Application of FFT for Detection of High Impedance Faults in Power System Network
Nabamita Banerjee Roy(1st Author) Associate Professor, Electrical Engineering, Narula Institute of Technology
Kolkata, India
Kushal Kumar(2nd Author)
Student, M. Tech, 2nd Year, Electrical Engineering, Narula Institute of Technology
Kolkata, India
Abstract Detection of High Impedance Faults mainly in distribution systems is a troublesome and challenging task that has caught researchers attraction over past years. The random behavior of HIF current, as well as its low magnitude, causes difficulties in the detection of faults by conventional fault detection methods. Conventional distance relays, overcurrent relays, and ground fault relays cannot be used for HIF detection due to its sensitivity and selectivity issue owing to the low value of fault current. There are several Signal processing techniques available for HIF detection such as Fourier transforms, wavelet transforms but this paper mainly focuses on application of Fast Fourier Transform (FFT) for feature extraction from the voltage signals of a power system network. The pattern of the extracted features has been observed thoroughly and the results indicate that all the types of faults can be correctly identified irrespective of the magnitude of fault resistance. In this paper, different types of High Impedance Faults (HIFs) have been simulated at different locations of the transmission line. All the simulations have been done in MATLAB.
Keywords Fast Fourier Transform (FFT), Feature extraction, Fault resistance, High Impedance Fault (HIF)
-
INTRODUCTION
Fast detection of faults allows the relays to isolate the faulty part from the rest of the power system in order to protect the assets of the faulty part and to continue power supply to the healthy part. In addition, the accurate classification of faults provides necessary information regarding fault location that expedites the required repair works. Consequently, fast and reliable fault detection and classification have become an essential operational requirement of modern electricity grids. The electrical power system is very large, complex and spread over a large geographical area. The electrical power system consists of a generator, transformer, transmission lines and load. A fault in a circuit is the disturbance or failure, which interfere the normal system operation. Fault usually occurs in a power system due to insulation failure, flashover, physical damage such as wire blowing together in the wind, an animal coming in contact with the wire. Fault usually causes the flow of excessive current, abnormal voltages, induce overvoltage on neighboring equipment and cause hazards to human, animals, etc. Fault analysis is generally needed to select the size of circuit breaker fuse and characteristics, setting of the relay. Fuse, circuit breaker, relays, lighting power protection device are some of the faults limiting devices. This study proposes the application of fuzzy assessment tree (FAT)-based short- time modified Hilbert transform (STMHT) as a new multiclass detection and classification technique, for a
distributed generation (DG)-based microgrid. The time varying non-stationary power signal samples extracted near the target DG are initially de-noised by passing through the morphological median filter and then processed through the proposed STMHT technique for disturbance detection. Further based on the overlapping in the target attribute values, an FAT has been incorporated, which significantly classifies the different multiclass disturbances on a standard IEC microgrid model simulated in MATLAB/Simulink environment with highest precision in accuracy [1]. Smart grid (SG) containing clean distributed generation (DG) has gained intensive research for reliable digital protection against fault conditions. The main objective of this study is to develop and validate a fast and efficient fault detection and classification algorithm taking into account the dynamic behaviour of DG units. The proposed algorithm does not require additional measurements as it based only on the synchronized measured three-phase currents through the communication facilities available in SG. The advanced communication technologies in SG are currently utilized for efficient and real-time data transfer from the protective relays to the monitoring and protection center. The transferred data are processed for fault diagnosing before taking the necessary trip actions. In the proposed algorithm, the statistical cross- alienation coefficients are calculated for the measured current signals at sending and receiving ends of each feeder. Fault detection and classification process will be achieved taking into account the changes in the synchronized and discretized waveform of current signals within a movable window of (1/4 cycle). The proposed algorithm is tested on real system to detect and classify the different fault condition. The results indicated that the proposed technique is fast and reliable for SG digital protection schemes [2]. Signal processing techniques have provided an alternative approach of fault diagnosis in overhead transmission lines. These techniques are fast, accurate and convenient. There are multiple signal processing tools are available like Fast Fourier Transform (FFT), Wavelet Transform (WT) and S-Transform. Extensive research work has been done and published in many
literatures as given in [3]-[7]. The present work involves detection of type of fault condition using Fast Fourier Transform (FFT) based on feature extraction. The rest of the paper is organized as follows. A brief overview of FFT is discussed in section II. The simulation of the power system and the different fault conditions have been described in section III. The method of feature extraction using FFT has been discussed in section IV. Results and discussions have
been given in section V. The conclusion and future scope of work have been explained in section VI.
