Power Flow Analysis of Integrated Wind and Solar Power Generation and Distribution System

DOI : 10.17577/IJERTV5IS060330

Download Full-Text PDF Cite this Publication

Text Only Version

Power Flow Analysis of Integrated Wind and Solar Power Generation and Distribution System

P. Yuvasri Lakshmi

P.G Student,

Power System Engineering, Kingston Engineering College, Vellore.

Abstract — Power flow analysis is also known as load flow analysis in which per unit voltage and magnitude of the system is analyzed by the MI POWER SOFTWARE using the Newton Naphsion method. Which is faster on the speed of convergence, but programming is more complex suitable for large size system and the number of iterations does not depend on the size of the system, extra retention memory or remembrance is essential. The power flow is not unable to combine parts in power system analysis the main factor incite is the inability regards the power system to meet the demand for reactive power voltage instability does not always occurs in its pure form. A distinction between angle stability is important for understanding the underlying determinant concerning the problem in order to develop appropriate design and operating procedures

Keyword — Load flow analysis; Newton Raphsion method; Extra retention memory; Reactive power voltage instability.

  1. INTRODUCTION

    Load flow analysis can be carried out for small and medium size power systems. It suits for the radial distribution system with high R/X ratio. The load flow analysis helps to identify the overloaded/underloaded buses in the system. It is used to study the optimum location of capacity is and their size to improve unacceptable voltage profile Power flow analysis or load flow analysis is performed in a symmetrical steady-state operating condition of a power system under the normal mode of operation. The solution of load flow gives bus voltages and line/ transformer power flow for a prone load condition. This information is essential for long-term planning and operational planning. In the network of the power system, buses become node and a voltage can be specified for each bus. Load flow analysis is essentially concerned with the persistence of complex bus voltages at all busses, given the network configuration and the bus demands. The bus generation and characterized by complex powers flowing into and out of the buses respectively. A generation inventory is nothing but a combination of MW generation of the various generations should match the given requirement plus the transmission losses. It should be noted that there are many generation schedules available to match the prone system demand and one such schedule is chosen for load flow analysis is Newton Raphsion method

  2. CLASSIFICATION OF BUSES

    The following information is essential for long term planning and operational planning.

    1. Long-term Planning

      Load flow analysis helps in investigating the effectiveness of alternative plans and choosing the perfect plan for system expansion to meet the projected operating state.

    2. Operational planning

      It helps in choosing the perfect unit commitment plan and generation schedules to run the system efficiently for the next days load condition without contravening the bus voltages and line flow operating limits.

    3. Steps for load flow analysis

      The following work has to be carried for a load flow study. Representation of the system by single line diagram.

      • Decisive impedance design diagram using the information in the single line diagram

      • Formation of network equation

      • Solution of network equation

        The buses are classified based on the variable specified. There are three types of buses.

        1. Slack bus or swing bus or reference bus.

        2. Generator bus or voltage bus or P-V bus or regulator bus.

        3. Load bus or P-Q bus.

        The following table gives the quantities specified and the quantities to be specified for each bus

        Table I.

        S.No

        Bus

        Quantities Specified

        Quantities to be Specified

        1.

        Slack Bus

        V,

        P, Q

        2.

        P-V Bus (or) Generator Bus

        P,V

        Q,

        3.

        P-Q Bus (or) Load bus

        P,Q

        V,

        At these buses, the active and reactive power are specified, the magnitude and phase angle of the voltage are unknown. These are called as load bus

        Advantages of load flow analysis

        In the power system design and operation there are four things that need to be understand

    4. Slack Bus

      In slack bus, voltage magnitude and phase angle of voltages are specified pertaining to a generator bus usually a large capacity generation bus is chosen. We assume voltage (V) as reference phasor

      I.e., = 0

      Where = Phase angle of voltage.

      This bus makes up the difference between the scheduled load and generated power that are caused by the losses in the network.

