Experimental and CFD Analysis of Tube in Tube Helical Coil Heat Exchanger

DOI : 10.17577/IJERTV4IS080441

Download Full-Text PDF Cite this Publication

Text Only Version

Experimental and CFD Analysis of Tube in Tube Helical Coil Heat Exchanger

Mr. Ganesh B. Mhaske

PG Student, Department of Mechanical Engineering Matoshri College of Engineering and Research Center Nashik,India

Prof. D. D. Palande

Associate Professor, Department of Mechanical Engineering

Matoshri College of Engineering and Research Center Nashik,India

Abstract This Present work represents an Experimental studies and CFD investigation for a counter flow tube in tube helical coil heat exchanger where hot water flows through the inner tube and cold water flows through the outer tube. An experimental setup is used for the estimation of the heat transfer characteristics. A wire is wound over the inner tube to increase the turbulence in turn increases the heat transfer rate. The analysis deals with internal wound wire and its result on the heat transfer rate. From Experimental results, heat transfer rate, LMTD, overall heat transfer coefficient, efficiency and Reynolds number, Nusselt number, Friction factor are calculated. CFD analysis for helical coil tube in tube heat exchanger is carried out and the simulation results are used to predict the flow and thermal development in tube in tube helical coil heat exchanger. Experimental and CFD analysis of tube in tube helical coil heat exchanger and conventional heat exchangers are studied.

Keywords Tube-in-tube helical coil, Nusselt number, wire wound, Reynolds number, Dean Number, dead zone, efficiency.

  1. INTRODUCTION

    To transfer the heat between two fluids Heat exchanger is used which may be in direct contact or may flow separately in two tubes or channels. We find numerous applications of heat exchangers in day today life. For example condensers and evaporators used in refrigerators and air conditioners. In thermal power plant heat exchangers are used in boilers, condensers, air coolers and chilling towers etc. Similarly the heat exchangers used in automobile industries are in the form of radiators and oil coolers in engines. Heat exchangers are also used in large scale in chemical and process industries for transferring the heat between two fluids which are at a single or two states.

    1. Helical Coil Heat Exchanger

      Recent developments in design of heat exchangers to full fill the demand of industries has led to the evolution of helical coil heat exchanger as helical coil has many advantages over a straight tube.

    2. Advantages

      1. Heat transfer rate in helical coil are higher as compared to a straight tube heat exchanger.

      2. Compact structure. It required small amount of floor area compared to other heat exchangers.

      3. Larger heat transfer surface area.

    3. Applications

      1. Heat exchangers with helical coils are widely used in industries. The most common industries where heat exchangers are used a lot are power generation plants, nuclear plants, process plants, refrigeration, heat recovery systems, food processing industries, etc.

    From the available literature I find that so much work had been done to find heat transfer characteristic of helical coil heat exchanger with constant wall temperature and constant heat flux conditions. Also by changing the working fluid heat transfer relation were found. But effect of pitch variation of the internal wounded wire and its result on the heat transfer rate is not explained properly. In the present work the performance of a Tube-in-tube helical coil heat exchanger for a waterwater counter current flow system is going to study experimentally. The effect of the fluid flow rate on the heat transfer and hydrodynamics is going to study in the tube as well as in the annulus. In the present work four turns of coils is consider and also copper wire is to be introduce in the annulus area of the Tube-in-tube helical coil heat exchanger.

  2. OBJECTIVES OF WORK

    1. Experimental analysis of tube in tube helical coil heat exchanger and find out heat transfer rates, LMTD, overall heat transfer coefficient and Reynolds number, Nusselt number ,Dean number for counter flow arrangement.

    2. CFD simulation for helical coil tube in tube heat exchanger will be carry out.

    3. Comparison of Experimental and CFD results of tube in tube helical coil heat exchanger.

  3. EXPERIMENTATION

      1. Experimental Setup

        Fig.1 Experimental-Setup Tube-in-Tube Helical Coil Heat Exchanger

        Experimental-Setup consists of following parts:-

        1. Tube-In-Tube Helical Coil Heat Exchanger

        2. Tank with thermostatic heater

        3. Water Reservoir

        4. Flow Control valve

        5. Pressure Indicator

        6. J-Type thermocouples

    Cold tap water is use for the fluid flowing in the outer tube. The water in the outer tube will be circulated. The flow is control by a valve, allowing flows to be control and measure between 480 and 1200 LPH. Hot water for the inner tube is heated in a tank with the thermostatic heater set at 600C. This water is circulated via pump. The flow rate for the inner tube is control by flow metering valve as described for the outer tube flow. Flexible PVC tubing is use for all the connections. J-Type thermocouple is used to measure the inlet and outlet temperatures for both fluids.

