Assessing the Torsional Response of Elevated Water Tank with Amended Bracings

DOI : 10.17577/IJERTV10IS060183

Download Full-Text PDF Cite this Publication

Text Only Version

Assessing the Torsional Response of Elevated Water Tank with Amended Bracings

Sujina Sahib S

M tech Student [Structural Engineering] Dept of Civil Engineering

Younus College of Engineering and Technology Kollam, India

AbstractElevated tanks are important structures in storing vital products such as petroleum as well as water. Elevated storage tanks are commonly used to secure constant water supply from longer distance under the effect of gravitational force. They are constructed in such a way that it's greater portion of their weight is concentrated at an elevation. Torsional failure of elevated water tanks in past earthquakes has highlighted the importance of this problem.

Modelling and analysis of elevated water tank should be done using ETAB Software. Seismic Response Spectrum, Equivalent Static Analysis and modal analysis were conducted. Different staging configurations consist of Staging with different altered longitudinal bracings are provided. Through this study an effective approach to reduce torsional effect must be formulated. Tank responses including Local Torsion, Global Torsion will also be calculated.

Keywords Elevated tanks, bracings, Local Torsion, Global Torsion , ETAB Software

  1. INTRODUCTION

    Water tanks are one of the most important lifeline structures. In most of the cities and rural areas, water tanks forms an integral part of water supply scheme. Types are underground water tanks, ground supporting water tanks and elevated storage water tanks. Elevated water tanks are mostly used .The elevated water tanks are also known as over head supply reservoir (OHSR) , elevated supply reservoir (ESR) etc. To secure constant water supply from longer distance under the effect of gravitational force, the elevated water tanks are necessary.

    They have low ductility and energy absorbing capacity as compared to the conventional buildings. They get heavily damaged during earthquake due to the fluid-structure interactions. Presence of heavy roof top masses like water tanks increases the seismic forces in the members of a building. They constructed in such a way that a greater portion of their weight is concentrated at an elevation. So seismic safety of liquid storage tanks is of considerable importance. Damage to these structures during strong ground motions may lead to fire or other hazardous events. Reinforced concrete water tanks can be made economical, monolithic and watertight by their design and construction. Different types of bracings configurations can be provided to the staging for adequate resistance of seismic forces.

  2. OBJECTIVE

    To find out the torsional behavior of the elevated water tank by altering the longitudinal geometry of the braces.

  3. METHODOLOGY

  4. MODELLING

    TABLE I. DESIGN DATA OF WATERTANK

    (Patel et al, 2017)

    SL.NO

    COMPONENT

    VALUES

    1

    Top slab

    150 mm

    2

    Bottom slab

    200 mm

    3

    230mmx230mm

    150 mm

    4

    Height of staging

    15 m

    5

    Height of container

    5 m

    6

    Dimension of tank

    6 x 6 m

    7

    Zone factor

    0.36 (V)

    8

    Importance factor

    1.5 for water tank

    9

    Reduction Factor

    5 (SMRF)

    10

    Type of soil

    Medium soil

    11

    Bracing type

    X bracing

    12

    Beam

    230mm x 300mm

    13

    Column

    300mm x 300mm

    14

    Bracing

    230mm x 230mm

    Type

    Value

    Source

    Basic wind speed (Vb)

    50 m/s

    Clause 5.2

    Probability factor or risk coefficient (k1)

    1.06

    Clause 5.2.1

    Terrain, height and structure size factor (k2)

    1.07

    Clause 5.2.2

    Topography factor (k3)

    1.0

    Clause 5.2.3

    Structure class

    B

    Clause 5.3.2.2

    Type

    Value

    Source

    Basic wind speed (Vb)

    50 m/s

    Clause 5.2

    Probability factor or risk coefficient (k1)

    1.06

    Clause 5.2.1

    Terrain, height and structure size factor (k2)

    1.07

    Clause 5.2.2

    Topography factor (k3)

    1.0

    Clause 5.2.3

    Structure class

    B

    Clause 5.3.2.2

    TABLE II. WIND LOADS (IS 875 PART 3)

    Fig.1. Plan, Elevation and 3d view of water tank

    A. Modification of Bracing Geometry

    In the present study modelling of 8 different types of altered longitudinal geometry of the braces. Only depth of the bracings are varying .Width remains the same. Length of bracings provided is 4.24m . Dimensions of large cross section provided is 230x230mm . Dimensions of small cross section provided is 230×76.67mm (That is 1/3 rd of the depth).

