Relationship between Compressive Strength and Pulse Velocity of medium Grade Concrete incorporating Rice Husk Ash

DOI : 10.17577/IJERTV1IS5028

Download Full-Text PDF Cite this Publication

Text Only Version

Relationship between Compressive Strength and Pulse Velocity of medium Grade Concrete incorporating Rice Husk Ash

AKANINYENE AFANGIDE UMOH

Building department, Faculty of Environmental Studies, University of Uyo, Uyo, Nigeria

Abstract

The partial replacement of cement with rice husk ash (RHA) in concrete has been reported to enhance the properties of the concrete especially its strength. The rice husk was sourced from a local rice mill in Akwa Ibom, Nigeria and fired at temperature range of 650 to 700oc and the ash obtained had high silica content. Four concrete grades of 15, 20, 25 and 30N/mm2 with cement content replaced by RHA at 0, 30, 40 and 50% and tested at 7, 14 and 28 days were investigated. The compressive strength were determined using both destructive (compression

  1. Introduction

    One material that has the potential not only to augment the supply of cementitious material but which is locally available and economical to produce is rice husk ash (RHA). The burning of the husk can be done either in open heaps, furnaces or in a purpose-made incinerator. The burning operation produces large quantity of ash, about one fifth by volume of husk [1].

    In Akwa Ibom and Cross Rivers States of Nigeria, rice is being produce in large quantity and the volume of husk being generated posed an environmental problem. The husk is usually burnt away as a mean of

  2. literature review

    The utilization of rice husk ash as mineral admixture in concrete provides several advantages. Its incorporation as supplementary cementitious material has led to increase in compressive strength of concrete [6]. According to Sugita et al. [7], blending of 20% by weight of RHA with ordinary Portland cement increases the compressive strength of concrete at 28 days by more than 25%. This is attributed to the reduction in effective water cement ratio in concrete blended with RHA as the free water is being absorbed by the added RHA and kept in its

    testing machine) and Non-destructive (pulse velocity tester) methods. The results indicated that the compressive strength of concrete incorporating RHA can attain the same order of strength as conventional concrete; and that compressive strength can be predicted from the pulse velocity value since there is a strong linear relationship between the two.

    Keywords: compressive strength, ordinary Portland cement, ground rice husk ash, ultrasonic pulse velocity

    disposal; this is evidence in large heaps of rice husk being burnt along Calabar Ikom expressway and some other major roads especially in the rice producing communities of the states.

    Many works have been carried out on the use of RHA as a pozzolanic material in concrete [2, 3, 4, 5]. One peculiar characteristic that have been discovered from the RHA is the fact that their chemical and physical composition varies depending on the source, geographical location, testing and processing methods. These variations in their compositions also affect the properties of concrete differently. Therefore, this study examined the effect of RHA from Itu-Mbonuso rice mill in Akwa Ibom State, Nigeria.

    mesopores. It has also been reported that the incorporation of RHA as a partial replacement of cement in concrete improved the concrete resistance to sulphate and acid attack [8, 9]. This is because the RHA pozzolanic reaction with calcium hydroxide leaves less lime to react with the sulphate or acid, thus reducing the risk of the expansive calcium sulphoaluminate formation, which can be destructive. It has been observed [6] that the more the RHA replacement, the less the amount of Ca (OH) 2 in concrete, and which they attributed to one of the main reasons for the strength enhancement of concrete.

    The common method for testing compressive strength of concrete has been the crushing of the concrete cubes or cylinders in a compression testing machine. This method is aptly classified as destructive since it entails irreversible damage to the concrete specimen. A number of non-destructive methods have been worked upon over years and one that has gained wide acceptability for the assessment of strength of concrete is the ultrasonic pulse velocity test.

    The measure of pulse velocity in concrete depends upon some of the following factors: water/cement ratio; aggregate/cement ratio; cement type and the amount of voids presence in the solid matter. Kaplan

    [10] found out that in concrete of the same age, the effects of aggregate/cement ratio and water/cement ratio balance one another so that at a given age, and at a constant workability level there is a unique relation between pulse velocity and strength of concrete.

