Numerical Simulation of Fin and Tube Gas Cooler for Transcritical CO2 Air Conditioning System

DOI : 10.17577/IJERTV1IS10421

Download Full-Text PDF Cite this Publication

Text Only Version

Numerical Simulation of Fin and Tube Gas Cooler for Transcritical CO2 Air Conditioning System

Nilam P. Jadhav

Asst. Professor

Suhas Deshmukh

Professor

Mandar M. Lele

Professor

Abstract

This paper focuses on the development of plain fin and tube gas cooler for CO2 transcritical air conditioning system operating in subtropical conditions. The numerical simulation is carried out for identification of variation of heat transfer and pressure drop. The thermo-physical and transport properties for CO2 are taken from NIST database. The simulation study has been carried out for 0.26 kg/sec air mass flow rate and 0.006944 kg/sec refrigerant mass flow rate. The gas cooler pressure of 90 bar at 40oC dry bulb temperature has been considered. Air side and refrigerant side heat transfer coefficients are estimated and compared with available correlations developed by various researchers viz. Rich, McQuiston, Webb and Gray. Further it is observed that simulation results are having a close matching with correlations from literature.

  1. Introduction

    Global energy and environmental issues have compelled the researchers and manufactures to develop an environmental friendly and energy efficient refrigeration and air conditioning systems. There are two ways to deal with this problem; one is retrofitting of existing system for an energy efficient working fluid or development of new system. A refrigerant is ideal when is chemically stable and inert, has excellent thermal and fluid flow characteristics. It is compatible with common materials, soluble in lubricating oils, nontoxic and nonflammable, environmentally acceptable and has low cost. Since no single fluid meets all these attributes, a variety of refrigerants have been developed and used in HVAC&R systems.

    Existing chemical refrigerants; CFC, HCFCs and HFCs have disadvantages of high cost and unresolved issues of environmental impact compared with natural refrigerants. Among natural refrigerants, CO2 has low

    toxicity, non-flammability and low cost. This makes it preferred sustainable refrigerant as a permanent replacement candidate to man-made refrigerants. CO2 offers the thermo-physical and transport properties that are unique and substantially different than other conventional refrigerants. Due to low critical temperature (31oC) of CO2, whenever ambient temperature exceeds the critical temperature, the heat rejection is by single phase gascooling process. High vapour pressure and volumetric heat capacity of CO2 causes to freshly design the air conditioning system instead of retrofitting the existing system.

    This paper focuses on simulation of plain fin and tube gascooler for transcritical CO2 air conditioning system for high ambient Indian subtropical climatic conditions. This study has oriented towards the development of the plain fin and tube gascooler, which will be possible to manufacture locally at low cost.

  2. Literature review

    Lorentzen et al. [1] reintroduced natural refrigerant CO2 as substitute to chemical refrigerants since it has competitive thermodynamic and transport properties. Many researchers have reported simulation studies and findings on fin and tube gascooler for low ambient climatic conditions [5, 6, 7, 13, 17, 18, 19]. The efforts are lacking in the thermal design of plain fin and tube gascooler for transcritical CO2 air conditioning system in the open literature for subtropical conditions. Few researchers have focused on the development of microchannel gascooler since they offer highest compact ratio and capacity [8, 9, 10, 11, 12]. However manufacturing and use of micro channel gascooler requires huge investment in design, tooling, etc., which may not be cost effective. Many studies are available on prediction of heat transfer coefficient and pressure drop for micro and mini channel tubes [2, 3, 9, 13, 14, 20, 21]. Pettersen et al. [8] have notified that because of smaller tube and manifold dimensions the size of heat exchanger gets reduced as compared with

    HFC134a system and the heat exchangers give best overall efficiency.

