Strength Evaluation of Fire Affected Hospital Building by using Non Destructive Test
Er. Skindar Bakht Shah
Research Scholar, Dept. of Civil Engineering.
Indo-global group of Colleges.
Abhipur, Mohali, India
Er. Manjit Kaur
Assistant Prof, Dept.of Civil Engineering Indo-global group of Colleges
Abhipur, Mohali. India
Abstract:- Concrete is broadly utilized for the development of frameworks, for example, structures, spans, cooling towers, stacks, mechanical and other numerical structures. Fire is one of the most damaging incidental loads that a structure can be oppressed during its lifetime. The measure of harm caused will depend for the most part on the seriousness and the term.
The physical properties of concrete and the
reinforcement steel are altered by the temperature and range of fire. Recovery of flame harmed structures are typically favored than destroying and remaking. Assessment of fire damaged concrete usually starts with visual observation followed by Non destructive tests Rebound hammer test, ultrasonic pulse velocity test, Carbonation Test. The Rebound hammer and ultrasonic pulse velocity measurements made on a structure will provide a qualitative estimation of the damaged members with the undamaged one. This paper outlines a methodology for assessing the condition of a fire damaged concrete structure based on non-destructive; the observations of the fire affected hospital building were taken and then compare with fire un-affected portion of the hospital building.
Key words: Fire damaged, Rebound hammer, Ultrasonic pulse velocity, Rehabilitation
-
INTRODUCTION
The purpose of using Non destructive tests is to determine the quality and integrity of materials, components or assemblies without affecting the ability to perform their intended functions. This paper deals with the change in properties of a fire affected concrete. Now days there are incidents of fires in buildings are often heard which are increasing day by day and also the repair and rehabilitation of fire damaged structures has become an area for study and research. Many efforts are been laid down to carry out research in these related fields. To build a structure usable again after fire damage is a discipline of great concern by civil engineering community. Concrete is known to exhibit a good behavior at high temperature, and the concrete is incombustible in Nature. Generally concrete having low thermal conductivity, which guarantee a slow propagation of thermal transients within the structural members. It was confirmed from the fire affected hospital building caused due to gas explosion located in Baramulla, Jammu and Kashmir that the physical and mechanical properties of concrete affected due to elevated temperature. A significant reduction in compressive strength, tensile strength has been found in the fire affected hospital building. Physical properties such as density, porosity, color and morphological properties were also remarkably affected.
Hence there is a need of using Non destructive test techniques to evaluate the properties of fire affected hospital building.
Key words: Non destructive test, compressive strength, tensile strength, porosity
-
LITERATURE REVIEW
Adam Levesque et al [2019] This research focuses on the effect of fire on structures due to the Boko Haram insurgency in Maiduguri, Northern Nigeria. It is aimed at giving a further contribution to understand the effect of fire with respect to the local aggregates, quenching methods and proposing an assessment methodology based on a suitable analytical procedure applied to reinforced concrete subjected to sustained fire. . The samples were burnt in a designed fire simulation furnace using sugarcane bags as fuel with varying air velocities for 2 hours. Cooling of samples was carried out using water splashing, CO2 powder fire extinguisher and air cooling methods before the compressive strength tests using a Seidner Compressive Testing Machine and Non-destructive test with Rebound Hammer. Kumavat H.R. et al. (2014) The paper present case study include the use of various Non- Destructive Test (NDT), to evaluate the concrete quality of building age was 8 years. Initially, the structure deteriorates due to cyclic temperature variations, physical causes and aggressive chemical attack the research paper also focus on standard testing procedure of NDT and sequence of operation for obtaining accuracy as well as the problems created during the testing and the limitations of the tests are considered. Said M. Allam, Hazem M.F and Elbakry Alaa G. Rabeai [2013] has investigated The behavior of reinforced concrete slabs under fire loading has been studied by researchers for many decades . It is well known that when the temperature increases the slab fire resistance decreases. This is because when concrete is exposed to heat, chemical and physical reactions occur such as loss of moisture, dehydration of cement paste and decomposition of the aggregate. Such changes lead to high pore pressures caused by the water evaporation, internal micro cracks and damages appear in concrete Also, the increase in the temperature leads to a decrease in the yield strength of the steel reinforcement. Concrete spelling under high temperatures is a major factor of reducing its fire resistance. The spelling is caused by the build-up of pore pressure during heating. F Ali, A Nadjai, A Abu-Tair [2011] has investigated the Explosive spalling of high