    Cement type affects the pulse velocity for the fact that different types of cement are made by varying their chemical composition and/or their fineness. Silica with lime form the essential cementing compounds tricalcium silicate (C3S) and dicalcium silicate (C2S) in the composition of Portland cement; and rice husk ash contain a high proportion of silica, but a low percentage of lime. In RHA concrete therefore, we are dealing with concrete containing cement which chemical composition is much different from that of the ordinary Portland cement (OPC).

    The presence of voids in concrete, as stated by Neville [11] is the most important factor that influences the velocity of ultrasonic pulse transmission. The liberation of calcium hydroxide produced during the hydration of the C3S and C2S compounds of Portland cement that react with the silica in the ash filled these voids thereby resulting in a very strong cementitious compounds [1].

    It is therefore, from the above discussion, to be expected that the pulse velocity of RHA concrete will be different from that of conventional concrete (that is, concrete containing OPC only as binder) designed for the same strength. The work covers strength of four concrete grades of 15, 20, 25 and 30N/mm2 at 28

    days and concerned mainly with obtaining empirical data on the compressive strength and pulse velocity of RHA concrete as well as establishing the pattern of relationship between the two parameters.

  3. Experimental procedure

    1. Materials

      1. Aggregates

        The aggregates used for the study were crushed granite for coarse aggregate and natural sand for fine aggregate. The sieve analysis conducted on the aggregates indicated a uniformly graded soil (Figure 1). The fine aggregate falls within zone one as specified by BS EN 12620: 2002 + AI [12] which make suitable for use as concreting material, and has specific gravity of 2.61; while the coarse aggregate were of nominal maximum size of 20mm, and has a specific gravity value of 2,69.

            1. Cement

              Ordinary Portland cement branded as UNICEM produced to NIS 444-1[13] specification was used. The chemical compositions are presented in Table 1.

            2. Rice husk ash

        The rice husk was obtained from one of the rice mills in Itu Mbonuso, in Ini local government area of Akwa Ibom state, Nigeria. The husk was calcined in a furnace to temperature range of 650oc to 700oc; as soon as this range was attained, it was allowed for one hour for the intensity of the heat flame to reduce. The black husk was removed and heaped in an open space for 5 7 hours within which period it turned into ash.

        Sieving was conducted on the ash using 300m sieve, and material retained on the sieve was discarded. Materials finer than 300m size were ground with the aid of steel mortar and pestle. The sieve analysis of the ground ash before use is as presented in Table 2, while the specificgravity is

        2.01. The chemical composition and other properties of the ground RHA is as shown in Table 2.

        120

        100

        Percentage passing

        80

        e

        gr

        e ag

        Fin

        60 egat

        Coarse aggregate

        40

        20

        0

        0.1 1 10 100

        BS Sieve sizes (mm)

        Figure 1. Grading curves for aggregates

        Table 1: Chemical Composition of Binders

        Chemical

        Rice husk ash

        Ordinary Portland

        composition (%)

        (RHA)

        cement (OPC)

        SiO2

        70.70

        20.10

        Al2O3

        12.85

        5.25

        Fe2O3

        0.17

        3.02

        Na2O

        0.13

        0.14

        K2O

        3.37

        0.97

        CaO

        2.80

        62.20

        MgO

        1.61

        1.93

        P2O5

        0.77

        0.17

        LOI 7.60 1.09

        Table 2. Sieve analysis of ground RHA

        Sieve size (m)

        Material retained

        Percentage passing

        Weight (g) Percentage (%)

        212

        – –

        100

        150

        12 1.97

        98.03

        75

        202 33.22

        66.78

        tray

        394 64.80

    2. Method

      Four types of concrete mixes were used for the study:

      1. Conventional concrete, that is, concrete containing only ordinary Portland cement as binding material;

      2. Concrete containing 30%, 40% and 50% RHA respectively as a partial replacement of cement.

      All the four mixes were designed in each case to attain characteristics cube strengths of 15, 20, 25 and 30N/mm2 respectively at 28 days. The method of mix design adopted is that of the department of Environment. Workability tests (Slump and Compacting factor) were carried out on all the mixes to ensure that low workability range was maintained. The tests were done in accordance with the provision

      of BS EN 12350-2[14] and BS EN 12350-4[15] for

      slump and compacting factor respectively. Immediately after the workability tests, the cubes were cast in 150mm moulds. The moulds were thereafter covered with wet jute bags for 24 hours before de-moulding and subsequently cured in water at a temperature of 29±1oc.

