A Comparitive Study on Different Control Algorithms of Distribution Static Compensator for Power Quality Improvement

DOI : 10.17577/IJERTCONV4IS15045

Download Full-Text PDF Cite this Publication

Text Only Version

A Comparitive Study on Different Control Algorithms of Distribution Static Compensator for Power Quality Improvement

Agarwal, Vaibhav Department Of Eletrical Engineering Graphic Era Hill University,Dehradun

Abstract- DSTATCOM (Distribution STATic COMpensator) is used for reactive power compensation, harmonics elimination, zero voltage regulation, power factor correction, neutral current compensation and unbalance caused by various loads in the distribution system. This paper presents a comparative study of the performance of different control algorithms for the control of DSTATCOM which are named as Character of Triangle Function control algorithm(CTF), Icosine based Isolated Topology with Unipolar Switching control algorithm and Adaptive Theory Based Improved Linear Sinusoidal Tracer control algorithm(ILST). These algorithms are used for extraction of load fundamental active and reactive power components of currents which are used for estimation of reference source currents. These schemes are simulated under the MATLAB environment using SIMULINK and PSB toolboxes. Simulation and experimental results represents the performance of these schemes for the control of DSTATCOM.

Keywords- Character of Triangle Function(CTF), Icosine, Adaptive Theory based Improved Linear Sinusoidal Tracer (ILST).

  1. INTRODUCTION

    In the present scenario of AC transmission network, the mitigation of power quality problems is the major challenge due to increase of power electronic devices [1]. Static power converters such as rectifiers, large number of low-power electronic-based appliances, induction heating, switch mode power supplies, adjustable speed drives, electric traction, cyclo-converters etc. are nonlinear loads that generate considerable distortions in the ac mains current and causing power quality problems [2, 3]. A control algorithm should have good detection accuracy, wide range of adjustment of internal parameters, stability performance, and fast dynamic response. The performance of DSTATCOM depends largely on the right and accurate real-time detection of harmonics and reactive currents etc. [4-8]. Sawant and Chandorkar [6] have described

    multifunction active filter using instantaneous p-q-r theory. One of the new application of active filter is described by Crosier and Wang [7] where it is applied for grid connected electric vehicle charging station. Bueno et al. [8] have described application of active filter for railway supply system. DSTATCOM (Distribution Static Compensator) is also used for power quality improvement in pico-hydro based power generation [9], isolated wind power generation system [10] etc. Singh [11] has described different configurations of DSTATCOM such as three leg, four leg and characteristics of nonlinear loads. Active filters needs to detect the total distortion current outside the fundamental active source component of currents. A widely used method is the detection algorithm based on the theory of instantaneous reactive power [12]. Because it is easy to calculate and has good robustness and self- learning ability, adaptive harmonic detection algorithm has been paid wide attention in recent years [13, 14]. Based on the adaptive noise cancelling method some adaptive detection techniques for harmonic compensation are introduced for active power filter application [15, 16]. Rocher et. al [17] have discussed adaptive filters with fixed-point arithmetic which improves the computation quality. Karuppanan and Mahapatra [18] have discussed Proportional Integral (PI) or Fuzzy Logic Controller (FLC) to extract the required reference current from the distorted load currents. Masand et. al [19] have discussed phase shift control, indirect decoupled current control algorithm for DSTATCOM application. In recent years, the adaptive linear neural network (ADALINE) have been widely used in so many research fields, such as signal detection, noise canceling, and harmonic compensation [20, 21]. An active shunt compensator can be treated as a variable conductance for different order of harmonics corresponding to voltage harmonics distortion such that this technology is also useful for suppression of harmonics resonance in the distribution system [22]. Various configurations and

    topologies of DSTATCOM are used for reduction of distortions with acceptable level of performance according to the IEEE-519 standard with an optimal use of dc bus of a voltage source converter (VSC) used as DSTATCOM and in cost-effective manner [23]-[25]. Effective use of DSTATCOM is directly related to the design of power circuit components such as dc-bus capacitor, interfacing inductors, and VSC, control algorithm used for the estimation of reference source currents with increased speed and less calculation, switching scheme for gating pulses, and stability issues of a designed control algorithm [26][28].

    This paper presents a comparative study of different control algorithms for the control of DSTATCOM. The comparison is on the basis of signal conditioning required dynamic performances under varying linear and non-linear load in PFC and ZVR mode, total harmonic distortion and its multi functionality. A dynamic model of DSTATCOM has been studied using various control algorithms in MATLAB/SIMULINK environment to observe their performance and comparison. Simulation results demonstrate the effectiveness of these three control algorithms of DSTATCOM for compensation of reactive power and unbalanced loading.

  2. SYSTEM CONGURATION

    A VSC-based DSTATCOM is shown in Fig. 1. It is connected to a three-phase AC mains feeding three-phase linear/nonlinear loads with grid source impendence For reducing ripple in compensating currents, interfacing inductors are used at an AC side of the VSC. A zig-zag/ three single-phase transformer is used for neutral current compensation. A three-phase series combination of capacitor ( , , ) and a resistor ( , , ) represent the passive ripple filter, which is connected at point of common coupling (PCC) for filtering the high frequency switching noise of the VSC. Generally, the same value of series-connected capacitor and resistance as a ripple filter is used in all the three phases. The DSTATCOM currents are injected as required compensating currents to cancel the reactive power components and harmonics of the load currents so that loading due to reactive power component/harmonics is reduced on the distribution system. The rating of the insulated gate bipolar transistor (IGBT) switches of the

    (0.8 lagging), the comApeCnMsaEtoEr-d2a0t1a6aCreongfievreenncienPAropcpeeenddinixgs

    A. The rating of the VSC for the reactive power compensation/harmonics elimination is found to be 35 kVA (approximate 15% higher than the reactive power from rated value). The designed value of different auxiliary components of DSTATCOM such as interfacing ac inductors, dc-bus voltage, and value of dc-bus capacitor are also given in Appendix A.