    Yin et al. [9] developed gas cooler model by using a finite element method. The experimental results have shown that the heat transfer coefficient increased as temperature of supercritical CO2 decreased along the gas cooler flow length. The authors concluded that the performance of the gas cooler improved by using multiple slabs instead of multiple passes and proved that the three pass gascooler was the best slab design. Kim et al. [13] suggested effectiveness and NTU method for obtaining air side thermal performance for cross flow heat exchanger with both fluids unmixed. The authors observed that for increased flow depth from 16 mm to 24 mm and face velocity 0.75 m/sec, the heat transfer coefficient decreased from 100 to 65 W/m2K. For change in flow velocity from 0.75 to 3 m/sec and flow depth of 16 mm, the heat transfer coefficient enhanced was from 100 W/m2K to 130 W/m2K. They concluded that for 16 mm flow depth and 23o louver angle, the heat transfer coefficient (140 W/m2K) does not change with flow velocity.For 16 mm flow depth and 23o louver angle, the heat transfer coefficient obtained was 100 W/m2K. For 27o louver angle from 15o to 23o, the pressure drop increased from 40 Pa to 60 Pa for 16 mm flow depth.

    Yoon et al. [14] proved that for copper tube diameter of 7.73 mm, increasing mass flux from 241 kg/m2sec to 464 kg/m2sec influences the heat transfer coefficient. For calculating heat transfer coefficient, the authors have used Krasnoshchekov and Protopopov, Baskov, Petrov and Popov and Pitla correlations [23, 24, 25, 26] with RMS deviations

    29.7, 29.6, 47.9 and 38% respectively. For calculating refrigerant properties at bulk temperature, the authors have suggested Dittus-Boelters correlation with average deviation 12.7%. The authors also observed the drastic variation in specific heat near the critical region. The heat transfer coefficient has the maximum value at its pseudo critical temperature. Pettersen [15]

    decreases, while longitudinal tube pitch has no influence on the air side heat transfer coefficient. The fin efficiency is not much affected by the fin pitch or the longitudinal tube pitch but decreases largely when the transverse tube pitch increases. Ge and Cropper [5] discussed the simulated performance of the air cooled gascooler for different circuitry arrangements.

  3. Numerical simulation

    The spreadsheet has been developed to simulate the cross flow unmixed unmixed plain fin and tube gascooler. The thermo-physical and transport properties of CO2 are taken from REFPROP, refrigerant properties database developed by NIST [27]. The operating inlet and outlet conditions of the gascooler are worked out by transcritical CO2 cycle simulation considering subtropical conditions and are given in Table 1.

    Input: geometry and operating conditions L1, L2, L3,di,do, Pt, Pl, Nt,Fd, Fs,tf,PGC, mair,mref

    Estimate thermo physical properties: CO2 and air

    Calculate surface geometrical properties for air side: core volume,Ao,Amin_air,At

    Calculate surface geometrical properties for fin side: Asf, Nf, Lf, M, , Re/rt

    Evaluate: fin, o

    reported that the heat transfer coefficient increases

    with varying heat flux from 5 to 20 kW/m2 and mass flux from 190 to 570 kg/m2sec.Son and Park [16]

    Estimate: Vair, Gair, Reair, Dh, Vref, Gref,

    presented that because of maximum specific heat of

    CO2 near the pseudo critical temperature, the heat transfer coefficient increases slowly in the entrance rgion of gascooler and decreases at the exit of gas cooler. The authors concluded that the Bringer- Smiths correlation showed the best agreement for heat transfer coefficient with mean deviation of 23.6%.

    Simulation model has been developed for plain fin and tube gas cooler by Chang and Kim [7]. The authors presented that for increased fin pitch and transverse tube pitch, the air side heat transfer coefficient

    Determine: Colburn j-factor. Nusselt number

    Calculate: hair, href, U

    Evaluate: Uo, NTU,

    Figure 1.Flow chart indicating steps in the simulation

    It has been reported that three to four rows gives better compact design of gascooler than two rows geometry [19]. Hence, the counter cross flow, four row single pass staggered tube arrangement has been considered for the gascooler as shown in Figure 2. Figure 1 shows

  4. Simulations

    The heat transfer rate of air side and refrigerant side is calculated using equations 1 and 2.

    the methodology used for the simulation and Table 2

    provides the geometry of the gascooler.