      For each of the grade of concrete, three 150mm cubes were cast and tested for each of the three hydration periods of 7, 14 and 28 days. Thus a total of 144 cubes were produced for the study. The combination of cement and RHA was proportioned by volume because of the remarkable difference in the specific gravities of the RHA and the cement. Table 3 shows sample batch quantities of the mixes.

      Table 3. Mix proportions (Per M3 of Concrete)

      Design strength

      RHA content (%)

      Cement (Kg)

      RHA (Kg) Water (Litres) Sand (Kg)

      Gravel (Kg)

      (N/mm2)

      15

      0

      220

      – 200 980

      1060

      30

      126

      54 210 978

      1059

      40

      108

      72 217 978

      1059

      50

      90

      90 224 978

      1059

      20

      0

      270

      – 185 873

      1112

      30

      156

      67 197 873

      1112

      40

      134

      89 204 873

      1112

      50

      111

      111 211 873

      1112

      25

      0

      298

      – 186 842

      1115

      30

      172

      74 204 842

      1115

      40

      148

      98 208 842

      1115

      50

      123

      123 214 842

      1115

      30

      0

      321

      – 192 812

      1122

      30

      185

      97 196 812

      1122

      40

      159

      106 203 812

      1122

      50

      132

      132 216 812

      1122

      measurement, the couplant (grease)

      was applied at

      3.2.1. Ultrasonic Pulse Velocity and Compressive strength tests

      The cubes were tested at each of the three curing ages of 7, 14 and 28 days for the ultrasonic pulse velocity. The equipment used for the measurement of the velocity of ultrasonic pulse is that manufactured by the C.N.S. Electronics Company, London, with the trade name PUNDIT.

      The PUNDIT (Transit) time was measured for each cube soon after it had been brought out of water, weighed, and the path length measured. Before

      the position were the transducers were to be placed and the instrument power lead connected to the main plug while the transducers were connected to the terminals. The transmitting transducer was coupled to one face of the cube and the receiving transducer to the other; the instrument immediately displayed the transit time which was recorded. The path length divided by the transit time gave the pulse velocity for the specimen. This test was usually followed by the compressive strength test for each cube, performed using a universal compression testing machine and as prescribed by BS EN 12390-3[16].

  4. RESULTS AND DISCUSSIONS

    1. Fresh paste

      Table 4. Standard consistency and Setting Times of Pastes

      1. Setting times

        The consistency values as shown in Table 4 increases from 29.33% to 53.87% as RHA increases

        RHA

        content (%)

        Consistency (%)

        Initial setting time

        (Hr. +

        Final setting

        time (Hr. +

        from 0% to 50%. The water required for a standard

        minutes) minutes)

        consistency was noted to increase as the RHA content increases. This can be attributed to the finer particle sizes of OPC/RHA blended cement as much water is

        0 29.33

        30 38.99

        40 46.56

        1 + 44

        2 + 27

        3 + 24

        3 + 00

        4 + 30

        5 + 34

        required for proper lubrication.

        Initial setting times were 1.73hours for plain cement paste and 2.45, 3.40 and 4.68 hours for the paste containing 30%, 40% and 50% RHA content respectively; while the final setting times were 3, 4.50, 5.67 and 6.50 hours for the pastes containing

        0%, 30%, 40% and 50% RHA content respectively

        (Table 4).

        These values clearly indicated that there is an increase in both the initial and final setting times of all pastes containing rice husk ash over plain cement paste. This may be attributed to the slower pace of heat induced evaporation of water from the OPC/RHA pastes due to lower cement content [17]; and because the reaction between cement and water is exothermic, a greater amount of heat would be evolved by the plain cement paste because of its higher cement content. The setting times for the plain and pastes containing RHA all satisfied NIS 447 [18] requirements of 4 minutes minimum initial setting time and maximum 10 hours final setting time.