      The power balance equation is

      • Generation (Type, capacity,forecast and others too)

      • Distribution network A = cross section area

    At 300 metre Resistance R = 0.3021 At 400 metre Resistance R = 0.402 At 200 metre Resistance R = 0.201 At 50 metre Resistance R = 0.0503

    H. The Formula to find Reactance

    X=XL XC

    Where

    XC = 1

    2

    =

    =

    XL = 2fL

    =1

    =1

    =1

    The Formula to find Inductance

    P depends on I2 R loss in the transmission line and

    L=2l[ ((2) (1 + 1 + ( ) 2))

    L

    transformer of the network. The individual current in the various lines of the network cannot be calculated until after

    1 + ( ) 2 + + ( )]

    2

    the voltage magnitude and angle are known at every bus of the system. Therefore, PL is initially unknown. Real and reactive power is not specified for slack bus. In power flow

    Where

    2

    4 2

    problem,we assume one generator bus as a slack bus at which power generation is Prespecified. After the power flow problem has been solved, the difference between the total specified real power going into the system at all the other buses and the total power consumed by loads plus I2 R losses are assigned to the slack bus. Therefore a generator bus must be selected as the slack bus. The slack bus is needed to account for transmission line losses.

    1. Generator bus or P-V bus or Regulated bus

      At these buses, the real power and voltage magnitude are specified. The phase angle of the voltage and the reactive power are also specified.

      In order to maintain a good voltage profile over the system, Automatic Voltage Regulator (AVR) is used.Static VAR compensator buses are called as buses because real power and voltage magnitude are specified at these buses

    2. Load Bus or P-Q Bus

      • Load (Types of Load, demand and forecast).

      • Protection

    3. Calculation of Resistance and reactance of system

      The Formula to find Resistance (R)

      R=

      Where

      = Resistivity L = Length

      d = Diameter

      l =length

      At 300 m Inductance L = 0.000688H At 400 m Inductance L = 0.000939H At 50 m Inductance L = 0.0000966H At 200 m Inductance L = 0.000442H

      Formula for cylindrical Capacitor

      C = 2

      ()

      At 300 m capacitance C = 0.0677F

      At 400 m capacitance C = 0.0810 F

      At 50 m capacitance C = 1.01293×10-8 F At 200 m cpacitance C = 0.04006 F Reactance of 300 m 0.1638

      Reactance of 400 m 0.2556

      Reactance of 50 m 0.28363

      Reactance of 200 m 0.05933

  3. SINGLE LINE DIAGRAM

    A single line diagram is a diagrammatic representation of power system in which the components are represented by their symbols and the interconnection between them are shown by a single straight line (even though the system is a three phase system). The ratings and the impedance of the component are also marked on the single line diagram

    20MVa

    250 KVa

    381.97Kw

      • Single phase transformer equivalents are shown as ideal transformers with transformer impedance indicated on appropriate side.

      • Magnetization reactance of the transformers have

        0.33021+0.1638

        0.402+0.2556j

          1. +0.05933j

            Admin

            Main Block 109 Kw

            0.0503+0.2

            63j

            0.0503+0.2

            63j

            E.B

            been neglected.

            • Generator are represented as voltage sources with series resistance and inductive reactance

        1. Steps to draw per unit impedance diagram

          83

          83

          • Choose a common MVA or base MVA for the system (Mostly highest generator rating is taken).

            110Kw

            Hotel Block

            250KVa

            Block

            223.85Kw

            110Kw

            125KVa

            Block

            125KVa

            • Choose an appropriate base KV for each and every section

        2. Applications of Y bus matrix

      • Y-bus is used in solving load flow problems.

      • It has gained applications owing to the simplicity in data preparation

      • It can be easily formed and modified for any

    changes in the network

    Fig. 1. Power system Network

    The scope of the single line diagram is to supply in concise form of the significant information about the system. The power system network is represented by one line diagram using suitable symbols for generator, motor, transformer, transmission line and loads.

    1. Impedance diagram

      The impedance diagram on the single phase basis under balanced operation conditions can be drawn from one line diagram

      Fig. 2. Single Line Diagram

      • It reduces computer memory and time requirements because of sparse matrix

    Y bus is determined by Two-rule method or inspection method.In the equivalent network generators are replaced by Nortons equivalent, the load is replaced by equivalent admittances and the lines replaced by -equivalent circuits.

  4. LOAD FLOW ANALYSIS RESULT

    Load flow analysis is done through newton Raphsion method

    Version number: 8.2

    %% first power system network

    The Largest bus number used 8

    Actual number of buses 8

    Number of 2 wind. Transformer 2

    Number of Transmission lines 5

    Number of Loads 4

    Number of solar plants 1

    Number of Generators 2

    Base MVA 50

    Nominal system Frequency (Hz) 50

    Maximum number of iterations 15

    Bus voltage below which load : 0.75 Model is changed

    Transformer R/X Ratio : 0.05

    Annual percentage interest charges 15

    Annual percent operation & 4

    Life of equipment I years 20

    Maintenance charge

    Table I. Bus Data

    BUS NO.

