PID Controller Tuning using Simulink for Multi Area Power Systems

DOI : 10.17577/IJERTV1IS7542

Download Full-Text PDF Cite this Publication

Text Only Version

PID Controller Tuning using Simulink for Multi Area Power Systems

M Nagendra Dr.M.S.Krishnarayalu

Post Graduate Student Professor, HOD

Department of EEE Department of EEE

V R Siddhartha Eng College V R Siddhartha Eng College

Vijayawada 520007, AP, India Vijayawada 520007, AP, India

Abstract

Practically all power systems are of multi- area in nature. Hence study of multi-area power systems (MAPS) is important. Basic problems of MAPS are Automatic Generation Control (AGC) which controls the system frequency and Automatic Voltage Regulator (AVR) that keeps system voltage constant at rated value.

PID controller is an established industrial controller. There are many methods available for tuning of PID controllers. All these methods are used as initial guess for PID controller parameter settings. Later these settings are improved by fine tuning. Now a days simulation softwares are widely popular. MATLAB Simulink is one of them. Hence we take the advantage of simulation tools and propose a method for tuning of PID controllers using simulation. This is a three step method. First step determines the gain parameter. Second step takes care of the transient performance. Third step deals the steady state performance. Finally it

results in good overall performance. First this method is demonstrated in detail for Automatic Voltage Regulator (AVR) of an isolated power system. Then it is applied to a four area power system. These applications vindicate the proposed method of tuning of PID controller.

Keywords: Automatic Generation Control (AGC), Automatic Voltage Regulator (AVR), Multi Area Power Systems (MAPS), Proportional-Integral-Derivative (PID) Controller

1 Introduction:

The main objective of power system operation and control is to maintain continuous supply of power with an acceptable quality to all the consumers in the system. Large scale power systems are normally composed of control areas or regions representing coherent group of generators. In power system, both active and reactive power demands are never steady they continuously change with the rising or falling trend. As the power in AC form has real and reactive components, the real power

balance as well as the reactive power balance is to be achieved. Changes in real power mainly affect the system frequency while changes in reactive power mostly affect the bus voltages. Quality of power supply must meet certain minimum standards with regard to constancy of voltage and frequency. There are two basic control mechanisms namely reactive power balance (for acceptable voltage profile) and real power balance (for acceptable frequency values). The former is called the Automatic Voltage Regulator (AVR) and the latter is called Automatic Generation Control (AGC). The voltage and frequency controller has gained importance with the growth of interconnected system and has made the operation of power system more reliable.

The conventional control strategy for the AGC problem is to take the integral of the area control error as the control signal. An integral controller provides zero steady state deviation but it exhibits poor dynamic performance [12]. To improve the transient response, various control strategies such as linear feedback, optimal control and variable structure control have been proposed [3-5]. However, these methods need some information for the system states, which are very difficult to know completely. The AGC

system investigated consists of four generating areas with reheat thermal systems [6]. Four area reheat thermal system with both AGC and AVR controls are studied in [7].

Fuzzy control methods are applied to AGC problem [8-9]. However these methods also need to be fine tuned. PID controller is a powerful tool to improve both transient and steady state performances. Proper tuning of PID controllers eliminates the need for complex controllers. There are many methods available for tuning of PID controllers [10-11]. All these methods are used as initial guess for PID controller parameter setting. Later these settings are improved by fine tuning. Now a days simulation softwares are widely popular. MATLAB Simulink is one of them. Hence we take the advantage of simulation tools and propose a method for tuning of PID controllers using simulation. This is a three- step method. First step determines the gain parameter. Second step takes care of the transient performance. Third step deals the steady state performance. First this method is demonstrated in detail for Automatic Voltage Regulator (AVR) of an isolated power system. Then it is applied to a four area power system with AGC and AVR.

2. Methodology:

The structure of a PID controller is

(1)

where KP, KI and KD are proportional, integral and derivative gain constants.PID controller tuning can be achieved in three steps. In Step 1 we select KP that results in a highly oscillatory stable response with KD = KI = 0. In Step 2 we fix the parameter KD, for KP selected in Step1, taking care of transient performance. In Step 3 we fix the parameter KI, for KP and KD selected in Steps 1 and 2, taking care of steady state performance.

Step1: First we set the gain parameter KP. Here KD and KI are zero. By trial and error select KP that results in a stable oscillatory performance. Higher KP results in decrease of rise time and steady state error but highly oscillatory response. Higher KP may be employed for a single input system.

In a multi input system if KP is high it is observed that it is difficult to damp out these oscillations. Hence select a KP resulting in near to critical damping in case of multiple inputs.

Step 2: Now using derivative control reduce the above oscillations by providing proper damping which results in reasonable overshoot and settling time. This can be achieved by varying KD with KP found in

Step 1 and analyzing the resulting response from the corresponding simulation. So we have fixed KP and KD. Still KI = 0.

