b)

      Fig. 6. Wavelet Transformation (a) Detail-2 (Va, Vb, And Vc) and

    2. Detail -3 (Va, Vb, And Vc)

    Figure 6 are the result of wavelet transformation for detail 2 and detail 3 for signals Va, Vb, and Vc.

    1. (b)

      Fig. 7. Wavelet Transformation (a) Detail-(Va, Vb, And Vc) and

    2. Detail -5 (Va, Vb, And Vc)

    Figure 7 are the result of wavelet transformation for detail 4 and detail 5 for signals Va, Vb, and Vc. From Figure 6 and Figure7, shown there are disturbance of voltage, i.e. unbalance voltage.

    The value of detail signal which obtained from Figure 5 and Figure 6 are used to calculate the wavelet energy on each voltage (Va, Vb, and Vc).

    The calculation result of wavelet energy the detail signal, indicate that the signal detail of Va, Vb and Vc have an average value (Edaverage) 0.14842, 0.04884, and 0.09926 respectively.

    Table 1. Wavelet Energy Of Three Phase Voltage EAF

    Ea

    Ed1

    Ed2

    Ed3

    Ed4

    Ed5

    Va

    99.2578

    0.0245

    0.0596

    0.1496

    0.2334

    0.2750

    Vb

    99.7559

    0.0076

    0.0226

    0.0497

    0.0639

    0.1004

    Vc

    99.5038

    0.0159

    0.0388

    0.0908

    0.1560

    0.1948

    From Table 1, it can be explained that in the event of voltage at phase-b (Vb) has the largest Ed value among other voltage. This suggests that the higher the value of Ed, the energy loss is also higher.

  4. CONCLUSSION

In this study, method of disturbance identification with wavelet analysis has been developed and tested. The test result show powerful capabilities of the proposed method based on wavelet transform to detect disturbance voltage occurs is unbalance voltage. Based on the value of wavelet energy, it is known that the energy value greater in one of voltage (Va) than another voltage (Vb and Vc).

ACKNOWLEDGMENT

The author is grateful to the steel industry and its power plants, especially to Mr. Ermawanto. He has allowed the author to obtain measurement data for the completion of this study.

REFERENCES

  1. S. Chattopadhyay, M. Mitra, and S. Sengupta, Sag, Swell, Interruption, Undervoltage and Overvoltage, Electr. Power Qual. Dordr. Springer Neth., pp. 3942, 2011.

  2. S. Mishra, C. N. Bhende, and B. K. Panigrahi, Detection and Classification of Power Quality Disturbances Using S-Transform and Probabilistic Neural Network, IEEE Trans. Power Deliv., vol. 23, no. 1, pp. 280287, Jan. 2008.

  3. A. M. Gaouda, S. H. Kanoun, M. M. A. Salama, and A. Y. Chikhani, Pattern recognition applications for power system disturbance classification, IEEE Trans. Power Deliv., vol. 17, no. 3, pp. 677683, Jul. 2002.

  4. S. Chattopadhyay, M. Mitra, and S. Sengupta, Sag, Swell, Interruption, Undervoltage and Overvoltage, in Electric Power Quality, Dordrecht: Springer Netherlands, 2011, pp. 3942.

  5. M. Ashari, C. V. Nayar, and S. Islam, A novel scheme for mitigation of line current harmonics and compensation of reactive power in three phase low voltage distribution systems, 2000, vol. 3, pp. 13241329.

  6. A. Hussain Elmetwaly, Detection and Identification of PQ Disturbances Using S-Transform and Artificial Intelligent Technique, Am. J. Electr. Power Energy Syst., vol. 4, no. 1, p. 1, 2015.

  7. 1159-1995, IEEE Recommended Practice for Monitoring Electric Power Quality, IEEE Inc., New York, 1995.

  8. Swapnil Arya and Bhavesh Bhalja, Simulation of Steel Melting Furnace in MATLAB and its effect on power Quality problems, Natl. Conf. Recent Trends Eng. Technol., May 2011.

  9. A. A. Gomez, J. J. M. Durango, and A. E. Mejia, Electric arc furnace modeling for power quality analysis, 2010, pp. 16.

  10. CV. Nayar and M. Ashari, Phase Power Balancing of a Diesel Generator using a biderectional PWM inverter, IEEE Power Eng. Rev., vol. 19 (11), 1999.

  11. M. Ashari, C. V. Nayar, and S. Islam, Steady-state performance of a grid interactive voltage source inverter, 2001, vol. 1, pp. 650655.

  12. Triveni M.T, Priyashree S, and Vidya H.A, Implementation Of Wavelet Transform Technique For Detection And Reduction Of Harmonics In An Induction Furnace, Proc. 08th IRF Int. Conf.

  13. C. Gargour, M. Gabrea, V. Ramachandran, and J.-M. Lina, A short introduction to wavelets and their applications, IEEE Circuits Syst. Mag., vol. 9, no. 2, pp. 5768, 2009.

  14. Wahyuni Martiningsih, Mochamad Ashari, Adi Soeprijanto, and Dian Sawitri, Sag Voltage Identification on 30 kV Systems Affected By Electric Arc Furnace using Wavelet Transformation Method, J. Theor. Appl. Inf. Technol., vol. 61, no. 2, pp. 352 357, Mar. 2014.

  15. D.-M. Li, X.-Y. Yu, X. Wang, and T.-Q. Tang, Power Quality Disturbances Fuzzy Identification Based on DQ Conversion and Wavelet Energy Distribution, 2012, pp. 14031407.

  16. Sudipta Nath and Priyanjali Mishra, Wavelet based feature extraction for classification of Power Quality Disturbances, Int. Conf. Renew. Energ. Power Qual. ICREPQ11, Apr. 2011.