    AREA

    ZONE

    BUS KV

    VMIN (P.U.)

    VMAX (P.U)

    NAM E

    1

    1

    1

    0.415

    0.95

    1.05

    BUS 1

    2

    1

    1

    33.0

    .95

    1.05

    BUS 2

    3

    1

    1

    0.69

    0.95

    1.05

    BUS 3

    4

    1

    1

    0.415

    0.95

    1.05

    BUS 4

    5

    1

    1

    0.415

    0.95

    1.0

    BUS 5

    6

    1

    1

    0.415

    0.95

    1.05

    BUS 6

    7

    1

    1

    0.415

    0.95

    1.05

    BUS 7

    8

    1

    1

    0.415

    0.95

    1.05

    BUS 8

    Table II. Transformer Data

    STATUS RATING

    CKT

    FROM NODE

    TO NODE

    IMPEDENCE

    R (P.U.)

    X(P.U.)

    MINT AP

    MAXT AP

    3

    2

    2

    3

    0.005

    0.11765

    0.95

    1.05

    3

    2

    2

    1

    0.1061

    8

    2.12357

    0.9105

    1

    1.00635

    Table III. Transformer Data

    STATUS RATING

    CKT

    FROM NODE

    TO NODE

    NOMINAL TAP

    TAP

    MVA

    TAPSTEP

    SHIFT- DE

    3

    2

    2

    3

    0.00588

    0.11765

    0.95

    1.05

    3

    2

    2

    1

    0.10618

    2.12357

    0.91051

    1.00635

    CKT

    FROM NODE

    FROM NAME

    TO

    NOD E

    TO NAME

    RATING MVA

    R(P.U)

    X(P.U)

    1

    4

    Bus4

    1

    Bus1

    17.88360

    10.2560

    1

    1

    Bus1

    5

    Bus5

    17.88360

    10.62560

    1

    1

    Bus1

    6

    Bus6

    17.88360

    10.62560

    1

    1

    Bus1

    7

    Bus7

    17.88360

    10.62560

    1

    1

    Bus1

    8

    Bus8

    17.88360

    10.62560

    CKT

    FROM NODE

    FROM NAME

    TO

    NOD E

    TO NAME

    RATING MVA

    R(P.U)

    X(P.U)

    1

    4

    Bus4

    1

    Bus1

    17.88360

    10.2560

    1

    1

    Bus1

    5

    Bus5

    17.88360

    10.62560

    1

    1

    Bus1

    6

    Bus6

    1.88360

    10.62560

    1

    1

    Bus1

    7

    Bus7

    17.88360

    10.62560

    1

    1

    Bus1

    8

    Bus8

    17.88360

    10.62560

    Table IV. Transmission line data

    1. NO OF ITERATION

      Iteration count 0 maxp 0.00200 max 0.002945

      Iteration count 1 maxp 0.00003 max 0.000022

      Iteration count 2 maxp 0.0000 maxq 0.0000

      Iteration count 3maxp 0 .0000maxq 0.00000

      Iteration count 4 maxp 0.0000 maxq 0.003894

      Itertion count 5 maxp 0.00002 maxq 0.000035

      • The N-R method is faster, more reliable and the result are accurate

      • Required less number of iterations for convergence

      • The number of iterations are independent of the size of the system

      • Suitable for large size systems.