performance concrete under fire is one of the major concerns in front of the engineering community today. It is associated with violent failure of thin layers of concrete resulting in sudden reduction of load carrying capacity which may lead to complete collapse. High pore pressures due to low permeability and stresses due to thermal gradients are considered to be the governing causes of explosive spalling. However, the failure mechanisms and all influencing parameters are not yet fully understood. The most popular method to prevent spalling is the addition of polypropylene (PP) fibers in concrete. It is generally accepted that the PP fibers leave a porous network after melting at around 160 °C, leading to an increase in permeability, thus allowing the water vapors to escape. Mohammad Reza Hamadan et al.(2009) In this research paper authors used Rebound hammer test and Ultrasonic pulse velocity test on specimen and existing structure and got compressive strength of concrete and comparison along with actual compressive strength which is obtain from compressive testing machine. The structural health monitoring by NDT methods comprised of UPV and RSH (Schmidt Rebound Hammer) were carried out in laboratory and site. The experimental investigation using NDT methods showed that a good correlation exists between compressive strength, SRH and UPV. Ian A.FLETCHER, Stephen WELCH, José L. TORERO, Richard O. CARVEL, Asif USMANI [ 2007] has investigated the performance of steel during a fire is understood to a higher degree than the performance of concrete, and the strength of steel at a given temperature can be predicted with reasonable confidence. It is generally held that steel reinforcement bars need to be protected from exposure to temperatures in excess of 250-300°C. This is due to the fact that steels with low C-contents are known to exhibit blue brittleness between 200 and 300°C. Concrete and steel exhibit similar thermal expansion at temperatures up to 400°C; however, higher temperatures will result in significant expansion of the steel compared to the concrete and, if temperatures of the order of 700°C are attained, the load-bearing capacity of th steel reinforcement will be reduced to about 20% of its design value. M.Z. Mohamed Firdows et al (2005) 34-year old industrial building was investigated to assess the extent of damage and the cause(s) of deterioration. This study involved visual inspection, non-destructive testing, and laboratory analysis for materials collected from the building. Besides rebound hammer and ultrasonic pulse velocity tests, cores were also extracted from select locations and a detailed analysis of the hardened concrete was carried out. Half-cell potential and concrete resistivity measurements were also conducted. The results of the testing and analysis indicated that the structural members were affected due to chlorine gas emission and carbonation. This paper describes details of the investigations carried out, evaluation of test results and recommendations on measures for strengthening the building. N.R. Short, J.A. Purkiss, et al [2001] this paper deals with Assessment of fire damaged concrete structures usually starts with visual observation of color change, cracking and spalling. On heating, a change in color from normal to a pink/red is often observed and this is useful
since it coincides with the onset of significant loss of concrete strength. . The full development of the pink/red color is coincident with substantial reduction in compressive strength and the method may be used to define the distance from a heated surface where strength degradation has occurred. J.K Chege et al (2000) this paper deals with a bomb blast affected building suffered extensive damage to structural elements and other areas of a building. Major and crucial information necessary in the evaluation included the mapping of the extent of damage which calls for both visual examination and extensive use of Non Destructive Testing Equipment and skilled personnel capable of checking for cracks, materials damage, and reinforcement bars condition including location sizing and strength measurement of critical structures elements.
-
OBJECTIVE OF THE STUDY
-
To Investigate the Rebound hammer measurements on fire un-affected concrete and compare with the values of fire affected concrete
-
To Investigate The Compressive Strength with the help of Rebound Hammer on fire un-affected concrete and compare with fire affected concrete
-
To Investigate the Ultrasonic Pulse Velocity (UPV) measurements on fire un-affected concrete and compare with the values of fire affected concrete.
-
To Investigate Any Discontinuity in cross section of structure like cracks, cover concrete delaminating.
-
To investigate the carbonation effect on fire affected and fire UN affected .concrete then compare with the obtained results.
-
To investigate the carbonation depth of the concrete cover over the reinforcement
-
-
METHODOLOGY
A precise methodology for completing a logical examination of a flame influenced in hospital building and the influenced in hospital building and the parameters that are to be assessed from these tests are displayed.
The review depends on the
-
Visual Inspection (Photographic Inspection).
-
Source of fire and its location in the building
-
Locations of portions with extensive, moderate and no-damage.