    In the present study one normal bracing with 230×230 mm uniform cross section and 8 altered longitudinal geometrical bracings are modelled and analysed. From the 8 models ,All the models are symmetrical bracings .From this, 4 models (B1 to B4) are designed in such a way that it is divided equally into three portions for altering the depth and in case of B5to B8 bracings they divided in to 3 portions and the middle portion again divides equally,so total of 4 portions for altering the depth.

    B1

    B5

    B6

    B7

    B8

    Fig. 2. Altered longitudinal geometry of the braces

  5. ANALYSIS

    1. Equivalent Static Analysis

      The equivalent static lateral force method is a simplified technique to substitute the effect of dynamic loading of an expected earthquake by a static force distributed laterally on a structure for design purposes.

      As per IS 1893:2002, Torsion should be considered when ratio of maximum story drift to average storey drift of the structure is more than 1.2

      .

      TABLE III. DRIFT RATIO

      Model Id

      Max drift/Avg Drift

      NB

      1.332

      B1

      1.314

      B2

      1.324

      B3

      1.308

      B4

      1.319

      B5

      1.319

      B6

      1.308

      B7

      1.327

      B8

      1.308

      1.32

      B2

      B3

      0.56

      1.78

      0.98 0.97

      1.77

      0.33

      1.79

      B1 B2 B3 B4 B5 B6 B7 B8

      B4 Fig.3.Percentage Reduction In Torsion w.r.t Normal Bracing

      For all models the maximum story drift to average story drift is greater than 1.2. Model with norma bracing have maximum torsion. Model B3, B6 and B8 have the maximum reduction in torsion.

    2. Modal Analysis

      Modal analysis is used to determine the number of modes and corresponding mode shapes. Loads are applied as acceleration in X and Y direction. 12 number of modes are

      The global torsion get reduced maximum for bracing B8. The torsion is less for bracings with least cross sectional area near the supports. The torsion is highest for bracing with largest cross sectional area near the support

      1. Local Torsion

        Local torsion refers to the torsion in each bracings.

        76.07

        taken for analysis (At mode 12, mass participation ratio is approximately 100%). The effective mass participation factor represents the percentage of the system mass that participates in a particular mode. It provides a measure of the energy contained within each resonant mode.

        Type : Eigen Vector Modal Analysis

        No. of modes = 17 at 99% mass participation

        56.31

        31.90

        66.31

        55.48

        40.36

        63.81

        29.05

        32 32 32

        25.6

        17.6 18.4

        12.8

        9.6

        B1 B2 B3 B4 B5 B6 B7 B8

        Fig.6.Percentage Reduction In Local Torsion w.r.t Normal Bracing

        The local torsion get reduced maximum for bracing B8. Model with normal bracing have maximum torsion .The torsion is less for bracings with least cross sectional area near the supports. The torsion is highest for bracing with

        B1 B2 B3 B4 B5 B6 B7 B8

        Fig 4. Percentage Reduction in torsion w.r.t Normal Bracing

        The time period at torsional mode get reduced maximum for bracing B3, B6 and B8. Model with normal bracing have maximum torsion. The torsion is less for bracings

        largest cross sectional area near the support.

      2. Brace Reactions

        TORSION AXIAL FORCE

        76.07

        with least cross sectional area near the supports. The torsion is highest for bracing with largest cross sectional area near the support.

    3. Response Spectrum Analysis

    Response-spectrum analysis (RSA) is a linear-dynamic statistical analysis method which measures the contribution from each natural mode of vibration to indicate the likely

    56.31

    17.44

    31.90

    66.31

    19.51

    55.48

    40.36

    63.81

    20.78

    29.05

    21.00

    maximum seismic response of an essential elastic structure. Seismic Zone Factor = 0.36

    9.03

    11.40 13.43

    7.54

    Soil Type = II Damping Ratio = 50%

    1. Global Torsion

      B1 B2 B3 B4 B5 B6 B7 B8

      Fig.7.Percentage Decrease Of Axial force with respect To Normal Brace

      TORSION SHEAR FORCE

      71.17

      55.07

      77.77

      70.62

      60.64

      76.12

      53.18

      84.21

      56.31

      47.69

      66.31

      55.48

      35.90

      40.36

      63.81

      76.07

      39.49

      31.90

      22.56

      26.15

      31.79

      30.26

      30.26

      29.05

      B1 B2 B3 B4 B5 B6 B7 B8

      Fig.5.Percentage Reduction In Global Torsion w.r.t Normal Bracing

      Global torsion refers to the torsion of the entire building.

