- Open Access
- Authors : Navasakthivel, Riyaz Ahamed, S. Ayswarya
- Paper ID : IJERTCONV7IS11087
- Volume & Issue : CONFCALL – 2019 (Volume 7 – Issue 11)
- Published (First Online): 14-12-2019
- ISSN (Online) : 2278-0181
- Publisher Name : IJERT
- License: This work is licensed under a Creative Commons Attribution 4.0 International License
A Hybrid Power Control Concept for PV Inverters
Navasakthivel
DEPT OF EEE-PITS
Riyaz Ahamed
DEPT OF EEE-PITS
S. Ayswarya Assistant Professor DEPT OF EEE-PITS
control with a reduced power mode control has been
Abstract:- This letter proposes a hybrid power control concept for grid-connected photovoltaic (PV) inverters. The control strat- egy is based on either a maximum power point tracking control or a constant power generation (CPG) control depending on the instantaneous available power from the PV panels. The essence of the proposed concept lies in the selection of an appropriate power limit for the CPG control to achieve an improved thermal per- formance and an increased utilization factor of PV inverters, and thus, to cater for a higher penetration level of PV systems with in- termittent nature. A case study on a single-phase PV inverter under yearly operation is presented with analyses of the thermal loading, lifetime, and annual energy yield. It has revealed the trade-off fac- tors to select the power limit and also verified the feasibility and the effectiveness of the proposed control concept.
Index TermsConstant power generation (CPG), efficiency, maximum power point tracking (MPPT), photovoltaic (PV) in- verters, reliability, thermal loading.
-
INTRODUCTION
MAXIMUM power point tracking (MPPT) is effective for photovoltaic (PV) inverters to maximize the energy har- vested from PV panels [1]. However, with increasing installa- tions of PV systems into the grid, the following issues appear if the inverters keep operation at MPPT mode even within the rated power range: 1) overloading of the grid at peak power generation [2] which may induce system level over-voltage and line frequency instability [3];
2) limited utilization of the PV inverters, since they operate at relatively low power level with respect to the designed power rating during most of long-term field operations; 3) high temperature peaks and variations on switching devices due to the intermittency, which accelerates the degradation of the switching devices [4].
To tackle the overloading issue, expanding the grid infrastruc- ture [5] (e.g., transformers, conductors) and integrating energy storage elements [6] are two of the solutions. However, as re- ported in [7], the expenses increased by grid expansion may severely exceed the initial project outlay. The energy storage elements are mostly installed at the substation side instead of in the individual inverters also considering cost and maintenance. Since the aforementioned solutions introduce considerable in- vestments, two kinds of hybrid control concepts have been pro- posed in prior-art research. In [3], an MPPT
introduced to avoid dy- namic overloading in a stand-alone wind-PV generation system. The selection of the power limit for the reduced power mode control is dynamically in accordance to the power oscillations during wind turbine soft stalling. The reduced power mode op- eration is achieved by modifying the MPPT algorithm based on a virtual MPPT. In [8], an MPPT control with power curtailment control is proposed to prevent over-voltage of low voltage feed- ers by limiting the excessive power injection to the grid from PV inverters. The selection of the power limit for the power cur- tailment control depends on the upper voltage limit of the low voltage feeders. These control concepts can effectively avoid the over-loading issue with an acceptable reduction of the over- all energy generation [9]. However, the issue on the utilization of PV inverter remains and the thermal performance of the PV inverters is still unknown.
This letter therefore proposes a hybrid power control concept with the objective to improve the thermal performance and in- crease the utilization factor of PV inverters. It has the following features: 1) a constant power generation (CPG) control mode is activated by using a direct power control when the dc power from PV panels reaches to a specific limit, the value of which depends on the trade-offs of thermal loading (therefore lifetime) of switching devices, PV inverter utilization factor, and annual energy yield under yearly mission profiles (i.e., solar irradiance and ambient temperature). It should be noted that the selection of this power limit is different from those in [3] and [8] as dis- cussed above. 2) The MPPT mode is active when the dc power is below the specific power level. The proposed MPPT-CPG con- trol concept allows a reduction of required power ratings of PV inverters and also a reduction of junction temperature peaks and variations on the power devices (i.e., an extended lifetime [4], [10], [11]). Meanwhile, it could contribute to the system level power management to some extent, due to its role in smoothing and limiting the power fed into the grid. The concept, imple- mentation, feasibility and effectiveness of the control strategy are discussed below.