    Fig. 3. Simulation Single Line Diagram Table V. Bus voltage and Powers

    Node No

    From name

    V-Mag P.U

    Angle degree

    MW GEN

    1

    BUS1

    1.0000

    0.00

    -0.017

    2

    BUS2

    1.0088

    0.24

    0.000

    3

    BUS3

    1.0089

    0.25

    0.100

    4

    BUS4

    1.0209

    0.27

    0.050

    5

    BUS5

    0.9716

    0.18

    0.000

    6

    BUS6

    0.9885

    0.07

    0.000

    7

    BUS7

    0.9835

    0.1

    0.000

    8

    BUS8

    0.9885

    0.07

    0.000

    Table VI Bus voltage and Powers

    Node No

    From name

    MVAr GEN

    MW LOAD

    MVAr LOAD

    1

    BUS1

    0.031

    0.000

    0.000

    2

    BUS2

    0.000

    0.000

    0.000

    3

    BUS3

    0.052

    0.000

    0.000

    4

    BUS4

    0.016

    0.000

    0.000

    5

    BUS5

    0.000

    0.053

    0.040

    6

    BUS6

    0.000

    0.022

    0.017

    7

    BUS7

    0.000

    0.031

    0.024

    8

    BUS8

    0.000

    0.022

    0.017

    Table VII. Transformer Flow And Transformer Losses

    Sl. No

    CS

    FROM NODE

    FROM NAME

    TO NODE

    TO NAME

    FORWARD

    MW

    MVAr

    1

    1

    2

    BUS 2

    3

    BUS 3

    -0.100

    -0.052

    2

    1

    2

    BUS 2

    1

    BUS 1

    0.100

    0.052

    Table VIII.Transformer Flow And Transformer Losses

    Sl. No

    CS

    FROM NODE

    FROM NAME

    TO NODE

    TO NAME

    LOSS

    MW

    MVAr

    1

    1

    2

    BUS 2

    3

    BUS 3

    0.0

    0.00

    2

    1

    2

    BUS 2

    1

    BUS 1

    0.0

    0.0005

    Table IX. Line Flows And Line Losses

    Sl. No

    CS

    FROM NAME

    TO NAME

    FORWARD

    Loading

    MW

    MVAr

    3

    1

    BUS 4

    BUS 1

    0.050

    0.016

    60.3

    4

    1

    BUS 1

    BUS 5

    0.055

    0.041

    80.4

    5

    1

    BUS 1

    BUS 6

    0.022

    0.017

    32.5

    6

    1

    BUS 1

    BUS 7

    0.032

    0.024

    46.6

    7

    1

    BUS 1

    BUS 8

    0.022

    0.017

    32.5

  5. SUMMARY OF RESULTS Total real power generation

    (CONVENTIONAL) : 0.00 MW

    Tolal reactive power Generation (CONVENTIONAL)

    :0.083 MVAr

    Toal real power generation (WIND)

    :0.100Mw

    Total reat. Power generation (WIND)

    :0.052MVAr

    Total real power generation (WIND)

    : 0.050 MW

    Total reat. Power generation (SOLAR)

    :0.052MVAr

    Total real power load : 0.129MW Total real power drawal(-ve gen) : 0.017MW Total reactive power load : 0.097MVAr

    \

    Fig. 4. Output of Simulation Single Line Diagram

    Load p.f : 0.8

    Total real power loss(AC+DC) : 0.003790 MW

    (0.003790+0.0000)

    Percentage real loss (AC+DC) : 2.527

    Total reactive power loss: : 0.002800MVAr

    A. Zone Wise Distribution Description

    MW generation : -0.0174

    MVAr generation : 0.0312

    MW wind gen. :0.1

    MVAr wind gen. :0.0517

    MW solar gen. :0.0500

    MVAr soalr gen. : 0.0164

    MW load : 0.1288

    MVAr load : 0.0966

    MW loss : 0.0038

    MVAr loss : 0.0028

  6. CONCLUSION

From the power flow analysis of a given system optimized power flow stabilized which is having

0.1 MW of generation from wind and 0.5MW of generation from solar to the grid connected system of 20 MW of synchronous generator generation. The corresponding voltage and magnitude are stabilized through reactive power compensation and obtianted per unit voltage of given system is also stabilized.

REFERENCE

  1. Power Flow Control using Quadrature Boosters With a suggested Optimal Power Flow Analysis San deep Sadanandan Electrical Engineer Arlington, Virginiasnsadana@yahoo.com Dr. Ghadir Radman Professor of Electrical Engineering, Tennessee Technological University Cookeville, Tennessee

  2. Power Flow Analysis Using Optimal Power Flow Method K. A. Dongre PG Department of Electrical and Electronics Engineering, Prof Ram Meghe College of Engineering and Management, Badnera, Amravati, India dongre_kiran@rediffmail.com A. P. Bhagat PG Department of Computer Science and Engineering, Prof Ram Meghe College of Engineering and Management, Badnera,

    Amravati, India amol.bhagat84@gmail.com

  3. Probabilistic Short Circuit Analysis in Electric Power Distribution Systems including Distributed Generation A. Bracale, P. Caramia,

    1. R. Di Fazio, D. Proto 8th Mediterranean Conference on Power Generation, Transmission, Distribution and Energy Conversion MEDPOWER 2012

  4. Wu Ming, 2004, " Solar energy of China equal to ten thousands of Sanxia Projects electrical power ", Population, Resource & Enviroment of China. vol. 16, 65-65.