    .

    a

    Qa = ma .Cp Ta

    .

    Qr = mr .Cpr Tr

    Qmax = Qa (3)

    (1)

    (2)

    For both fluids unmixed effectiveness is calculated by equation 4.

    NTU 0.22 0.78

    (4)

    = 1- exp

    Cr

    exp -Cr .NTU

    – 1

    Where,

    .

    p

    mC

    C = min

    (5)

    r .

    Figure 2.Four pass – three circuit staggered tube

    gascooler

    mCp

    max

    Overall heat transfer coefficient for the heat exchanger is obtained from equation 6.

    .

    (6)

    The geometrical size of the base case gascooler is finalized by parametric evaluation considering the

    Uo Ao = m Cp

    min

    NTU

    optimum gascooler pressure of 90 bars and 40oC dry bulb temperature to avoid an extensive loss of capacity

    The air side heat transfer coefficient is calculated

    using equation 7.

    at higher temperatures.

    1 =

    Uo Ao

    1

    hi Ai

    + w

    kw Aw

    + 1

    o ho Ao

    (7)

    Table 1.Operating conditions at gascooler

    Colburn j factor is calculated by using available

    Air inlet

    temperature [oC]

    40

    Mass flow rate of

    air [kg/sec]

    0.26

    Refrigerant inlet

    temperature [oC]

    106

    Velocity of air

    [m/sec]

    2.55

    Refrigerant outlet temperature [oC]

    42

    Mass flow rate of refrigerant

    [kg/sec]

    0.0069

    Refrigerant inlet pressure [bar]

    90

    Velocity of

    refrigerant [m/sec]

    0.9254

    correlations suggested in literature review and found that Rich correlation shows best agreement with maximum deviation of 23%, and equation 8 calculates j factor.

    R e

    j = 0.195* R

    air

    -0.35

    (8)

    Tube inner diameter

    [mm]

    4.75

    Tube material

    Cu

    Tube length [mm]

    550

    Fin material

    Al

    Transverse tube

    spacing [mm]

    25

    Fin spacing

    [mm]

    1.37

    Longitudinal tube

    spacing [mm]

    18

    Fin density

    [fpi]

    16

    Number of tube rows

    4

    Fin thickness

    [mm]

    1.27

    Table 2.Geometry of base case gascooler model

    Based on the experimental data on gas cooling of supercritical carbon dioxide, Yoon et al. [14] suggested an empirical correlation using the form of Dittus-Bolters correlation and multiplying the density ratio, shown in equation 9. The Yoon correlation has an average deviation of 1.6%, the absolute average deviation of 12.7% and the root mean square deviation of 20.2%.

    n

    N = a.R b .P c . pc

    (9)

    u e r

    Where,

    a=0.14; b=0.69; c=0.66; n=0 … for T >Tpc a=0.013; b=1.0; c=-0.05; n=1.6 for T <Tpc

    temperature 40oC, it is observed from Figure 4 that, as fin density increases from 8 fpi to 24 fpi through 33.33% change, air side minimum free flow area decreases by 5.04%, Reynolds number increase by 10.53% and j factor decreases by 0.9%. This increase in the fin density has marginally increased Nusselt number through 1.58% shown in Figure 5.

    0.0205

    0.02

    0.0195

    830m3/hr

    930 m3/hr

    1030 m3/hr

    Figure 3.Continuous circular fins

    Taylor has symmetrically divided the continuous plain fin area around the staggered tubes into hexagonal shaped section to calculate the overall air side fin surface efficiency [18]. The authors modified this method and considered circular fin sectional area to

    0.019

    jR [-]

    0.0185

    0.018

    0.0175

    8 10 12 14 16 18 20 22 24

    Fin density [fpi]

    avoid iterations involved in calculating geometry parameters of hexagonal fin surface area shown in Figure 3.

    The air side fin efficiency is calculated by equation 10.