-
OVERVIEW OF FAST FOURIER TRANSFORM The Fast Fourier Transform does not refer to a new or
different type of Fourier transform. It refers to a very efficient algorithm for computing the DFT. The time taken to evaluate a DFT on a computer depends principally on the number of multiplications involved. DFT needs principally on the number of multiplications involved. DFT needs N2 multiplications. FFT only needs Nlog2(N). The central insight which leads to this algorithm is the realization that a discrete Fourier transform of a sequence of N realization that a discrete Fourier transform of a sequence of N points can be written in terms of two discrete Fourier transforms of length N/2Thus if N is a power of two it is possible to recursively apply. Thus, if N is a power of two, it is possible to recursively apply this decomposition until we are left with discrete Fourier transforms of single points. The FFT of a signal x[n] is given by is given by Equation (1):
x (1)
-
SIMULATION OF POWER SYSTEM NETWORK
-
Simulation of power system network
The single line diagram of the power system network considered in this study has been simulated in MATLAB and shown in Fig .1. The specifications of the system shown in Fig.1. have been provided in TABLE I.
Fig. 1. Single Line diagram of 400 kV, 50 Hz, 3-phase power system
network
The parameters of the system are given in TABLE I. The voltage signals have been simulated for a time period of 0.04 sec.
System Components
Specifications
Generator
Impedace = (0.2+j4.49) , X/R ratio = 22.45.
Transmission Line
Length: 300 Km, R1 = 0.02336/km,
R2 = 0.02336/km, R0 = 0.38848/km,
L1 = 0.95106mH/km, L2 =
0.95106mH/km,
L0 = 3.25083mH/km, C1 =
12.37nF/km, C2 = 12.37nF/km, C0 = 8.45 nF/km
Balanced Load
Load Impedance = (720+j11) , p.f.= 0.9, MVA rating = 200
System Components
Specifications
Generator
Impedance = (0.2+j4.49) , X/R ratio = 22.45.
Transmission Line
Length: 300 Km, R1 = 0.02336/km,
R2 = 0.02336/km, R0 = 0.38848/km,
L1 = 0.95106mH/km, L2 =
0.95106mH/km,
L0 = 3.25083mH/km, C1 =
12.37nF/km, C2 = 12.37nF/km, C0 = 8.45 nF/km
Balanced Load
Load Impedance = (720+j11) , p.f.= 0.9, MVA rating = 200
TABLE I. SYSTEM PARAMETERS
-
Simulation of power system faults
The following ten types of faults have been simulated in steps of 10 Km from sending end (B1) of power system network as shown in Fig.1. The fault resistance has been considered to be 500 ohms.
-
Single line to Ground -AG, BG, CG (e.g., AG- Phase A to Ground)
-
Double line faults – AB, BC, CA
-
Double line to ground fault- ABG, BCG, CAG
-
Three phase short circuit fault -ABC
-
All the faults have been simulated in steps of 10 km on the transmission line from the sending end(B1) of the power system. As the objective is to simulate high impedance faults, fault resistance is taken to be 500 Ohm.
(a)
(b)
Fig. 2. Plots of Three phase voltage waveform during (a) AB type (b) ABG type of fault occurring at 100 Km from B1 in the power system network with Fault resistance=500ohms
-
-
APPLICATION OF FFT IN ANALYSIS OF HIGH IMPEDANCE FAULTS
A. Method of feature extraction
FFT has been implemented on the voltage waveform of each phase simulated at the sending end of the network during a fault condition the output of the FFT is a complex matrix. The absolute value of the FFT matrix is obtained which is referred to as the frequency spectrum of the voltage waveform. The frequency spectrum of voltage during ABG kind of fault shown in Fig. 3.
Fig. 3. Frequency spectrum of the voltage signal of phase A during ABG type of fault occurring at 100 km from the sending end of the power system with fault resistance = 500 ohms
The maximum value of every spectrum is noted as an important feature for classification of fault in the present study. The process is repeated for all the types of faults at different location of the transmission line. The plots of the features of four types of fault conditions are shown in Fig. 4. to Fig. 5.
(a)
(b)
Fig. 4. Plot of magnitude of features obtained from FFT with respect to fault location in case of (a) AG fault (b) AB Fault occurring at 100 km from B1 in the power system network with fault resistance = 500 ohms
(a)
(b)
Fig. 5. Plot of magnitude of features obtained from FFT with respect to fault location in case of (a) ABG fault (b) ABC Fault occurring at 100 km from B1 in the power system network with fault resistance = 500 ohms
-
DISCUSSIONS
The following observations have been made from the profile of features shown in Fig.4. to Fig 5.