-
PROPOSED HYBRID POWER CONTROL CONCEPT
The single-phase two-stage configuration is preferable for residential PV applications [1]. The control structure of a
Fig. 1. Schematic and control diagram of a two-stage single-phase PV system with the proposed hybrid control concept.
Fig. 3. PV characteristics with limiting maximum feed-in power control (solid lines 1 kW/m2 insolation; dashed lines 0.8 kW/m2 insolation).
where Empp is the available energy during a day with MPPT control, and Ecpg is the energy production in CPG operation mode in regions of II and IV in Fig. 2. Hereby, the cut-off energy (dotted-area) during the day can be given by,
Eess =
t2 t1
PPV (t)dt +
t4 t3
PPV (t)dt
Ecpg (3)
Fig. 2. Operation regions (I, III, V – MPPT; II, IV – CPG) for a single-phase PV system during a day with the proposed control concept, where Plim it is determined by the tradeoffs among the device thermal performance, the inverter utilization factor, and the annual energy yield.
two-stage single-phase PV system with the proposed control concept is shown in Fig. 1, which indicates that the hybrid con- trol strategy is implemented in the control of the boost stage. As shown in Fig. 1, depending on the instantaneous available power of the PV panels, the actual output power of the PV panels can
be expressed as
PPV (t), MPPT, when PPV (t) < Plim it
P (t) = (1)
which can be adopted as a trade-off factor to determine the
power limit Plimit as discussed later.
According to Figs. 1 and 2, and (1), the operation principle of the proposed hybrid MPPT-CPG control can be described as follows. When PPV (t)Pl imit, the system enters into CPG operation mode and the MPPT control is deactivated. The PV output power is regulated by a proportional controller (kcpg ) to maintain the output power constant (i.e., Po (t) = Plimit). When PPV (t) < Plimit, the system maximizes the output power with an MPPT control, and thus the CPG control is disabled.
The CPG control can be achieved by diverting the operating point from the maximum power point. As an example illus- trated in Fig. 3, if the available power of the PV panel exceeds the power limit when the solar irradiance is increased from
0.8 kW/m2 to 1 kW/m2 , the operating point of the PV panels
either moves to L or H rather than M. Accordingly, the operating point of the PV inverter is changed. There are three
o P
limit
, CPG, when PPV
(t) P
alternatives of the control variables for CPG control: v , i ,
or
or
l imit pv pv
Ppv . The first two control options can be acheved on a ba-
where Po (t) is the output power of the PV panels (i.e., input power of the power conversion stage), PPV (t) is the available maximum power of the PV panels, and Plimit is selected by taking intoaccount the tradeoffs amongthe thermal performance (lifetime) of power devices, the PV inverter utilization factor, and the annual energy yield.
As the available PV power is weather-dependent, the op- eration modes will alter accordingly with the solar irradiance and ambient temperature. Fig. 2 exemplifies different operation regions for a single-phase PV system during a day with the pro- posed control strategy. Then, according to (1), it can be obtained
sis of the existing power point tracking algorithms, e.g. Perturb and Observe (P&O) and incremental conductance methods [12], [13]. The third one is applied in this study by using Plimit as a power reference since it is relatively simple. It is worthwhile investigating the dynamic performance of different implemen- tation methods, which is beyond the scope of this letter and is considered as a further in-depth study.