      1. onstruction of Tube-in Tube Helical coil Heat Exchanger

        During Construction of Tube-in Tube Helical coil Heat Exchanger following parameters are taken into considerations

        • Effect of curvature ratio on heat transfer

        • The Influence of pitch of coil on heat transfer

        • Influence of the tube diameter change on heat transfer characteristics.

    Actual Selected Dimensions from summary of tube-in-tube helical coil heat exchanger. To increase heat transfer rate, we have to increase the curvature ratio.

    TABLE I

    DIMENSIONAL PARAMETERS OF HEAT EXCHANGER

    Dimensional parameters

    Heat Exchanger

    di,mm

    10

    do,mm

    12

    Di,mm

    23

    Do,mm

    25

    Curvature Radius,mm

    125

    Stretch Length,mm

    3992

    Wire diameter, mm

    1.5

    Curvature ratio

    0.1

    No. of Turns

    4

    Fig.2 Tube-In-Tube Helical Coil Heat Exchanger

    The tube of the heat exchanger is made up of copper for maximize the heat transfer, because copper has good thermal conductivity. Also the properties of the copper were also remains constant throughout the analysis.

    TABLE II PROPERTIES OF COPPER

    Description

    Value

    Units

    Density

    8978

    kg/m3

    Specific Heat Capacity

    381

    J/kg-K

    Thermal Conductivity

    387.6

    W/m-K

  4. SIMULATION OF TUBE-IN TUBE HELICAL COIL

    HEAT EXCHANGER

    A. CFD Methodology

    For simulation of Tube-in Tube Helical coil Heat Exchanger, first we have to create a Heat Exchanger model using Solid Edge Software. After creating the geometry and doing the meshing in ANSYS 14 the problem is analysed in ANSYS 14. As this iscounter flow of inner hot fluid flow and outer cold fluid flow so there is two inlet and outlet respectively. There is a pipe which separates the two flows which is made by copper. The detail about all boundary conditions are as follows. Inner fluid is taken as hot water and outer fluid is taken as cold water.

    TABLE III BOUNDARY CONDITIONS

    Heat transfer rate of hot water (J/sec)

    S.N.

    Parameters

    Range

    1.

    Inner tube flow rate

    120-480 LPH

    2.

    Outer tube flow rate

    480-1200 LPH

    3.

    Inner tube inlet temperature

    (0C)

    58-62

    4.

    Inner tube outlet temperature

    (0C)

    35-46

    5.

    Outer tube inlet temperature

    (0C)

    28-30

    6.

    Outer tube outlet

    temperature (0C)

    30-40

    qH = mH×CP× tHOT× 1000

    Heat transfer rate of cold water (J/sec)

    qC = mC×CP×tCOLD× 1000

    Average heat transfer rate [7]

    Q = (q + q )/2

    avg H C

    The heat transfer coefficient was calculated with [2],

    =/ (×)

    The overall heat transfer surface area was determined based on the tube diameter and developed area of heat transfer which is A= 0.22272m2, The total convective area of the tube keep constant for two geometry of coiled heat exchanger. LMTD is the log mean temperature difference, based on the inlet temperature difference T1, and outlet temperature difference T2,

    LMTD=(12)/ (ln (1/2))

    The overall heat transfer coefficient can be related to the inner and outer heat transfer coefficients by the following equation [7],

    1/0= (0/)+(0×ln(/)/2)+(1/)

    Where di and do are inner and outer diameters of the tube respectively. k is thermal conductivity of wall material and L, length of tube(stretch length) of heat exchanger. After calculating overall heat transfer coefficient, only unknown variables are hi and ho convectiveheat transfer coefficient inner and outer side respectively, by keeping mass flow rate in annulus side is constant and tube side mass flow rate varying[5],

    Fig.3Solid Edge Model of Tube-In-Tube Helical Coil Heat Exchanger

  5. RESULTS &DISCUSSION

    1. Experimental Results

      TABLE IV

      Cold water flow rate =720LPH

      S.N

      Flow rate

      Cold water temp.

      Hot water temp.

      t1

      t2

      LMTD

      Tin

      Tout

      Tin

      Tout

      1

      120

      30

      36.2

      60

      41.4

      23.8

      11.4

      16.85

      2

      240

      30

      37.4

      60

      42.4

      22.6

      12.4

      17

      3

      360

      30

      39

      60

      43.5

      21

      13.5

      17

      4

      480

      30

      40

      60

      44.5

      20

      14.5

      17.10

      FOR COLD WATER FLOW RATE =720LPH

      hi= CV n

      i

      Where Vi are the tube side fluid velocity m/sec., the values for the constant, C, and the exponent, n, were determined through curve fitting. The inner heat transfer could be calculated for both circular and square coil by using Wilson plot method. This procedure is repeated for tube side and annulus side for each mass flow rate on both helical coils [7].