  5. Institute of Electrical Engineering, Chinese Academy of Science, 2001, Acceptance Report of Bange PV station, Beijing, P .R . China.

  6. Yang Xiuxia, Zhang Xiaofeng, 2004, "Present situation and developing trend of isolated power system restoration", Realy, vol. 19, 74-79.

  7. Liu Shu, Zhao Zhengming, 2005, "One-level photovoltaic grid- connected system based on an improved MPPT algorithm", JOURNAL OF TSINGHUA UNIVERSITY(SCIENCE AND TECHNOLOGY, vol. 45, 873-876.

  8. Vachtsevanos, G.J. Kang, H, 1989, 1989, "Simulation studies of islanded behavior of grid-connected photovoltaic systems", IEEE Transactions on Energy Conversion, Vol2, 177-183.

  9. Asiminoaei. L, Teodorescu. R, Blaabjerg. F, 2005, "A digital controlled PV-inverter with grid impedance estimation for ENS detection", IEE ETransactions on Power Electronics, Vol.20, 1480 – 1490] Yu yixin, Wang Chengshan, 2001, Power system stability theory and method Science Press, Beijing, P. R. China.

  10. P.P Varaiya, F.F.Wu, R.L.Chen, 1985, "Direct Methods for Transient Stability Analysis of Power System Recent Results", Proceeding of IEEE, vol.73, 1120-1125.

  11. Load flows, Chapter 18,Bus classification, Comparison of solution methods, N-R methodElectrical Power system by C.L.WADHWA. Stability concept -Power Systems -Basic Concepts and Applications Part II By Shih-Min Hsu, Ph.D., P.E.

  12. Thyristor controlled reactors in flexible AC transmission systems part 1:series compensation by Arindam Ghosh,& Gerard Ledwich F. Sato, A.V. Garcia, A Monticelli: Parallel Implementation of Probabilistic Short-circuit Analysis by Monte Carlo Approach. IEEE Trans. on Power Systems. Vol. 9, May 1994, pp. 826-832.

  13. M.T. Schilling, A.M. Leite da Silva, R. Billinton, M.A. EI- Kady:Bibliography on Power System Probabilistic Analysis. IEEE Trans.on Power System, Vol. 5, No. 1, Feb. 1990, pp. 1-11.

  14. G. Carpinelli, D. Proto, C. Di Perna, P. Varilone, P. Verde:Probabilistic Short Circuit Analysis in Unbalanced Three- PhasePower Systems, Proc. of International Conference on Probabilistic Methods Applied to Power System (PMAPS), Sept. 2004, pp.807-812.

  15. N. Jenkins, R. Allan, P. Crossley, D. Kirschen, and G. Strbac:

    Embedded Generation. London, U.K.; Inst. Elect. Eng. , 2000.

  16. T. E. McDermott and R. C. Dugan: PQ, reliability and DG, IEEE Industry Applications Magazine, Vol. 9, Issue 5, Sep./Oct. 2003, pp. 1723.

  17. S. Hunt and G. Shuttleworth, Unlocking the GRID, IEEE Spectrum, Vol. 33, No. 7, July 1996, pp. 20-25.

  18. R Ouiddir, M Rahli & L Abdelhakem-Koridak, Economic Dispatch using a Genetic Algorithm: Application to Western Algerias Electrical Power Network Power Systems Optimization Laboratory, Faculty of Electrical Engineering, University of Science and Technology of Oran: Journal of information science and engineering 21, 659-668 (2005)

  19. J D WEBER, Implementation of a Newton-based optimal power flow into a power system simulation environment, thesis submitted at University of Wisconsin -Platteville, 1995.

  20. J D Glover & M S Sarma, Power system analysis and design 3rd

    Edition, Brooks/Cole, 2002.

  21. J. M. Guerrero, Microgrids: Integration of distributed energy resources into the smart grid, in Proc. IEEE Int. Symp. Ind. Electron.(ISIE), 2010, pp. 42814414.

  22. R. H. Lasseter, Extended CERTS microgrid, in Proc. IEEE Power and Energy Society General MeetingConversion and Delivery of Electrical Energy in the 21st Century, 2008, pp. 15.