Development Of A Temperature Monitoring And Control System Using Temperature Sensor

DOI : 10.17577/IJERTV1IS8223

Download Full-Text PDF Cite this Publication

Text Only Version

Development Of A Temperature Monitoring And Control System Using Temperature Sensor

Sayan Samanta 1, Subhodip Maulik 2 and Srismrita Basu 3

Sayan Samanta, corresponding author

Subhodip Maulik,Assistant professor Camellia Institute of technology, Madhyamgram,

Srismrita Basu , Assistant professor Greater Kolkata College Of Engg & Mgmt, Baruipur,

  1. Abstract: This project aims at controlling the temperature of an aluminum plate which is being heated by a 50 watt heating element. For controlling the temperature of the metal plate the current through the heating element is controlled. The thermal energy produced by the heater is directly proportional to the square of the current passing through the heater coil. Hence, by controlling the current through the heater coil

    ,the heat produced by the heater is controlled. The target is to control the temperature of the plate between room temperature and 100 °C with the optimal control range being from 44°C to 63°C. Following this significance of temperature control in processes, a temperature sensor and control system using the AD590 IC as the temperature sensor is designed.

    Keywords Temperature sensors, AD-590 sensor, Heater, Thyristor, Signal conditioning unit, PID controller.

  2. Proposed design:

    fig(1) Block diagram

    The main scheme of the project is to control the temperature of the plate via a feedback control loop. The system consists of a plate heated by an electrical heater, temperature sensor IC AD590, a signal conditioning unit, a controller and a final control element.

    The function of each of the following blocks is briefly explained below:

    Heater:

    The heater used was a 50 watt heating element. This was used to heat an aluminum plate whose temperature was in turn measured and controlled.

    Temperature sensor:

    The function of the temperature sensor is to produce an electrical signal whose magnitude would be proportional to the temperature of the plate. Here, the temperature sensor used is an IC temperature sensor named AD590. This device produces an electrical current directly proportional to the absolute temperature. The output of this sensor is fed to the signal conditioning unit.

    fig(2) AD590 PIN out

    fig(2.1) Absolute maximum ratings for AD-590

    Signal Conditioning Unit:

    The signal is so named because it takes its input from the sensor and produces an electrical signal that is usable by the controller circuitry. This is necessary since the electrical output of the sensor is of very low magnitude. It is necessary to amplify these signals before they can be processed by the controller. Typically, the output of sensors is in the order of mill volts. The signal conditioning unit performs this necessary amplification with the help of small signal amplifiers. Mostly op amps and instrumentation amplifiers are used for this purpose.

    Controller:

    The controller performs the function of controlling the process output by changing the manipulated variable. In this case the manipulated variable is the current through the heating element which cannot be directly controlled by the controller. Hence. It controls the manipulated variable with the help of the final control element. There are two inputs to the controller namely, the measured value and the set point. The measured value is the sensor output processed by the signal conditioning unit. The set point input is used to set the temperature at which we are to control the plate temperature. A controller can be of discontinuous type or continuous type. Here a continuous type controller was used. The controller was used both in the PD mode and in the PID mode and the results were observed. When used in the PD mode, the process featured a constant steady state offset error. The PID mode featured a near to set point process output with a maximum variation of 0.75°C. The controller circuit was primarily constructed and simulated using NI Multisim 11 simulation software. After successful simulation it was interfaced to the process namely, the signal conditioning unit and the final control element through a DAS card. The same circuit was constructed in the form of the original controller.

  3. Experimental Results:

    Here, Vsp = set point voltage, Vscu = voltage input from SCU i.e. the measured value

    fig(3) Practical circuit for controller

    Final Control Element:

    The final control element does the job of receiving the control signal (1V to 5V) from the controller and accordingly changing the manipulated variable. This is necessary since the controller alone does not have the ability to handle such high AC loads. The final control element used here is a thyristor drive. The response of the thyristor drive was observed to be linear in the range of 3V to 5V of the control voltage. The thyristor drive output voltage is directly proportional to the input control voltage. Hence, by varying the control voltage to the thyristor drive, the voltage applied to the heater can be varied.