    A

    Figure 4.Effect of fin density on j factor

    830m3/hr

    930 m3/hr

    15 1030 m3/hr

    14.5

    = 1- fin 1-

    o

    (10) 14

    A

    fin

    o

    The fin efficiency of a circular fin is calculated from equation 11.

    13.5

    Nu [-]

    13

    = tanh mrt

    fin mr

    (11)

    12.5

    12

    t

    Where, m is the standard extended surface parameter, which is defined as,

    11.5

    8 10 12 14 16 18 20 22 24

    m= 2ho

    k fin .t f

    (12)

    Fin density [fpi]

    Figure 5.Effect of fin density on Nusselt number

    The fin efficiency parameter for a circular fin, is calculated using equation 13.

    5.2 Fin thickness

    As shown in Figures 6 to 9, for 830 m3/hr air flow

    = Re

    Re

    (13)

    rate, 26.78% increase in fin thickness from 0.112 mm

    r – 1 1+0.35ln r

    to 0.142 mm, the minimum free flow area reduces by

    t

    t

    2.57% results in 2.62% increase in the Reynolds

    where, the equivalent circular fin radius, Re, is defined from equation 14

    number, 1.70% increase in Nusselt number, 5.18% increase in number of transfer units and 7.84%

    R t X

    X

    e = 1.27 2 l – 0.3

    rt rt Xt

    (14)

    increase in fin efficiency. This change in the fin

    thickness increases an effectiveness of the gascooler by 2.88% as shown in Figure 9.

    2

  5. Result and discussion

    5.1 Fin density

    Colburn j factor is the dimensionless heat transfer coefficient. For air flow rate 830 m3/hr and inlet air

    15

    830 m3/hr

    930 m3/hr

    1030 m3/hr

    0.112 0.117 0.122 0.127 0.132 0.137 0.142

    p [mm]

    0.112 0.117 0.122 0.127 0.132 0.137 0.142

    p [m]

    830 m3/hr

    930 m3/hr

    1030 m3/hr

    0.67

    0.66

    0.65

    0.64

    0.63

    0.62

    0.61

    0.6

    0.59

    0.58

    0.57

    14.5

    14

    13.5

    13

    12.5

    12

    Nu [-]

    [-]

    Figure 6.Effect of fin thickness on Nusselt number

    NTU [-]

    As shown in Figures 7 and 9, for the base case gascooler model when air flow rate increases from 930 m3/hr to 1030 m3/hr Reynolds number and Nusselt number increase by 10.75% and 6.88% respectively and fin efficiency decreases by 2.32%. The effectiveness of gas cooler decreases by 4.89% and the capacity of the gas cooler increases by 2.36% for the same change in the air flow rate.

    p> 830 m3/hr

    930 m3/hr

    1030 m3/hr

    1.05

    1

    0.95

    0.9

    0.85

    0.112 0.117

    0.122 0.127

    p [mm]

    0.132 0.137 0.142

    fin [-]

    Figure 7.Effect of fin thickness on NTU

    0.66

    0.65

    0.64

    0.63

    0.62

    0.61

    0.6

    0.59

    0.58

    0.57

    0.56

    830 m3/hr

    930 m3/hr

    1030 m3/hr

    0.112 0.117 0.122 0.127 0.132 0.137 0.142

    p [mm]

    Figure 8.Effect of fin thickness on fin efficiency

    Figure 9.Effect of fin thickness on effectiveness

      1. Transverse tube spacing

        The effect of transverse tube spacing and longitudinal tube spacing on the performance of gas cooler is also studied. It has been notified that the performance of gas cooler mainly depends upon the transverse tube spacing rather than on the longitudinal tube spacing. If the transverse tube spacing is very less, the average air velocity and the Reynolds number in the core are very high. This also causes un-necessary turbulence effect in the core of the gascooler. Air side pressure drop tends to increase in inverse proportion with the transverse tube pitch and definitely affects the performance of gas cooler.

        Nu [-]

        The effect of 66.66% increase in transverse tube spacing from 15 mm to 25 mm on the Nusselt number for varying air flow rate is represented in Figure 10.