        50 53.87 4 + 41 6 + 30

          1. Fresh concrete

            1. Slump and compacting factor values

              The workability tests performed on the mixes using slump and compacting factor methods presented in Table 5 revealed that to attain the same low workability level in all the mixes containing OPC/RHA with that of the conventional concrete, higher water content was required. This is reflected in the increase in the water/cementitious ratios as the percentage of the RHA increases in all the four design strengths, which have been calculated on the assumption of constant cement content by weight. The results obtained agreed with the earlier results [1, 2].

              The higher water contents in mixes containing RHA could be attributed to the proportion of carbon present in the ash and the high fineness of the ash which meant a greater specific surface to be wetted and lubricated.

              Table 5. Actual water/Cementitious ratios, Slump and Compacting factor values of mixes

              Design strength

              RHA

              content (%)

              Water/Cementitious ratios

              Slump (mm)

              Compacting factor

              (N/mm2)

              15

              0

              0.89

              16

              0.84

              30

              0.91

              15

              0.86

              40

              0.94

              20

              0.87

              50

              0.96

              14

              0.88

              20

              0

              0.65

              17

              0.85

              30

              0.68

              14

              0.86

              40

              0.71

              14

              0.87

              50

              0.74

              19

              0.89

              25

              0

              0.60

              16

              0.84

              30

              0.63

              21

              0.88

              40

              0.68

              20

              0.86

              50

              0.71

              20

              0.88

              30

              0

              0.58

              14

              0.85

              30

              0.60

              15

              0.88

              40

              0.62

              13

              0.86

              50

              0.64

              12

              0.87

          2. Hardened concrete

            1. Compressive strength

              The compressive strengths of all the mixes up to 28 days hydration are shown in Tables 6, 7 and 8 for

              7, 14 and 28 days respectively. From Table 6, the compressive strength for 0% and 30% RHA concretes attained over 60% of the designed strengths at the age of 7 days. At 14 days, the strengths of mixes containing 40% and 50% RHA made over 70% of the 28-day designed strength (Table 7). The compressive strength continued to increase with age up to 28 days, all the mixes, except those designed for 25N/mm2 and 30N/mm2 and containing 50% RHA, attained their designed strength (Table 8). This indicates that grades 15N/mm2 to 30N/mm2 OPC/RHA concrete can attain the same order of

              strength as conventional concrete at the age of 28 days.

              The rate of strength gain of the OPC/RHA mixes increased after the age of 7 days. The strength development of conventional concrete at early all ages is solely a function of cement hydration whereas, the strength development of OPC/RHA concretes at later ages depends on cement hydration as well as pozzolanic reaction involving the silica and alumina present in RHA. It is therefore obvious why the rate of strength gain of the OPC/RHA concretes is higher than that of the conventional concretes beyond 7 days. The compressive strength results agree with those of Ikpong [17].

              Table 6: 7-day Compressive strength and Pulse velocity of conventional and OPC/RHA concretes

              Design

              RHA content

              Density (Kg/m3)

              Pundit Time 10-

              Pulse velocity

              Compressive

              strength

              (%)

              6 (s)

              (Km/s)

              strength (N/mm2)

              (N/mm2)

              15

              0

              2276

              47.4

              3.16

              13.14

              30

              2273

              49.2

              3.05

              12.09

              40

              2322

              48.7

              3.09

              8.94

              50

              2254

              52.6

              2.85

              5.65

              20

              0

              2353

              44.3

              3.39

              18.56

              30

              2304

              42.4

              3.55

              16.70

              40

              2266

              45.5

              3.30

              14.11

              50

              2342

              45.7

              3.34

              11.14

              25

              0

              2325

              41.8

              3.59

              21.71

              30

              2294

              43.4

              3.47

              17.80

              40

              2323

              44.2

              3.40

              14.11

              50

              2290

              43.1

              3.49

              9.99

              30

              0

              2380

              38.0

              3.95

              26.45

              30

              2372

              39.7

              3.79

              21.16

              40

              2283

              42.9

              3.50

              15.61

              50

              2278

              45.6

              3.29

              8.46

              Table 7: 14-day Compressive strength and Pulse velocity of conventional and OPC/RHA concretes

              Design

              RHA content

              Density (Kg/m3)

              Pundit Time 10-

              Pulse velocity

              Compressive

              strength

              (%)