Step 3: So far we have taken care of transient performance. What remains is steady state performance. Here we concentrate on steady state error. If steady state error is not zero, then for the values of KP and KD fixed in Step 2, vary KI and select the KI that results in zero steady state error in minimum time.

This completes the tuning of PID controller. Please note that sometimes Step 2 or 3 may not be required. That is PD or PI controller is good enough.

    1. Case Study 1: AVR of Isolated Power System

      The proposed methodology mentioned in Section 2 is implemented on the AVR of the following isolated power system.

      Fig1: AVR with PID controller According to step1 select the gain parameter KP = 6, here KI and KD are zero. This makes system unstable. By trial and error decreasing the value of KP to1.1 results in stable oscillatory response. Further decrease in KP leads to high rise time and

      steady state error which is not desirable. From step 2, select the gain parameter KD such that the above oscillations are reduced, KD = 0.2 results in damped oscillations with the selected value of KP in step1and KI = 0. As steady state error still exists, according to step 3 select the value of gain parameter KI that results in zero steady state error in minimum time. KI = 0.5 results in better steady state performance. This completes the tuning of PID controller for the AVR system. Resulting voltage response of AVR is shown in Fig 2. From the figure we note that both transient and steady state performances are good.

      1.4

      1.2

      terminal voltage in p.u.

      1

      0.8

      0.6

      04

      primarily composed of an integral controller. The integrator gain is set to a level that compromise between fast transient recovery and low overshoot in the dynamic response of the overall system. This type of controller is slow and does not allow the controller designer to take into account possible non- linearity in the generator unit. . So the PID controller will be used for the stabilization of the frequency in the AGC problems. So tuning of PID controller is very important to get optimal performance.

      PID controller consists of Proportional, Integral and Derivative actions. It is usually tuned by Ziegler-Nichols method. Ziegler- Nichols method is by far the most common control algorithm [12]. In this paper we propose a simple method for tuning of PID controller through MATLAB Simulink. The

      0.2

      0

      0 1 2 3 4 5 6 7 8 9 10

      time in sec

      proposed methodology is implemented for

      AGC and AVR of four area power system.

      Fig2: Voltage response of AVR of isolated power system

    2. Case Study 2: AGC and AVR Control in Multi Area Power System

In order to keep the power system in normal operating state, a number of controllers are used in practice. Because of the inherent nonlinearities in system components and synchronous machines, most of the Automatic Generation Controllers are

Fig 3 shows the simplified representation of four area power system. Fig 4 shows the Area1 (with AGC and AVR) of four area power system. Modeling of different components for AGC and AVR are taken from reference paper [7]. System parameter values are shown in Tables 1 and 2.

Area 3

Area 2

Area 1

Area 4

Fig 5, 6, 7, 8 shows the frequency responses of this four area power system with PID controller tuned by this method (Table 4) and Integral control only [7]. Fig 9, 10 shows the variation of tie-line exchange power and mechanical output power with PID controller and those of [7]. Fig 11, 12

Fig 3: Simplified representation of four area power system

Fig4: Area1 (with AGC and AVR) of four area power system

4. RESULTS AND DISCUSSIONS:

PID controllers of the form (1) are used in AGC and AVR modeling. These PID controllers are tuned as mentioned in Section 2 and shown in Tables 3 and 4. Figs 5-12 show the resulting responses.

shows the voltage response of this power system for the tuning given in Table 3 and those of [7].

From all these figures we note that the results are better with PID controller tuned by this method compared to Integral control with less overshoot/undershoot and settling time.