        22

        830m3/hr

        930m3/hr

        1030m3/hr

        20

        18

        16

        14

        12

        15

        17

        19

        21

        23

        25

        Xt [mm]

        Figure 10.Effect of transverse tube spacing on Nusselt number

        An increase in transverse tube spacing at air flow rate 830 m3/hr, minimum free flow area increases by 101.67% as a result the Reynolds number reduces by 101.67%. Therefore j factor decreases by 27.82% and the mass flux decreases by 101.66%, which results in 57.57% decrease in Nusselt number as shown in Figure 10.

      2. Effect of gas cooler width

    Nu [-]

    An increase of 24.48% gascooler width from 490 mm to 610 mm for constant air flow rate 830 m3/hr, it is observed that minimum free flow area increases by 28.57% and j factor increases by 7.96%. This result in 24.48% and 15.33% drop in Reynolds and Nusselt numbers respectively as shown in Figure 11.

    16

    15.5

    15

    14.5

    14

    13.5

    13

    12.5

    12

    11.5

    11

    10.5

    10

    830m3/hr

    930m3/hr

    1030m3/hr

    0.49 0.51 0.53

    0.55

    Lt [m]

    0.57 0.59 0.61

    Figure 11.Effect of gas cooler width on Nusselt number

    This change in gascooler width has also an effect on the number of transfer units and the overall heat transfer coefficient of the gascooler. The number of transfer units increased by 17.7% for the same change in the width of the gascooler as given in Figures 12. The effectiveness of the gascooler increases by 9.83% as shown in Figure 13.

    coefficients increase by 4.89% by Rich correlation, 3.65% by McQuiston and 3.93% by Webb and Gray correlations as shown in Figure 14.

    830 m3/hr

    0.68 930 m3/hr

    1030 m3/hr

    0.66

    0.64

    0.62

    0.6

    0.58

    0.56

    0.54

    0.49 0.51 0.53 0.55 0.57 0.59 0.61

    Lt [m]

    [-]

    Figure 13.Effect of gas cooler length in effectiveness

    UA_Rich [W/K]

    UA_FCM [W/K]

    320 UA_WG [W/K] 310

    300

    UA [W/K]

    290

    280

    270

    260

    250

    240

    1.15 830 m3/hr

    930 m3/hr

    1.1 1030 m3/hr

    1.05

    1

    NTU [-]

    0.95

    0.9

    0.85

    0.8

    0.75

    0.49 0.51 0.53 0.55 0.57 0.59 0.61

    Lt [m]

    Figure 12.Effect of gas cooler length on NTU

    5.4 Effect of inlet temperature

    The effect of 53.33% increase in inlet temperature of air from 30oC to 46oC on the overall heat transfer coefficient is depicted in Figure 14 by using different air side correlations: Rich, McQuiston and Webb and Gray correlations [19]. The overall heat transfer

    30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46

    Tair [oC]

    Figure 14.Effect of inlet temperature of air on overall heat transfer coefficient

    The effect of change in inlet temperature on effectiveness for 830 m3/hr flow rate is graphically represented in Figure 15. From Figure 15 it has been notified that the effectiveness calculated by Rich correlation is 13.77% more compared with McQuiston correlation and 9.77% more compared with Webb and Gray correlation.

    0.69

    0.67

    _Rich [-]

    _FCM [-]

    _WG [-]

    0.65

    0.63

    0.61

    0.59

    0.57

    0.55

    30 32 34

    36 38 40

    Tair [oC]

    42 44 46

    [-]

    Figure 15.Effect of inlet temperature of air on effectiveness of gas cooler

  6. Conclusion

From this simulation work following conclusions can be drawn.1) For increase in fin density, Reynolds number increases by 10.53%, Nusselt number by 1.58% and heat transfer coefficient by 7.39 for 830 m3/hr air flow rate. While Colburn j factor decrease by 0.9%. For increase air flow rate, the air side minimum free flow area decreases by 5.04% and Reynolds number increases by 4.08% which results 4.18% decreases in j factor.