-
Color of concrete.
-
Spalling of concrete, horizontal and vertical cracks in concrete.
-
Damage of structural steel sections and their locations Inspection over damaged portions
-
-
Conditional Survey.
The motivation behind the overview is to gather adequate information to pinpoint the reason and wellspring of the issue and to decide the degree of the harm. Contingent
upon the reasonable justification of the harm, the site work includes a mix of the accompanying procedures:
-
Detailed visual inspection;
-
Survey of cracks, spalling, concrete degradation etc.
-
Drilling holes or mini-cores for carbonation test
-
Coring of concrete for determination of strength and petrography examination;
-
Rebound hammer test for compressive strength (comparison only);
-
Ultrasonic pulse velocity test for honeycombing depth of cracks, or compressive strength (comparison only).
-
-
Non-Destructive Testing.
These tests are based on indirect measurement of concrete strength through measurement of surface hardness and dynamic modulus of elasticity. Calibration curves relating these properties to the strength of concrete are available. The most commonly adopted NDT methods for assessment of the strength of concrete and their principles are given in the following
Rebound Hammer: – Spring-driven mass strikes the surface of concrete and rebound distance is given in R- values. Surface hardness is measured and strength estimated from calibration curves, keeping in mind the limitations.
Ultrasonic Pulse Velocity: – It operates on the principle that stress wave propagation velocity is affected by the quality of concrete. Pulse waves are induced in materials and the time of arrival measured at the receiving surface.
Carbonation Test: – Carbonation occurs when CO2 from air finds its way into the body of concrete through its pores in presence of moisture & water forms carbonic acid which neutralizes the Ca (OH) 2 formed due to their action during setting of concrete thus reducing the alkalinity of concrete
Table 1: Relation between Rebound No and Concrete Quality
AVERAGE REBOUND
QUALITY OF CONCRETE
>40
30-40
20-30
<20
0
Very Good Good
Fair
Poor and/or delaminated Very Poor and/or delaminated
Table 2: Relation of Pulse velocity with Quality of concrete
PULSE VELOCITY (KM/SEC.)
QUALITY OF CONCRETE
0-2
2-2.5
2.5-3
3-4
POOR DOUBTFUL MEDIUM
GOOD
Picture 1 (Spalling of Concrete)
S.No
Specification
Data
1
Building
Hospital
2
Location
Baramulla Jammu and Kashmir
3
Fire accident
31 July 2015
4
Floors
3
5
Height of building
11 m
6
Grade of Concrete
M 25
7
Grade of steel
Fe 415
S.No
Specification
Data
1
Building
Hospital
2
Location
Baramulla Jammu and Kashmir
3
Fire accident
31 July 2015
4
Floors
3
5
Height of building
11 m
6
Grade of Concrete
M 25
7
Grade of steel
Fe 415
-
-
RESULT AND DISCUSSION Table: 3 Specifications of the building
REBOUND HAMMER TEST
Table: 4 Ground Floor Fire Affected Portion.
C No.
Reading
R No.
Compressive Strength(N/mm2)
Quality
1
2
3
4
5
6
C1
20
30
35
34
32
33
30
24
Fair
C4
29
31
27
30
28
26
29
23
Fair
C7
31
25
30
26
29
30
28
22
Fair
C13
29
28
26
25
28
27
27
20
Fair
C7
25
23
25
26
22
28
25
18
Delaminated
B1
30
32
31
25
24
29
28
23
Fair
C8
25
32
25
32
33
28
30
24
Fair
Table: 5 First and second Floor Fire Un Affected Portion.
C No.
Reading
R No.
Compressive Strength(N/mm2)
Quality
1
2
3
4
5
6
C6
33
31
25
39
35
25
31
25
Good
C14
50
35
20
32
29
27
32
26
Good
C5
33
31
33
27
33
30
32
26
Good
B8
33
31
29
31
33
29
30
24
Fair
B9
30
35
29
36
30
28
31
25
Good
SECOND FLOOR
C6
35
33
30
35
32
33
33
28
Good
C7
35
30
38
35
30
35
34
30
Good
C8
30
30
39
30
38
30
32
26
Good
C9
30
30
30
35
38
38
33
28
Good
C5
33
35
32
30
38
32
33
28
Good
C3
31
34
33
35
38
34
34
30
Good
C2
39
32
32
35
31
35
34
30
Good
30
25
20
15
30
25
20
15
compressi
ve strenth
compressi
ve strenth
10
5
0
10
5
0
30 29 28 27 25 28 30
30 29 28 27 25 28 30
31
30
29
28
27
26
25
24
31
30
29
28
27
26
25
24
compressi
ve
strength
compressi
ve
strength
33 34 32 33 34
33 34 32 33 34
Fig: 1 Graph between compressive strength and rebound number of Fire affected portion.