0.005

0

pid integral

-0.005

change in frequency

-0.01

-0.015

-0.02

-0.025

-0.03

-0.035

-0.04

-0.045

0 5 10 15 20 25 30 35 40 45 50

time in sec

Fig5: Frequency response of area-1

0.01 0.6

0 0.5

pid

integral

change in frequency

-0.01

-0.02

0.4

MW

0.3

dpm1

dpm2

dpm4

-0.03

-0.04

-0.05

-0.06

0.01

0

0 5 10 15 20 25 30 35 40 45 50

time in sec

Fig6: Frequency response of area-2

0.2

0.1

0

-0.1

dpm3

tie line power flow

0 5 10 15 20 25 30 35 40 45 50

time in sec

Fig9: Tie-line power of four areas with Integral controller

-0.01

chane in frequency

-0.02

-0.03

-0.04

pid integral

0.8

0.7

0.6

0.5

MW

0.4

0.3

dpm4

dpm2

dpm3

dpm1

-0.05

0.2

0.1

tie line power flow

-0.06

-0.07

0

-0.01

change in frequency

-0.02

0 5 10 15 20 25 30 35 40 45 50

time in sec

Fig7: Frequency response of area-3

pid

integral

1.4

1.2

0

-0.1

0 2 4 6 8 10

time in sec

Fig10: Tie-line power of four areas with PID controller

-0.03

-0.04

-0.05

1

area1 area2 area3 area4

terminal voltage

0.8

0.6

0.4

-0.06

0 5 10 15 20 25 30 35 40 45 50

time in sec

Fig8: Frequency response of area-4

0.2

0

0 5 10 15 20 25 30 35 40 45 50

time in sec

Fig11: Voltage response of four areas With integral controller

1.4

1.2

1

terminal voltage

area1

0.8 area2

area3

Table 2: Simulation parameters for AVR

0.6 area4

Component

Gain

Time constant

AMPLIFIER

9

0.1

EXITER

1

0.4

GENERATOR

1

1.0

SENSOR

1

0.05

0.4

0.2

0

0 1 2 3 4 5 6 7 8 9 10

time in sec

Fig12: Voltage response of four areas with PID controller

Table 1: Parameters used in simulation

Area-1

H1=5, TT1=0.5sec, TG1=0.2sec,

R1=0.051,D1=0.62

Area-2

H2=4,TT2=0.6sec, TG2=0.3sec,

R2=0.065,D2=0.91

Area-3

H3=4.5,TT3=0.7sec, TG3=0.4sec,

R3=0.089,D3=0.95

Area-4

H4=4, TT4=0.6sec, TG4=0.3sec,

R4=0.066,D4=0.92

T12=T13=T14=T21=T23=T31=T32=T41=0

.545

T24=T34=T42=T43=0

PLi = 0.1802 pu

TT: Turbine time constant, TG: Governor time constant, R: Regulation parameter, Kp: Power system gain, Tij: Synchronizing coefficient, B: Frequency bias parameter,

Pli: load disturbance, H: Inertia constant, Base power 1000MVA,Frequency 50hz

of AGC

Table 3: PID controller parameters for AVR

PID

parameters

Area-

1

Area-

2

Area-

3

Area-

4

KP

1

1

1

1

KI

0.65

0.65

0.65

0.65

KD

0.35

0.35

0.35

0.35

Table4: PID controller parameters for AGC

PID

parameters

Area-

1

Area-

2

Area-

3

Area-

4

KP

0.8

1

1.2

1

KI

0.7

0.8

1

0.8

KD

1

1

1.2

1

6. CONCLUSIONS

This paper presents a new simple tuning method for PID controller through MATLB simulink and is applied to four area power system consisting of both AGC and AVR. Case study 1 presents the proposed methodology. The case study 2 presented justifies the proposed method with better results for a MAPS. Next this method will be applied to a MAPS consisting of nonlinearities.

ACKNOWLEDGEMENTS

We greatly acknowledge Siddhartha Academy of General and Technical Education, Vijayawada for providing the facilities to carryout this research.

REFERENCES:

  1. JALEELI, N.EWART, D. N.FINK,

    L. H.: Understanding Automatic Generation Control, IEEE Trans. on Power Systems 7 No. 3 (1992), 11061122.

  2. ELGERD, O. I.: Electric Energy System Theory: An Introduction, Mc Graw-Hill, New Yourk, 1971.

  3. HSSU, Y.CHAN, W.Optimal Variable Structure Control of Interconnected Hydrothermal Power Systems, Electrical Power and Energy Systems 6 (1984, 2231.

  4. ALI-HAMOUZE, Z.ABDEL MAGIDE, Y.: Variable Structure Load Frequency Controllers for Multi Area Power System, Inter. Journal Electrical Power Energy System 15 (1995), 2229.

  5. KARNAVAS, Y. L.: On the Optimal Control of Interconnected Power Systems in a Restructured Environment Using Genetic Algorithms, WSEAS Trans. on System Journal 4 No. 8 (2004), 12481258.

  6. Yao Zhang, Lili Dong, Zhiqiang Gao;

    Load Frequency Control for Multiple-Area Power Systems, 2009 American Control Conference Hyatt Regency Riverfront, St. Louis, MO, USA June 10-12, 2009.

  7. Mat lab Design and Simulation of AGC and AVR for Multi Area Power System and Demand Side Management Praveen Dabur*, Naresh Kumar Yadav* and Vijay Kumar Tayal** International Journal of Computer and Electrical Engineering, Vol. 3, No. 2, [8]Automatic Generation Control with Fuzzy logic controller in the power system including three areas by engin yesil, aysen demiroren, erkin yesil department of electrical eng., electric&electronic faculty istanbul technical university, 80626 masla Istanbul ,turkeyApril, 2011 1793-8163 [9]Load Frequency Control in Four Area Power Systems Using Fuzzy Logic PI

Controller by Emre Ozkop1, Ismail H.

Altas1, Adel M. Sharaf2

  1. The Design of PID Controllers using Ziegler Nichols Tuning Brian R Copeland March 2008

  2. PID Controller Tuning Using Bodes Integrals Alireza Karimi, Daniel Garcia and Roland Longchamp

[12]B. Venkata Prasanth, Dr. S. V. Jayaram Kumar,Robust Fuzzy Load Frequency Controller for a Two Area Interconnected Power System , Journal of Theoretical and Applied Information Technology. pp. 242 – 252.