              6 (s)

              (Km/s)

              strength (N/mm2)

              (N/mm2)

              15

              0

              2320

              38.6

              3.89

              17.82

              30

              2239

              43.7

              3.43

              16.04

              40

              2367

              48.5

              3.09

              14.27

              50

              2262

              45.9

              3.27

              10.33

              20

              0

              2340

              42.8

              3.50

              22.58

              30

              2323

              41.8

              3.59

              17.16

              40

              2294

              40.3

              3.72

              14.45

              50

              2328

              41.6

              3.61

              11.52

              25

              0

              2335

              44.5

              3.37

              25.52

              30

              2337

              40.0

              3.75

              22.46

              40

              2306

              41.6

              3.61

              19.65

              50

              2345

              42.3

              3.55

              16.59

              30

              0

              2392

              34.0

              4.41

              29.14

              30

              2307

              37.0

              4.05

              24.77

              40

              2308

              38.1

              3.94

              21.27

              50

              2321

              40.2

              3.73

              18.07

              Table 8: 28-day Compressive strength and Pulse velocity of conventional and OPC/RHA concretes

              Design

              RHA content

              Density (Kg/m3)

              Pundit Time 10-

              Pulse velocity

              Compressive

              strength

              (%)

              6 (s)

              (Km/s)

              strength (N/mm2)

              (N/mm2)

              15

              0

              2349

              34.5

              4.35

              23.66

              30

              2293

              34.8

              4.31

              21.29

              40

              2291

              42.1

              4.56

              19.87

              50

              2294

              42.8

              3.50

              18.93

              20

              0

              2312

              30.7

              4.89

              31.54

              30

              2333

              37.3

              4.02

              27.76

              40

              2292

              36.6

              4.10

              25.86

              50

              2295

              38.0

              3.95

              23.97

              25

              0

              2368

              32.1

              4.67

              33.13

              30

              2304

              34.9

              4.30

              29.15

              40

              2336

              36.2

              4.14

              26.84

              50

              2276

              37.3

              4.02

              24.85

              30

              0

              2373

              32.7

              4.59

              41.16

              30

              2289

              34.6

              4.34

              36.22

              40

              2309

              38.8

              3.87

              30.05

              50

              2324

              37.2

              4.03

              26.75

            2. Ultrasonic pulse velocity

              Pulse velocity decreased as the RHA content increased as shown in Tables 6, 7 and 8. The explanation for this is that for the mixes containing RHA, the required water to attain the same workability increased as the RHA content increased. The effect of this would be that more capillaries are left in the RHA concrete as hydration progressed. The presence of voids in concrete has been recognised to be the most important factor that

              influences the velocity of ultrasonic pulse transmission [11]. The speed of pulse propagation is much less through voids than through solid matter, this increases the time of travel of the pulse in voids and hence decreases the calculated velocity. It is observed that there is an increase in the values of the pulse velocity with age of the concrete. This increase in pulse velocity with age can be related to the fact that calcium silicate and aluminates hydrates produced by the pozzolanic reaction of RHA in

              concrete serves to fill unoccupied spaces in the concrete. It then follows that less will be the volume of capillary pores and the greater would be the velocity pulse propagated through the concrete.

            3. Compressive strength – Pulse velocity relation

        Figure 2 shows the plot of cube compressive strength against pulse velocity for the OPC/RHA concretes at all ages, RHA contents and design

        strengths. From the graph, the relationship between compressive strength, fcu in (N/mm2) and pulse velocity, v in (Km/s) is of the form: fcu = 13.49v

        30.30. The coefficient of correlation is 0.825 indicating a strong linear relationship between the two parameters. It means that the cube compressive strength can be predicted from the pulse velocity for OPC/RHA blended concrete up to 28 days hydration period.

        Cube Compressive strength (N/mm2)

        45

        40

        35

        30

        25

        20

        15

        fcu = 13.49v – 30.30

        10 R² = 0.681

        5

        0

        0 1 2 3 4 5 6

        Pulse velocity (Km/s)

        Figure 2: Variation of Cube Compressive strength with Pulse velocity for all ages, design Strength and all replacement levels of OPC with RHA.

