Optimization Of Air Inlet Angle For Increase The Effectiveness Of Induced Draught Cross Flow Cooling Tower
Prof.Ravindra kirar1, Dilip vaghela2, Hitesh Patel3
1HOD Mechanical Department (PCST,BHOPAL)
2 M.Tech Student of PCST,Bhopal
3Assistant professor HGCE, Vahelal
Abstract
A cooling tower is an enclosed device for the evaporative cooling of water by contact with the air. Cooling tower is a heat rejection device. Common applications include cooling the circulating water used in oil refineries, petrochemical and other chemical plants, thermal power stations and HVAC systems for cooling buildings. The efficiency and the effectiveness of cooling tower is depend on number of parameter like inlet air angle, inlet and outlet temperature of air and water, fill materials, fan speed etc. In current work the air inlet angle is optimize by selecting three different inlet angles. For this CFD analysis of induced draught cross flow cooling tower is done in ANSYS workbench.
-
INTRODUCTION
cooling tower is a heat rejection device that transfers waste heat from a process to the atmosphere though the cooling of the recalculated water flow. The type of heat rejection is commonly termed "evaporative cooling". Cooling Towers are used in facilities where process cooling is required in order to dissipate the heat that is created as a result of the process application, including power generation, oil refining, steel mills, pulp and paper plants, chemical processing and more. Cooling Towers are also a necessary component of the HVAC systems used to heat and cool large commercial buildings or server rooms.
There are number of factor affecting the performance of cooling tower like inlet temperature of water and air,outlet temperature of water and air,porosity in fins, speed of fan, mass flow rate of air and water. Out of this parameter inlet air angle is very effective parameter on the performance of the cooling tower. So we optimize this angle by CFD analysis of cooling tower.
ten node tetrahedral elements. The reason for selecting this element is that is gives the good meshing on curvature parts Here the ANSYS is automatically select the element. In step 3 various domains is define. Here there are three domain are define. Domain 1 is for water. The domain 2 is porous domain and domain 3 is air domain. After define the domain interface between domain is define between each domain to transfer the effect of each other. In boundary condition the inlet water
temperature 380 C , inlet air temperature 20 , Volume of circulating water circulated in cooling tower 30 m3/hr.
Fig 1,fig 2 and fig 3 show the cooling tower model in solid work for 30,15 and 45 degree air inlet angle respectively
.
Fig 1: 3D Model of 30 Degree Air Angle
-
CFD ANALYSIS
Here ANSYS workbench is used for CFD analysis of cooling tower.. For CFD analysis following step are perform. In step 1 cooling tower modal make in solidworks are converted in to STEP file and this step file are imported in ANSYS. In step 2 the meshing of this cooling tower model is done. In meshing CFD mesh type is selected and fine meshing is done by using
Fig 2: 3D Model of 15 Degree Air Angle
Fig 3: 3D Model of 45 Degree Air Angle
Fig 4 shows the meshing of cooling tower. The meshing detail of cooling tower is shown in Table 1.
Fig 4: Meshing detail of cooling tower
Table 1: Meshing detail of cooling tower
DOMAIN |
NODES |
ELEMENT |
DOMAIN 1 |
85825 |
415025 |
After meshing the boundary condition is shown in fig 5 and fig 6 and fig 7.
Fig 5: Inlet for Air Domain
Fig:6 Define inlet for Water Domain
Fig 7: Outlet for Water Domain
Post processor result of ANSYS is shown in Fig 8,Fig 9,Fig 10 below.
Fig :8 Temperature Contour for 30 Degree Air Angle
Fig :9 Temperature Contour for 15 Degree Air Angle
Fig :10 Temperature Contour for 45 Degree Air Angle
Table 2 shows the result of three different air inlet angle.
Sr No. |
Air inlet Angle |
Temperature |
1 |
15 |
302.5 |
2 |
30 |
304.67 |
3 |
45 |
306.3 |
Temperature viruses air inlet angle graph is shown in fig 11.
FIG 11: TEMPERATURE VIRUSES AIR INLET ANGLE
CONCLUSION
-
It has been shown that CFD can be used for performance evaluation of cooling towers in terms of cooling efficiency and effectiveness.
-
Water outlet temperature of cooling tower decreases as the air inlet angle decreases. Hence the cooling efficiency and effectiveness of cooling tower increases. Out of selected three air inlet angles, angle of 150 leads to maximum efficiency and effectiveness for selected cooling tower.
-
On the other side, as the air inlet angle increases the water outlet temperature also increases and cooling efficiency and effectiveness of cooling tower decreases.
REFERENCES
[1]. Numerical simulation of a wet cooling tower J. van der Merwel C.G. du Toit2 (First received October 2001; Final version May 2002) [2]. CFD Prediction of Forced Draft Counter-Flow Cooling Tower Performance Dr. Jalal M. Jalil*, Dr.Talib K.Murtadha** & Dr. Qasim S. Mehdi*** Received on: 16/12/2009 Accepted on: 16/2/2010 [3]. PERFORMANCE ANALYSIS OF MECHANICALDRAFT COOLING TOWER Si Y. Lee Savannah River National Laboratory si.lee@srnl.doe.gov 803- 725-8462 Alfred J. Garrett Savannah River National Laboratory alfred.garrett@srnl.doe.gov803-725-4870 James S. BollingerSavannah River National Laboratory james02.bollinger@srnl.doe.gov 803- 725-1417 Larry D. Koffman Savannah River National Laboratory larry.koffman@srnl.doe.gov 803-725-1038
[4]. Numerical Simulation of the Performance Characteristics of the Hybrid Closed Circuit Cooling Tower M.M.A. Sarker1, E. Kim2, C.G. Moon2, J. I. Yoon2 1Department of Mathematics Bangladesh University of Engineering and Technology Dhaka- 1000, Bangladesh masarker@math.buet.ac.bd 2Department of Refrigeration and Air-conditioningEngineering Pukyong National University Namgu, Pusan 608-739, Korea Received:15.05.2007 Revised: 01.12.2007 Published online: 06.03.2008
[5]. Heat and mass transfer in an indirect contact cooling tower: cfd simulation and experiment Jorge Facao and Armando C. Oliveira Department of Mechanical Engineering, Faculty of Engineering, University of Porto, Portugal [6]. Performance evaluation of wet-cooling tower fills with computational fluid dynamics by yngvi gudmundsson