The implementation of the hybrid control concept requires an appropriate power limit (Plimit) as shown in Fig. 1. To quanti- tatively find the optimal power limit, a PV inverter utilization factor (in hours) is defined as
that
Em pp =
t
PPV
(t)dt
= E Pn
(4)
Ecpg =
t0 t2
Plimit
t1
dt +
t4
Plimit dt
t3
(2) in which E is the annual energy production and Pn is the rated maximum power of the PV inverter. Equation (4) indicates how
many equivalent hours the system operates at the maximum
Fig. 4. Energy reduction due to the limitation of maximum feed-in power from a 3-kW grid-connected PV system using yearly real-fielddata.
TABLE I
PARAMETERS OF THE 3 KW TWO-STAGE SINGLE-PHASE PV SYSTEM
Parameter Value
PV panels rated power Pn = 2925 W
Boost converterinductor L = 5 mH
DC-link capacitor C dc = 2200 F
LCL-filter L1 = 2 mH, L2 = 3 mH, Cf = 4.7 F
Switching frequencies for boost stage and inverter
fb o o s t = f i n v = 10 kHz
Grid nominal voltage (RMS) Vg = 230 V
Grid nominal frequency 0 = 2 × 50 rad/s
rated power through a year. With the proposed MPPT-CPG con- trol, i.e. Pn = Plimit, a larger value of implies a relative lower cost of the PV inverters, as the ratings arereduced.
Additionally, the selection of Plimit should be compromised with the energy loss defined in (3). Fig. 4 presents the depen- dency of energy reduction on Plimit for a 3-kW PV system operating under a specific yearly mission profile. The energy loss is increased with the reduced value of Plimit. For example, a 20% reduction of the maximum feed-in power will result in a 6.23% reduction of the annual energy production. Correspond-
ingly, the PV inverter utilization factor is increased by 17% (i.e.,
Fig. 5. Performance of the PV system with the hybrid control: (a) output power and solar irradiance profile and (b) PV power versus PV voltage.
presented in Fig. 5. It can be noted that, when the maximum power exceeds the limitation (80% of nominal power according to Fig. 4), the CPG control is activated and thus constant output power is achieved. Once the PV power goes below the limit, the system resumes MPPT operation mode. Then, the maximum power from the PV strings are fed into the grid.
Fig. 6(a) shows the output power and corresponding energy yield of the PV system with and without CPG control under two real-field daily profiles (sampling rate: 30 min per sample). According to (2) and (3), the energy yield is 94.9% and 88.8%
10.0623
1). Further trade-off design factors, such as the im-
of the MPPT controlled system in a clear day and a cloudy
0.8
pact on the lifetime of PV inverters and the cost-of-energy of
the PV systems, are not covered in this letter.
-
OPERATION EXAMPLES
To illustrate the effectiveness of the proposed hybrid con- trol concept, simulations of a 3-kW two-stage single-phase PV system are carried out referring to Fig. 1. The system consists of three PV strings (15 panels of each). The parameters of the system are listed in Table I. The P&O MPPT control method is adopted in the MPPT operation mode [12]. A proportional resonant controller is used in the current control loop for power quality consideration [1]. In both operation modes, the dc-link voltage is regulated within 400±5 V to ensure the power in- jection, and the proposed power control is adopted according to Figs. 1 and 3.
Firstly, the single-phase PV system with the proposed hy- brid MPPT-CPG control is tested under ramp-changes of solar irradiance at a constant ambient temperature. The results are
day, respectively. It demonstrates the effectiveness of the hybrid control on limiting and smoothing the feed-in power and on improving the utilization factor of the PV inverter. It should be noted that further efforts could be devoted to improving the dynamics during the transitions from MPPT mode to CPG mode or vice versa.