      5.64

      B1 B2 B3 B4 B5 B6 B7 B8

      Fig.8.Percentage Decrease Of Shear force with respect To Normal Brace

      TORSION BENDING MOMENT

      76.07

      1. P.L.N. Saroja and V. S. Rao, Comparative Study of Analysis of Elevated Water Tank Due To Earth Quake from Different Zones of Earth Quake, International Journal of Constructive Research in Civil Engineering, Volume 2, January 2016

      2. A. N. Asati, Dr. M. S. Kadu, Seismic Investigation Of RCC

        62.00

        56.31

        31.90

        66.31

        60.00

        55.48

        40.36

        63.81

        60.00

        29.05

        46.00

        Elevated Water Tank For Different Types Of Staging Patterns, International Journal of Engineering Trends and Technology (IJETT) Volume 14, August 2014

      3. G. P. Deshmukh, A. S. Patekhede, analysis of elevated water storage structure using different staging system, Indian Journal of Science and Technology, Volume 9, August 2016

      4. P.I.N. Saroja,Vanka. Srinivasa Rao, Comparative Study Of

        20.00 22.00

        15.00

        2.00

        B1 B2 B3 B4 B5 B6 B7 B8

        Fig.9.Percentage Decrease Of Bending moment with respect To Normal Brace

        Brace Axial force and shear force are proportional to brace torsion. For braces with less cross sectional area near the supports, bending moment decreased by 15 to 46%.

  6. CONCLUSION

Staging with same cross-sectional area throughout the bracing have maximum torsion. The torsion is less for bracings with least cross-sectional area near the supports. Brace Axial force and shear force are proportional to brace torsion. For braces with less cross-sectional area near the supports, bending moment decreased by 15 to 46%. By reducing the cross-sectional area near the support, reinforcement and cost of the bracing can be reduced

REFERENCES

  1. C. N. Patel, S. N. Vaghela, H. S. Patel, Sloshing Response Of Elevated Water Tank Over Alternate Column Proportionality International Journal of Advanced Engineering Technology,

    Volume 3 Issue IV Oct.-Dec.-2012

  2. V. Varur, S. B. Vankudre, P. Prabhavati ., Optimization of Water Tank The International Journal Of Science & Technology,

    Volume 2 Issue 7 July-2014

  3. N. J. Singh, I. Mohammad, Design Analysis & Comparison Of Intze Type Water Tank For Different Wind Speed And Seismic Zones As Per Indian Codes, International Journal of Research in Engineering and Technology, Volume: 04 Issue: 09 September- 2015

  4. S. Wankhede, P. J. Salunke, N. G. Gore, Cost Optimization of Elevated Circular Water Storage Tank, The International Journal Of Engineering And Science, Volume 4, Issue 2015

  5. H. Mohammed, Optimization of water storage tank, International Journal of Engineering and Technical Research,

    Volume 3, Issue 4 April 2011

  6. F. Asari, M. G. Vanza, Structural Control System For Elevated Water Tank, International Journal of Advanced Engineering Research and Studies, Vol. 1 Issue 3 April-June-2012

  7. A. N. Asati, M. S. Kadu, S. R. Asati, Seismic Analysis And Optimization Of RC Elevated Water Tank Using Various Staging Patterns International Journal Of Engineering Research And Application, Volume 6 Issue 7(Part-1) July 2016

  8. S. A. Barakat, S. Altoubat, Optimization of Elevated Water Tank The International Journal Of Science & Technology Volume 2 Issue 7 July 2009

  9. S. Siddiqui, B. K. Singh and P. Thakur, Performance based Seismic Analysis on RCC Framed Elevated Circular Tanks with Flat and Domical Bases, Indian Journal of Science and Technology, Volume 9, August 2016

  10. Swathi C. Naik and M.S. Bhandiwad, Seismic Analysis and Optimization of a Rectangular Elevated Water Tank, International Journal of Man Machine Interface, Volume 4, July 2016

Elevated Water Tank Due To Earth Quake From Different Zones International Journal Of Construction Research In Civil Engineering, Volume 2, Issue 1,2016, Issn2454-8693

    1. Latesh T. Patil, Rajashekar Tailkoti, Comparision Of Seismic Behavior Of Rectangular Elevated Water Tank International Journal For Scientific Research And Development, Volume 3,Issue 05,2015, Issn (Online):2321-0613