Fig: 2 Graph between compressive strength and rebound number of Fire un-affected portion
Ultrasonic pulse Velocity Test
Table: 6 Ground Floor Fire Affected Portion
C No.
Distance (Metre)
Time
Velocity
Time
Velocity
Average Velocity
Method
Quality
I
I
II
II
C4
0.381
180
2.116
170
2.241
2.178
Direct
DOUBTFUL
C10
0.381
177
2.152
180
2.116
2.134
Direct
DOUBTFUL
C11
0.381
180
2.116
175
2.177
2.146
Direct
DOUBTFUL
C12
0.381
151
2.523
160
2.381
2.452
Direct
DOUBTFUL
C13
0.381
180
2.116
171
2.228
2.172
Direct
DOUBTFUL
C14
0.381
177
2.152
185
2.059
2.105
Direct
DOUBTFUL
B1
0.381
180
2.116
172
2.215
2.165
Direct
DOUBTFUL
C6
0.178
80
2.225
76
2.342
2.283
Indirect
DOUBTFUL
C7
0.178
75
2.373
71
2.507
2.440
Indirect
DOUBTFUL
C5
0.178
75
2.373
78
2.282
2.327
Indirect
DOUBTFUL
Table: 7 First and second Floor Fire UN Affected Portion.
C No.
Distance (Metre)
Time
Velocity
Time
Velocity
Average Velocity
Method
Quality
I
I
II
II
C8
0.381
175
2.177
182
2.093
2.135
Direct
DOUBTFUL
C7
0.381
182
2.093
170
2.241
2.167
Direct
DOUBTFUL
C6
0.381
170
2.241
177
2.152
2.196
Direct
DOUBTFUL
C3
0.381
174
2.196
171
2.228
2.212
Direct
DOUBTFUL
C5
0.178
71
2.570
80
2.225
2.397
Indirect
DOUBTFUL
C13
0.178
73
2.488
75
2.373
2.410
Indirect
DOUBTFUL
C12
0.178
75
2.373
75
2.373
2.373
Indirect
DOUBTFUL
C11
0.178
77
2.351
71
2.570
2.460
Indirect
DOUBTFUL
C10
0.178
80
2.225
71
2.570
2.397
Indirect
DOUBTFUL
C9
0.178
75
2.373
77
2.351
2.362
Indirect
DOUBTFUL
SECOND FLOOR
C7
0.381
120
3.175
113
3.371
3.273
Direct
Good
C12
0.178
65
2.740
61
2.940
2.840
Indirect
MEDIUM
C11
0.178
60
2.960
65
2.740
2.850
Indirect
MEDIUM
C10
0.178
61
2.940
62
2.870
2.905
Indirect
MEDIUM
C9
0.178
74
2.450
69
2.580
2.515
Indirect
MEDIUM
C8
0.381
120
3.175
113
3.392
3.30
Direct
GOOD
C6
0.178
72
2.455
65
2.740
2.597
Indirect
MEDIUM
C4
0.178
65
2.740
61
2.940
2.840
Indirect
MEDIUM
B8
0.178
60
2.960
62
2.870
2.915
Indirect
MEDIUM
The building is essentially a three storied framed structure having columns and beams running in perpendicular directions and is covered by R.C.C. slab. The fire has occurred mainly in the Ground floor of the building , so readings obtained from the rebound hammer test in fire affected portion of the building are not satisfactory as compared with Readings obtained from the rebound hammer test on second floor of the building are satisfactory as the concrete used in building is of M25 grade.
Based on the UPV values, the members may be classified as:
-
Unaffected – members with hair cracks and UPV values greater than 3.5 km/sec
-
Moderately affected- members with wide cracks and UPV values between 2.5 and 3.5km/s
-
Fairly affected – members with major cracks, spalling of concrete, and UPV values
Below 2.5 km/sec
-
Severely affected – major cracks, spalling of concrete, exposure and de-bonding of Reinforcement and finally the load carrying capacity can be
calculated based on the Parameters evaluated using the various test results.