In addition, Fig. 6(b) presents the thermal loading of a power switching device in the PV inverter under those two daily mis- sion profiles. It demonstrates that the hybrid control concept can contribute to a redistribution of the thermal loading on the switching devices, affecting the overall reliability, which is highly dependent on the mean temperature and temperature variations [4]. As further explored in Fig. 7, the resultant yearly junction temperature profiles of the switching devices under the MPPT control and the hybrid MPPT-CPG control are compared. It can be noted that the peak junction temperature is reduced by 6 C with the hybrid MPPT-CPG control scheme. Moreover, the temperature variations are also lowered in the hybrid control mode. The reduction of thermal stresses imply the reliability
Fig. 6. Results of a single-phase PV system with and without the hybrid control using real-field daily profiles (top: A clear day; bottom: a cloudy day): (a) PV output power and energy yield and (b) thermal loading of an Insulated-Gate Bipolar Transistor (IGBT) of the PV inverter.
model parameters, Tj , Tjm , and tON are the amplitude, mean value, and the period of the temperature cycles of the power devices, Ea = 0.066 eV is the activation energy, and kB = 8.617 105 e×V/K is the Boltzmann constant. A quanti- tative calculation of Nf can be enabled by a rain-flow counting algorithm [4], [14]. In this letter, for comparison, a normalized lifetime (LF) is defined as
LF = 1
LC
. (6)
Fig. 7. Thermal loading of the power devices of the PV inverter with and without the proposed control concept (80 % of peak feed-in power) under a yearly real-field mission profile.
improvement and maintenance cost reduction, contributing to the reduction of cost-of-energy.
In order to further explore the potential reliability improve- ment by the proposed control concept, a lifetime model [10]
(number of cycles to failure, Nf ) is adopted a.s
E
with LC being the Life Consumption LC of the power devices in the MPPT-CPG operation mode normalized to that in MPPT mode. The LC can be calculated according to the Miners rule
[14] and the lifetime model shown in (5). The benefit of lifetime extension by the proposed control concept has been demon- strated in Fig. 8, where the energy yield and reliability improve- ment under different power limitations Plimit are presented. The power limit Plimit can be selected according to Fig. 8 when con- sidering the energy yield and lifetime extension.In addition, since the thermal loading of the power devices
in the MPPT-CPG mode is reduced, the efficiency of the PV inverter might be improved. Fig. 9 shows the experimental re-
= ( ) (
T +
) exp a
sults of the efficiency of a single-phase PV inverter nd the case
Nf
with
A Tj ar)1 j 0 f (tON
C + (tON )
kB Tjm
fd (5) temperature of the power devices under different power levels. It can be observed in Fig. 9 that the efficiency of the PV inverter varies with the dc input power (i.e. the PV output power) and also the case temperature of the power devices. When the input
C +1
C +1
f(tON ) = power is kept constant (e.g., 2.4 kW of Point A and Point B), the case temperature is increased from 51 C to 52 C, while
where A = 3.44 × 1014 , = 4.92, 0 = 1.94, 1 =
9.01 × 103 , = 1.21, fd = 0.62, and C = 1.43 are the
the efficiency is also increased from 93.20 % to 94.19 %. This can also contribute to an increase of the PV inverter utilization
REFERENCES
Fig. 8. Energy yield of the PV inverter and normalized lifetime of the power device in the PV inverter with the proposed control concept.
Fig. 9. Experimental results (inverter conversion efficiency and case temper- ature of the power devices) of a grid-connected single-phase PV inverter under different input power levels.
factor according to (4), and thus a reduction of the cost of energy can be achieved.
-
CONCLUSION
A hybrid MPPTCPG control concept is proposed for grid- connected PV inverters by considering the long-term mission profiles and the system level power management requirements. The proposed control strategy enables to increase the utilization factor of PV inverters and to reduce the temperature variations on power devices. Moreover, it is beneficial to system level power management by smoothing and limiting the PV inverter out- put power to some extent. This benefit is especially important to increase the PV installations with the existing grid infras- tructure under a high PV penetration degree in the future. The aforementioned advantages are compromised with the energy loss due to the proposed control, allowing the optimal selection of the power control limit depending on specific mission pro- files. In the study case of a single- phase PV inverter, the power limit is selected as 80% of the maximum feed-in power of the PV panels, which is corresponding to a 6.23% energy yield reduction under a specific yearly mission profile. The PV in- verter utilization is increased by 17% and the lifetime of the power devices is extended to 5.62 times of that in MPPT control mode.