TABLE II. COMPARISON OF THE MAGNITUDES OF FEATURES OF THREE PHASES DURING DIFFERENT TYPES OF FAULT CONDITIONS WITH THOSE
Nature of fault
Magnitude of feature in comparison to the feature of the voltage signal during no fault condition
Phase A
Phase B
Phase C
AG
Lowest
Higher than normal value
Higher than normal value
BG
Higher than normal value
Lowest
Higher than normal value
CG
Higher than normal value
Higher than normal value
Lowest
AB
Lowest
Lowest
Higher than normal value
BC
Higher than normal value
Lowest
Lowest
CA
Lowest
Higher than normal value
Lowest
ABG
Lower than normal value
Lower than normal value
Higher than normal value
BCG
Higher than normal value
Lower than normal value
Lower than normal value
CAG
Lower than normal value
Higher than normal value
Lower than normal value
ABC
Lower than normal value
Lower than normal value
Lower than normal value
Nature of fault
Magnitude of feature in comparison to the feature of the voltage signal during no fault condition
Phase A
Phase B
Phase C
AG
Lowest
Higher than normal value
Higher than normal value
BG
Higher than normal value
Lowest
Higher than normal value
CG
Higher than normal value
Higher than normal value
Lowest
AB
Lowest
Lowest
Higher than normal value
BC
Higher than normal value
Lowest
Lowest
CA
Lowest
Higher than normal value
Lowest
ABG
Lower than normal value
Lower than normal value
Higher than normal value
BCG
Higher than normal value
Lower than normal value
Lower than normal value
CAG
Lower than normal value
Higher than normal value
Lower than normal value
ABC
Lower than normal value
Lower than normal value
Lower than normal value
OF PHASES DURING NORMAL CONDITIONS WITHOUT NOISE
-
CONCLUSION
In the present work, different types of High Impedance Faults have been simulated with fault resistance of 500 ohm at different locations of the transmission line. Suitable features have been selected from the voltage signals by using FFT under no fault and different fault conditions. The voltage signals of the three phases at a single terminal of the power system network have been considered for feature extraction. FFT works quite fast as a signal processing tool and is independent of the number of the samples of a signal. The features have been thoroughly studied and it has been observed that the fault conditions can be accurately identified at every location.
In the future scope of work, the signal features that have been obtained would be used to train a suitable classifier involving neural network or support vector machine so that fault can be notified automatically under different conditions. The effect of noise on the voltage signals also requires to be studied. The study can be further extended by considering higher values of fault resistances and applying other signal processing tools like wavelet transform, for obtaining signal features.
REFERENCES
-
Mohamed M.A. Mahfouz; Mohamed A.H. EI-Sayed. Smart grid fault detection and classification with multi-distributed generation based on current signals approach, Issue 16,08 December 2016, p.4040-4047.
-
Voltage Based Transmission Line Protection Algorithm Using Signal Processing Techniques, IEEE; 2015 23rd Signal Processing and Communication Applications Conference (SIU).
-
Kunjin Chen; Caowei Huang; Jinliang He. Fault detection, classification and location for transmission lines and distribution systems, High Volt,2016, Iss.1, pp. 25-33.
-
State-of-the-art on the protection of FACTS compensated high-voltage transmission lines, IET; High Volt,2018, Iss.1, pp. 21-30.
-
Power System Fault Analysis Using Signal Processing Technique, IJIREEICE; Issue 8, August 2018.
-
Waveform asymmetry of instantaneous current signal based symmetrical fault detection during power swing, Electric Power Systems Research Volume 155, February 2018, Pages 340-349.
Tatiana Chakraborty; Rajesh Kumar Patnaik; Pradipta Kishor Das. Advanced signal processing techniques for multiclass disturbance detection and classification in microgrids, Issue 4, July 2017, p. 504- 515.
AUTHOR
Dr. Nabamita Banerjee Roy is presently Associate Professor in the Electrical Engineering Department of Narula Institute of Technology, Kolkata, India. She has obtained her graduation in Electrical Engineering from B.E. College, Shibpur, Howrah, West Bengal (presently IIEST Shibpur) in 2002. She has obtained both M.E.E and PhD from Jadavpur university, Kolkata in 2004 and 2017 respectively. She has a rich and diverse academic career as a faculty in Electrical Engineering Degree level and as an administrator (acting principal) at the diploma engineering level, since 2004. She has also served as HOD, Electrical Engineering Department at Narula Institute of Technology. She has supervised many B.Tech and M.Tech projects. She has published papers in National/International conferences and journals along with a Book Chapter in Springer. Her areas of research include signal processing, power system faults, neural network, soft computation, and high voltage engineering.
Kushal Kumar is presently final year student of M. Tech in Power Systems at Narula Institute of Technology. He has completed his M. Tech project under the supervision of Dr. Nabamita Banerjee Roy. He is enthusiastic to pursue further research work in the domain of signal processing, power system faults, neural network and soft computation.