      The Reynolds number

      Re= (×V×D) /

      Dean number,

      De= ((×V×D) / ) x (/2) ½

      In present investigation work the heat transfer coefficient and heat transfer rates were determined based on the measured temperature data. The heat is flowing from inner tube side hot water to outer tube side cold water.

      Mass flow rate of hot water (Kg/sec):

      mH = QHOT(LPH) ×(Kg/m3)

      Mass flow rate of cold water (Kg/sec)

      mC = QCOLD(LPH) × (Kg/m3)

      Velocity of hot fluid (m/sec)

      VH = /(1000×Area)

      TABLE V

      Parameters

      120 LPH

      240 LPH

      360 LPH

      480 LPH

      For Inner Side of Inner Tube

      LMTD(0c)

      16.85

      17

      17

      17.10

      MH(Kg/sec)

      0.0327

      0.0655

      0.0983

      0.131

      Mc(Kg/sec)

      0.2

      0.2

      0.2

      0.2

      VH(m/sec)

      0.4246

      0.8492

      1.2738

      1.6985

      qH(J/sec)

      2546.01

      4825.62

      6789.48

      8499.67

      qc(J/sec)

      5190.64

      6195.28

      7534.8

      8372

      Qavg(J/sec)

      3868.325

      5510.45

      7162.14

      8435.84

      RESULT TABLE FOR COLD WATER FLOW RATE =720LPH

      Uo(W/m2k)

      1961.99

      2321.068

      2822.92

      3118.236

      Re

      5230.34

      10460.69

      15691.04

      20922.02

      De

      1689.89

      3307.96

      4961.94

      6616.11

      Nu

      7.92

      13.06

      17.56

      22.13

      For Outer Side Of Inner Tube

      Nu

      29.65

      33.82

      36.02

      45.44

      Vc(m/sec)

      0.66159

      0.66159

      0.66159

      0.66159

      Re

      16581.20

      16581.20

      16581.20

      16581.20

      De

      5243.43

      5243.43

      5243.43

      5243.43

    2. CFD Results

      For CFD analysis, we were taken Constant Cold water Flow Rate =720LPH and different Hot water flow rate i.e. 120LPH, 240LPH, 360LPH, 480LPH for Validation of above experimental results.

      Fig.4 CFD Analysis of Tube in Tube Helical Coil Heat Exchanger with copper wire wounded over inner tube with 6 mm pitch for constant cold water flow rate =720LPH with different hot water flow rate a) 120 LPH b)240 LPH c) 360 LPH d)480 LPH.

      From above CFD results, we were obtained the outlet temperature of Hot and Cold Fluid. From temperature data, we find Nusselt number, Reynolds number, Dean Number, overall heat transfer coefficient. After Calculation, We observed that overall heat transfer coefficient is increases with increasing inner tube flow rate, for constant Cold Water Flow Rate =720LPH.

  6. COMPARISON OF EXPERIMENTAL & CFD RESULTS OF TUBE IN TUBE HELICAL COIL HEAT

    EXCHANGER

    TABLE VI

    RESULT TABLE FOR CONSTANT COLD WATER FLOW RATE =720LPH WITH DIFFERENT HOT WATER

    FLOW RATE (120,240,360,480LPH)

    N

    Nusselt no.(Nu)

    Reynolds no.(Re)

    LMTD

    (Uo)

    (W/m2K)

    E

    xpt

    FD

    E

    xpt.

    C

    FD

    E

    xpt.

    C

    FD

    Ex

    pt.

    C

    FD

    7.92

    8

    5230

    5530

    16.85

    17

    1961

    2000

    13.06

    13

    10460

    11460

    17

    17.25

    2321

    2400

    17.56

    18

    15691

    16691

    17

    17.25

    2822

    2900

    22.13

    23

    20922

    21922

    17.1

    17.5

    3118

    3195

    From above Experimental and CFD (FLUENT) Results, we obtained the graphs for Constant Cold water Flow Rate =720LPH and different Hot water flow rate i.e 120LPH, 240LPH, 360LPH, 480LPH.