    1. Temp vs Sensor output voltage

      TEMP(°C)

      SENSOR OUTPUT (mV)

      25

      298

      30

      303

      35

      308

      40

      313

      45

      318

      50

      323

      55

      328

      60

      333

      65

      338

      70

      343

      75

      348

      80

      353

      85

      358

      90

      363

      95

      368

      100

      373

      fig(4) Temperature vs sensor output voltage.

    2. Temp vs Signal conditioning unit O/P

      1. Temp vs DPM output

        TEMP(°C)

        SCU Output (V)

        25

        1.007

        30

        1.248

        35

        1.53

        40

        1.795

        45

        2.06

        50

        2.325

        55

        2.59

        60

        2.855

        65

        3.12

        70

        3.385

        75

        3.65

        80

        3.915

        85

        4.18

        90

        4.445

        95

        4.71

        100

        4.975

        TEMP(°C)

        SENSOR

        OUTPUT(mV)

        DPM DISPLAY

        VALUE

        25

        298

        25.1

        30

        303

        30.2

        35

        308

        35.0

        40

        313

        40.0

        45

        318

        45.0

        50

        323

        50.0

        55

        328

        55.0

        60

        333

        60.1

        65

        338

        65.0

        70

        343

        70.0

        75

        348

        75.0

        80

        353

        80.0

        85

        358

        85.0

        90

        363

        90.0

        95

        368

        95.0

        100

        373

        100.0

        fig(5) Temperature vs signal conditioning unit output voltage

        RED=set point voltage & GREEN=controller

        response

        fig(6)Controller response in PD mode.

        RED=set point voltage & GREEN=controller response

        fig(7)Controller response in PID mode

      2. Performance characteristics of PID controller

        RED=set point voltage, GREEN=PID controller response, BLUE=measured value

        fig(8)PID controller output vs step change from 2.5v to 2.75v

      3. Performance characteristics of final control element:

    Table for Input volt vs output volt(increasing)

    Input DC voltage (V)

    Output AC voltage (V)

    1.0

    0.16

    1.3

    0.16

    1.7

    1.9

    2.0

    2.5

    2.3

    3.4

    2.5

    17.8

    2.8

    24

    3.0

    30

    3.1

    32.25

    3.2

    44

    3.3

    145

    3.6

    159

    4.0

    172

    4.3

    179

    4.6

    185

    4.8

    189

    5.0

    192

    Table for Input volt vs output volt(decreasing)

    Input DC voltage (V)

    Output AC voltage (V)

    5.0

    190

    4.6

    186.4

    4.3

    180

    4.0

    172

    3.8

    166.5

    3.5

    154

    3.2

    143.6

    2.9

    136.9

    2.8

    135.7

    2.7

    23

    2.6

    20

    2.2

    10

    2.0

    8

    1.8

    5.2

    1.5

    0.16

    1.3

    0.16

    1.0

    0.16

    fig(9)input control voltage versus output voltage of final control element(increasing)

    fig(9)input control voltage versus output voltage of final control element(decreasing)

  4. Reference:

  1. Bela G. Liptak, Process Measurement and Analysis, 4th edition, CRC Press, 1995.

  2. Robert L. Boylestad and Louis Nashelsky,

    Electronic Devices and Circuit Theory, 9th edition, Pearson Education Prentice Hall, 2008.

  3. Surekha Bhanot, Process Control Principles and Applications, 1st edition, Oxford University Press, 2010.

  4. A. K. Sawhney, A Course in Electrical and Electronic Measurements and Instrumentation, 17th edition, Dhanpat Rai and Co., 2005.

  5. Robert F. Coughlin and Frederick F. Driscoll,

    Operational Amplifiers and Linear Integrated Circuits, 1st edition, Pearson Education Prentice Hall, 2007.

  6. AD590 datasheet, Analog Devices.

  7. OP07 datasheet, Analog Devices.

  8. PID controller, www.wikipedia.org.