2) Effect of fin thickness on various factors are monitored and observed that, increased fin thickness increases Reynolds number by 2.62%, Nusselt number by 1.70% hence increases the heat transfer coefficient by 1.69%. It has been also notified that increased fin thickness reduces minimum free flow area by 2.57%, this results increase in NTU by 5.18%, overall heat transfer area by 1.73%, effectiveness by 2.88% and capacity of gas cooler by 3.29%. While the fin efficiency decrease by 2.38%.

4) As the transverse tube spacing increases, minimum free flow area decrease by 108.5%, Reynolds number by 101.68%, mass flux by 101.66%. Hence this

parameters decreases Nusselt number by 57.57% and

near the critical region, the capacity of the gas cooler increases greatly and reaches the maximum value nearly at the pseudo critical temperature.

7) Increase in gas cooler length decreases minimum free flow area by 24.37%, Colburn j factor by 8.02%, Reynolds number by 24.48%, mass flux by 48.16%, Nusselt number by 15.33% and heat transfer area by 15.30% for 830 m3/hr air flow rate. While increase gas cooler length increases NTU by 17.7%, overall heat transfer coefficient by 18%, effectiveness of gas cooler by 9.83% and capacity of gas cooler by 1.96% for 830 m3/hr air flow rate.

It has been observed that for increase in gas cooler length and air flow rate, increases Nusselt number by 6.90%, heat transfer coefficient by 6.87%, Reynolds number by 10.75% and capacity of gas cooler by 1.96%, while it decreases NTU by 8.64%, overall heat transfer coefficient by 2.27% and effectiveness of gas cooler by 5.45%.

References

  1. G. Lorentzen,The use of natural refrigerants: a complete solution to the CFC / HCFC predicament, International Journal Refrigeration, 1995, Vol. 18, No. 3, pp 190-197

  2. TorgePfafferott, Gerhard Schmitz,Modelling and transient simulation of CO2 refrigeration systems with Modelica, International Journal of Refrigeration, 2004 Vol. 27 pp 42-52

  3. Pfafferott T., Schmitz G.,Modeling and simulation of refrigeration systems with the natural refrigerant CO2, 2nd International Modelica conference, Proceedings, 2002, pp 145-1 145-9

  4. O. Garcia-Valladares,Numerical simulation of transcritical carbon dioxide (R744) flow through short tube orifices, Applied Thermal Engineering,2006, Vol. 26 pp144-151

  5. Y.T. Ge and R.T. Cropper,Simulation and performance evaluation of finned-tube CO2 gas coolers for refrigeration systems, Applied Thermal Engineering,2009, Vol. 29, No. 5-6, pp 957-965

    ,

    heat transfer coefficient by 57.76%, while j factor

  6. Varun Singh

    Vikrant Aute and

    increase by 28.28% for 830 m3/hr air flow rate.

    1. Effect of increase in inlet temperature of air is monitored and observed that the overall heat transfer coefficient increase by 4.89% calculated by Rich correlation, which shows well agreement as compared with McQuiston and Webb and Gray correlations. Also as the inlet temperature of air increases, the effectiveness of gas cooler increases by 13.77%. The capacity of the gas cooler is more calculated by Rich correlation and shows maximum value up to 6.18 kW for 31oC.

    2. As the gas cooling process progresses, the capacity of gas cooler reaches its maximum and then decreases. Since the specific heat increases drastically

    ReinhardRadermacher,Numerical approach for modeling air-to-refrigerant fin-and-tube heat exchanger with tube-to- tube heat transfer, International Journal of Refrigeration,2009,Vol. 32, Issue 7, pp 1724-1735

  7. Young-Soo Chang Min Seok Kim,Modeling and performance simulation of a gas cooler for a CO2 heat pump system, HVAC&R Research May 2007

  8. J. Pettersen, A. Hafner and G. Skaugen,Development of compact heat exchangers for CO2 air conditioning systems, International Journal of Refrigeration,1998, Vol. 21, No. 3, pp 180-193