    Fig.5 Inner Tube Nusselt Number(Nui) Vs Inner Tube Reynolds

    Number(Rei)

    Fig.6 Inner TubeNusselt Number(Nui) Vs Inner Tube Flow Rate (LPH)

    Fig.7 LMTD Vs Inner Tube Flow Rate (LPH)

    Fig.8 overall heat transfer coefficient (Uo) Vs Inner Tube Flow Rate

    (LPH)

  7. CONCLUSION

    1. By comparing these Experimental and CFD results of wire wounded Tube in Tube Helical Coil Heat Exchanger, we observed that as the inner tube flow rate (LPH) increases, inner heat transfer coefficient (hi) is also increases. As we know that Nusselt Number is directly proportional to inner heat transfer coefficient (hi)

      ,So that Nusselt Number is increases with increasing

      inner tube flow rate, for constant Cold Water Flow Rate.

    2. We found that as the inner tube flow rate (LPH) increases, Velocity of hot fluid (VH) (m/sec) is also increases, So that Reynolds Number, Dean Number is increases with increasing inner tube flow rate, for constant Cold Water Flow Rate.

    3. We observed that as the inner tube flow rate (LPH) increases, Temperature difference (t1-t2) also increases, So Log mean temperature difference (LMTD) is increases with increasing inner tube flow rate, for constant Cold Water Flow Rate.

    4. We found that as the inner tube flow rate (LPH) increases, the heat gain by cold water(J/sec) is also increases, So that overall heat transfer coefficient is increases with increasing inner tube flow rate, for constant Cold Water Flow Rate.

ACKNOWLEDGMENT

First and foremost, I would like to express my deep sense of gratitude and indebtedness to my guide Prof. D.D.Palande for his invaluable encouragement, suggestions and support from an early stage of this project and providing me extraordinary experiences throughout the work. Above all, his priceless and meticulous supervision at each and every phase of work inspired me in innumerable ways. I am highly grateful to Dr.G.K.Kharate, Principal, Matoshri College of Engineering and Research Center, Eklahare,Nashik, Prof.J.H.Bhangale, Head, Department of Mechanical Engineering and Prof.D.D.Palande,PG coordinator, Department of Mechanical Engineering for their kind support and permission to use the facilities available in the Institute.

REFERENCES

  1. D.G.Prabhanjan, G.S.V., Raghavan and T.J.Rennie, Comparison of heat transfer rates between a straight tube heat exchanger and a helically coiled heat exchanger, Heat and mass transfer, Vol. 29, No. 2, (2002), pp.185-191.

  2. T.J. Rennie, D.G. Prabhanjan, Laminar parallel flow in a tube-in-tube helical heat exchanger, in AIC Meeting, 2002.

  3. D.G.Prabhanjan, G.S.V., Raghavan and T.J.Rennie, Natural convection heat transfer from helical coiled tubes, International Journal of Science, Vol. 43, No. 4, (2004), pp. 359-365.

  4. T.J. Rennie, V.G.S. Raghavan, Experimental studies of a double-pipe helical heat exchanger, Experimental Thermal and Fluid Science,29 (2005) 919924.

  5. J.R.Timothy., G.S.Vijaya, Numerical studies of a double-pipe helical heat exchanger, Applied Thermal Engineering, Vol. 26, (2006), pp. 1266-1273.

  6. T.J. Rennie, V.G.S. Raghavan, Effect of fluid thermal properties on heat transfer characteristics in a double pipe helical heat exchanger, Int J Therm Sci,2006b; 45:115865.

  7. V. Kumar, S. Saini, M. Sharma, Pressure drop and heat transfer in tube-in-tube helical heat exchanger, Chem. Eng. Sci. 61 (2006) 4403- 4416.

  8. J.S. Jayakumar, S.M. Mahajani, J.C. Mandal, Experimental and CFD estimation of heat transfer in helically coiled heat exchangers,Chemical engineering research and design, Vol. 86, (2008), pp. 221-232.

  9. V. Kumar, B. Faizee, M. Mridha, K.D.P. Nigam, Numerical studies of a tube in-tube helically coiled heat exchanger, Chem. Eng. Proc. 47 (2008) 22872295.

  10. Jung-Yang San, Chih-Hsiang Hsu, Shih-Hao Chen, Heat transfer characteritics of a helical heat exchanger, Applied Thermal Engineering39 (2012) 114-120, Jan 2012.

  11. R.M.Soumya, CFD analysis of heat transfer in a helical coil heat exchanger using fluent,M.Tech. Thesis, NIT Rourkela, India, (2013), pp. 1-33.

  12. Mr.G.B.Mhaske, Prof.D.D.Palande, Experimental Investigation of Heat Transfer Analysis of Tube in Tube Helical Coil Heat ExchangerMechPGCON,Jully (2015).