3.5
3
2.5
2
fire affected
3.5
3
2.5
2
fire affected
1.5
1
fire un
affected
1.5
1
fire un
affected
0.5
0
0.5
0
Fig: 3 Graph between pulse velocity (km/s) and Quality of concrete for fire affected and un-affected.
-
-
CONCLUSION AND FUTURE SCOPE
-
The duration of fire in the room is of one hour and the estimated temperature is of the order of 300- 500ºC.
-
The Ground Floor of the building is majorly affected by the fire and heat. Because of high temperature, the concrete cover is spalling out of the main members.
-
Rebound hammer shows higher compressive strength in fire un affected portions than of fire affected portions.
-
The effect of fire is clearly observed in UPV values i.e., the UPV readings of Un affected portion is higher than the affected portion.
-
The Core was also extracted from one of the front columns up to 250mm depth, which shows the concrete is affected up to the cover level.
-
The pH of concrete is decreased to 9 at Ground floor.
-
-
RECOMMENDATIONS
-
By using these results we can modify the properties of hospital buildings.
-
To increase the compressive strength of fire affected buildings Concrete Jacketing has been used to increase the capacity of existing structures by placing cage around the beams and columns
-
Grouting technique can be used on inclined and vertical cracks on walls, columns and beams.
-
Epoxies and Epoxy Systems including Epoxy Concretes are used as repairing materials.
-
Keim mineral paints preferred to protect from carbonation.
-
-
REFERENCES
-
Adam Levesque et al [2019] effect of fire on structures due to the Boko Haram insurgency in Maiduguri, Northern Nigeria American journal of civil Engineering and Architecture .2019,Vol 7 10.12691/ajcea-7-1-1.
-
Kumavat H.R. et al. [2014] The concrete evaluation is necessary for the proper diagnosis of successful rehabilitation work International Journal of Research in Engineering and Technology EISSN: 2319-1163.
-
Said M. Allam, Hazem M.F and Elbakry Alaa G. Rabeai [2013] behavior of reinforced concrete slabs under fire loading has been studied by researchers for many decades International Journal for Innovative Research in Science & Technology| ISSN (online): 2349-6010.
-
F Ali, A Nadjai, A Abu-Tair [2011] explosive spalling of normal strength reinforced concrete slabs subjected to conventional fire F Ali, A Nadjai, A Abu-Tair – Materials and structures.
-
Mohammad Reza Hamadan et al.(2009) Rebound hammer test and UPV on specimen and existing structure and got compressive strength of concrete and comparison along with actual compressive strength which is obtain from compressive testing machine. International Journal of Research in Engineering and Technology.
-
Ian A.FLETCHER, Stephen WELCH, José L. TORERO, Richard O. CARVEL, Asif USMANI [ 2007] steel during a fire is understood to a higher degree than the performance of concrete, and the strength of steel at a given temperature can be predicted
with reasonable confidence Directory of Open Access Journals , pp. 37-52(16).
-
M.Z. Mohamed Firdows, A. Chellapan, J. Prabhakar and P. Srinivasan[2005],assessing the quality of in-situ concrete in the turbo generator foundation using UPV measurements, The Indian concrete journal, Feb 2005.
-
N.R. Short U, J.A. Purkiss, et al [2001] Assessment of fire damaged concrete structures usually starts with visual observation of color change, cracking and spalling. Magazine of Concrete Research, Volume 54
-
J.K Chege, NDT Application in Structural Integrity Evaluation of Bomb Blast Affected Buildings, 15th WCNDT-Roma, Apr 2000.
-
IS 13311: 1992 (Part 1), Indian Standard Non-Destructive testing of Concrete-Methods of Test, Part 1-Ultrasonic Pulse Velocity.
-
IS 13311: 1992 (Part 2), Indian Standard Non-Destructive testing of Concrete-Methods of Test, Part 2-Rebound Hammer
-
BS 6089: 1981, Guide to Assessment of concrete strength in existing structures.
-
BS 1881 Part 201:1986, British Standard Testing Concrete, Part 201-Guide to the use of Non-Destructive Methods of Test for Hardened Concrete.
-
BS 1881 Part 202:1986, British Standard Testing Concrete, Part 202 Recommendations for Surface Hardness Testing by Rebound Hammer.