-
F. Blaabjerg, R. Teodorescu, M. Liserre, and A. V. Timbus, Overview of control and grid synchronization for distributed power generation systems, IEEE Trans. Ind. Electron., vol. 53, no. 5, pp. 13981409, Oct. 2006.
-
D. Maxwell. (2013, Nov. 13). Parts of northern Irelands electricity grid overloaded. BBC News. [Online]. Available: http://www.bbc.co.uk/
-
A. Ahmed, L. Ran, S. Moon, and J.-H. Park, A fast PV power track- ing control algorithm with reduced power mode, IEEE Trans. Energy Convers., vol. 28, no. 3, pp. 565575, Sep. 2013.
-
H. Wang, M. Liserre, F. Blaabjerg, P. de Place Rimmen, J.B. Jacobsen, T. Kvisgaard, and J. Landkildehus, Transitioning to physics-of-failure as a reliability driver in power electronics, IEEE J. Emerging Sel. Topics Power Electron., vol. 2, no. 1, pp. 97114, Mar. 2014.
-
D. Rosenwirth and K. Strubbe. (2013, Mar.). Integrating variable renew- ables as Germany expands its grid. RenewableEnergyWorld.com. [Online]. Available: http://renewableenergyworld.com/
-
H. Gaztanaga, J. Landaluze, I. Etxeberria-Otadui, A. Padros, I. Berazaluce, and D. Cuesta, Enhanced experimental PV plant grid-integration with a MW Lithium-Ion energy storage system, in Proc. Energy Convers. Congr. Expo., 1519, Sep. 2013, pp. 1324 1329.
-
Fraunhofer ISE. (2014, May 28). Recent facts about photovoltaics in Germany. Fraunhofer Inst. Sol. Energy Syst., Freiburg, Germany, Tech. Rep., [Online]. Available: http://www.pv- fakten.de/
-
R. Tonkoski, L. A. C. Lopes, and T. H. M. EL-Fouly, Coordinated ac- tive power curtailment of grid connected PV inverters for overvoltage prevention, IEEE Trans. Sustain. Energy, vol. 2, no. 2, pp. 139147, Apr. 2011.
-
Y. Ueda, K. Kurokawa, T. Tanabe, K. Kitamura, and H. Sugihara, Analysis results of output power loss due to the grid voltage rise in grid-connected photovoltaic power generation systems, IEEE Trans. Ind. Electron., vol. 55, no. 7, pp. 27442751, Jul. 2008.
-
U. Scheuermann, Pragmatic bond wire model, Presentation at ECPE Workshop Lifetime Modeling Simulation, Jul. 34, 2013.
-
Y. Yang, H. Wang, and F. Blaabjerg, Reduced junction temperature con- trol during low-voltage ride-through for single- phase photovoltaic invert- ers, IET Power Electron., pp. 110, in press, 2014. DOI: 10.1049/iet- pel.2013.0734.
-
D. Sera, L. Mathe, T. Kerekes, S. V. Spataru, and R. Teodorescu, On the perturb-and-observe and incremental conductance MPPT methods for PV systems, IEEE J. Photovoltaics, vol. 3, no. 3, pp. 10701078, Jul.2013.
-
L. Nousiainen, J. Puukko, A. Maki, T. Messo, J. Huusari, J. Jokipii, J. Viinamaki, D.T. Lobera, S. Valkealahti, and T. Suntio, Photovoltaic generator as an input source for power electronic converters, IEEE Trans. Power Electron., vol. 28, no. 6, pp. 30283038, Jun. 2013.
-
H. Huang and P. Mawby, A lifetime estimation technique for voltage source inverters, IEEE Trans. Power Electron., vol. 28, no. 8, pp. 4113 4119, Aug. 2013.