  9. Jain Min Yin, Clark W. Bullard, Predrag S. Hrnjak,R- 744 gas cooler model development and validation, International Journal of Refrigeration,2001, Vol. 24, pp 692-701

  10. Tomoichiro Tamura, YuuichiYakumaru, FumitoshiNishiwaki,Experimental study on automotive cooling and heating air conditioning system using CO2 as a refrigerant, International Journal of Refrigeration, 2005, pp 1-6

  11. J. Steven Brown, Samuel F. Yana-Motta, Piotr A. Domanski,Comparative analysis of an automobile air conditioning systems operating with CO2 and R134a, International Journal of Refrigeration, 2002, Vol. 25, pp 19- 32

  12. XiulanHuai, Shigeru Koyama, T.S. Zhao, EtsouShinmura, Kinoshita Hidehiko, Morita Masaki,An experimental study of flow boiling characteristics of carbon dioxide in multiport mini channels, Applied Thermal Engineering, 2004,Vol. 24 pp 1443-1463

  13. Man-Hoe Kim, Clark W. Bullard,Air-side thermal hydraulic performance of multi-louvered fin aluminum heat exchangers, International Journal of Refrigeration,2002,

    Vol. 25 pp 390-400

  14. Seok Ho Yoon, Juhyokkim, Yun Wookhwang, Mm Soo Kim, Kyoungdoug Min, Yongchan Kim,Heat transfer and pressure drop characteristics during the in-tube cooling process of carbon dioxide in the supercritical region, International Journal of Refrigeration, 2003, Vol. 26 pp 857-864

  15. JosteinPettersen,Flow vaporization of CO2 in microchannel tubes, Experimental Thermal and Fluid Science, 2004, Vol. 28, pp 111-121

  16. Chang-Hyo Son, Seung-Jun Park,An experimental study on heat transfer and pressure drop characteristics of CO2 during gas cooling process in a horizontal tube,

    International Journal of Refrigeration, 2005, pp 1-8

  17. A.M. Hansen,CFD simulation of a fin and tube heat exchangers, Master of Science Thesis, Computational Chemical Engineering, 2008, Issue 6

  18. Liao,Heat transfer of supercritical carbon dioxide in mini/micro tubes, Ph.D. Thesis, Hong Kong University of Science and Technology, 2002

  19. Creed Taylor, Measurement of finned tube heat exchanger performance, A Thesis, Georgia Institute of Technology, Dec. 2004

  20. X. Fang,Modeling and analysis of gas coolers, Air Conditioning and Refrigeration Centre, University of Illinois, CR-16, 1999, Vol. 217 pp 333-3115

  21. S.K. Fisher and C.K. Rice,The Oak Ridge heat pump models: I.A. steady state computer design model for air-to- air heat pumps, Proceedings of DOE/ORNL heat pump conference, 1983

  22. GuohuaKuang,Heat transfer and mechanical analysis of supercritical gas cooling process of CO2 in microchannels, Dissertation Report, University of Maryland,2006

  23. Krasnoshchekov E.A., Kuraeva I.V., Protopopov V.S.,Local heat transfer of carbon dioxide at supercritical pressure under cooling conditions, TelofizVys. Temp., 1969, 7(5) pp 922-930

  24. Baskov V.L., Kuraeva I.V., Protopopov V.S.,Heat transfer with the turbulent flow of a liquid at supercritical pressure in tubes under cooling conditions, High Temp., 1977, Vol. 15(1) pp 81-86

  25. Pitla S.S. Groll E.A., Ramadhyani S.,New correlation for the heat transfer coefficient during in-tube cooling of turbulent supercritical carbon dioxide, International Journal of Refrigeration, 2002, Vol. 25, pp 259-67

[26 ]Petrov N.E., Popov V.N.,Heat transfer and resistance of carbon dioxide being cooled in the supercritical region,

Thermal Engineering, 1985, Vol. 32(3) pp 131-134

[27] John Willey and Sons,NIST12 National Institute of Standards and Technology, distributed with the Handbook of Heat Transfer