  5. Conclusions

    The following conclusions were drawn from the study:

    1. The combined percentages of silica, alumina and iron oxide in the ash used in the study was over 70% and therefore satisfied the ASTMC618 [19] requirements for class F Pozzolans.

    2. Higher water content was required for mixes containing RHA to attain the same workability as concrete without RHA.

    3. The setting times of both conventional paste and paste containing RHA were within the recommended range for ordinary Portland cement as per NIS 444-1[13].

    4. The compressive strength and the pulse velocity of RHA concrete increased with age but decreased with the RHA content. The regression equation for the two parameters is fcu = 13.49v 30.30.

    5. The ultrasonic pulse velocity can be used to assess the strength of rice husk ash concrete up to 28 days hydration.

  6. References

  1. P.K. Mehta, Properties of Blended cement made from Rice husk ash, ACI Journal proceedings, 74 (sept.), 1977, pp. 440-442

  2. D. C. Okpala, Rice husk ash as partial replacement in concrete, The Nigerian Society of Engineers annual conference proceedings, Port-Harcourt, 1987.

  3. M. H. Zhang, and V. M. Malhotra, High performance concrete incorporating rice husk ash as a supplementary cementing material, ACI Material Journal, 93 (6),1996, pp. 629-636.

  4. P.K. Mehta, and N. Pitt, Energy and Industrial materials from crop residuals, Resources, Recovery and Construction, Elsevier Scientific publishing company,1996, pp. 23-38

  5. J. Sampalo, S.J. Coutiaho, and, M.N. Sampalo Portuguese rice husk ash as a partial cement replacement,

    Technical report, Department of Civil Engineering, FEUP, Universidade do porto, Portugal, 2002.

  6. F. Qing-ge, , L. Qing-yu, Y. Qi-jun, Z. San-ying, Y. Lu- feng, and S. Sugita, Concrete with highly active rice husk ash, Journal of Wuhan University of Technology Mater. Sci. Ed. (Sept.), 19 (3), 2004.

  7. S. Sugita, , Q. Yu, M. Shoya, Y. Tsukinaga, and Y. Isojima, (1997). Semi-industrial production of highly reactive rice husk ash and its effect on cement and concrete properties, proceedings 10th International congress on the Chemistry of cement, Sweden, June 2-6, 1997, 9p.

  8. K. Sakr, Effects of Silica fume and rice husk ash on the properties of heavy weight concrete, Journal of Materials in Civil Engineering, 18 (3), 2006, pp. 367-376.

  9. P. Chindraprasirt, , S. Homwuttiwong, and C. Jaturapitakkul, Strength and water permeability of concrete containing palm oil fuel ash and rice husk ash, Construction and Building Materials, 21 (7), 2007, pp. 1492-1499.

  10. M. F. Kaplan, The Relationship between Ultrasonic Pulse Velocity and the Compressive strength of concrete having the same workability but different mix proportions, Magazine Concrete Research, 12 (34), 1960, pp. 3-8.

  11. Neville, A. M., Properties of Concrete, 5th edition, Pitman, New York, 2000.

  12. BS EN 12620: 2002 + AI, Aggregate for Concrete, British Standard Institution, London, 2008.

  13. Standards Organisation of Nigeria, Cement- part 1: Composition, Specification and Conformity criteria for common cements (NIS 444 1), Lagos, Nigeria, SON, 2003.

  14. BS EN 12350 2, Testing fresh concrete: Slump test, British Standard Institution, London, 2009.

  15. BS EN 12350 4, Testing fresh concrete: Degree of Compatibility, British Standard Institution, London, 2009.

  16. BS EN 12390 3, Testing hardened Concrete: Compressive strength of test specimens, British Standard Institution, London, 2009.

  17. A. A. Ikpong, The relationship between the strength and Non-Destructive parameters of rice husk ash concrete, Cement and concrete research, 23, 1993, pp. 387-398.

  18. Standards Organisation of Nigeria, Methods of testing cement: Determination of setting time and soundness, Lagos, Nigeria, SON, 2003.

  19. American Society for Testing and Materials, Standard Specification for Coal fly ash and raw or Calcined natural pozzolans for use in concrete (ASTMC618-08), ASTM, West Conshohocken, PA, 2008.