    Fig1. Schematic diagram of VSC based DSTATCOM

  3. CONTROL ALGORITHMS

    1. CTF Control Algorithm [33].

      The main aim of this algorithm is to get the fundamental active and reactive power component. Fig 2 shows a block diagram of a CTF based control algorithm based on CTF time domain for estimating of reference source currents.

      The load fundamental active ) and reactive can be estimated by considering the phase voltage ( of AC mains at PCC distortion free sinusoidal wave as,

      (1)

      Where the peak value of phase voltage.

      The polluted load current ) is the mixture of fundamental load current is the mixture of the fundamental load current and the harmonic current

      . t can be written as,

      (2)

      VSC is based on the voltage and current rating for the required compensation. For a considered load of 50 kVA

      Fig2 .Generation Of reference source currents using CTF based control algorithm[33]

      Where are the RMS value of order harmonics current and phase angle of the order harmonic, is the dc component presence in the load which is very small in case of the symmetrical loads and

      Where Multiply by {2(sint)} in eq. (8) and according to character of triangle function is as,

      +

      represents frequency in radian per second.Eqn(2) can be

      (9)

      expressed as,

      =

      (3)

      (4) Where is the fundamental value of the RMS load current and its phase angle is .

      The fundamental load current can be expressed as ,

      (5)

      From eqn. (5),the load current can be expressed as,

      (6) Where are the load fundamental active current ,reactive current harmonics current and DC component presence in due to load respectively.

      Maximum value of active current

      Eqn. (9) shows is the mixture of DC and AC components which is seprated by low pass filter. Following relations from above eqn. are:-

      } (10) Similarly

      }

      Basic equations for the estimation of different control variables of control algorithms are discussed below

      For the estimation of in phase and quadrature unit templates of AC mains the in phase voltage unit templates ( ) are estimated from respective phase voltages ( , and divided by amplitude of the terminal voltage ( ) at PCC as [29].

      ( )

      ( )= (7)

      (11)

      Maximum value of the reactive current ( )=

      Unit template in phase with phase voltages , and

      are estimated as

      From eqn. (6-7) and (3),

      (12)

      Similarly, the quadrature unit templates ( , and

      are given as:

      (8)

      ( );

      ( ) (13)

      ( )

      phase b and phase cACaMmEpElit-ud20e1o6fCloonafderreenaccetiPvreocceuerdreinngts

      component of are also estimated.

      The average of amplitudes of fundamental active and reactive power components of load currents of the three phase loads are estimated using the amplitude of the load

      active and reactive power component of each phase and its

      Major components in the distorted load currents are fundamental active power, reactive power, harmonics components, and the dc components. Fundamental active

      average value is calculated for the extraction of three phase reference source current as

      power, reactive power and harmonics component of load currents are the primary components in the polluted distorted current loads.

      In this control algorithm phase a load, fundamental active

      power component are subtracted from original load

      ( )

      ( )

      (14)

      (15)

      currents and reactive and harmonic current are estimated. After taking constant factor r which is the % of harmonic and reactive current are added with polluted load current ( ).Added value is multiplied with inphase voltage unit template( ).

      After suppressing the harmonic an other components using low pass filter this component is again multiplied with a factor of 2 in closed loop control system .Thus phase a load fundamental active component ( ) is extracted from original load current using above procedure. After extraction of load fundamental active power component of current, its root mean square value is estimated and converted to peak value using factor k=1.414 as a gain.

      An amplitude of phase a load active power component of current is considered as .Similaraly phase b and phase

      c amplitude of load active component of current

      are also estimated.

      For the extraction of load reactive current component

      ,harmonic and active currents are estimated after subtracting fundamental reactive current component from the polluted load currents .After taking factor r which is the % of harmonic and active current are added with polluted current and it is multiplied with quadrature phase unit template .After suppressing the harmonics and other components using low pass filter ,this component is again multiplied with a factor of 2 in closed loop control system. Thus phase a load current reactive component is extracted from original load current

      using above procedure.

      After extraction of load reactive power current component

      ,its root mean square value is estimated and converted to peak value using k=1.414 gain. An amplitude of phase

      a load reactive power current component is .Similarly

      Reference dc-bus voltage and sensed dc-bus voltage

      of a VSC are compared and error in dc-bus voltage at the kth sampling instant is expressed as:

      (16) This dc-bus voltage error is fed to a proportional integral (PI) regulator whose output is required for maintaining dc-bus voltage of the DSTATCOM. Its output at the kth sampling instant

      is given as:-

      } (17) where and are the proportional and integral gain constants of the dc bus PI controller. and

      are the dc-bus voltage errors at kth and (k 1)th instants

      and and are the amplitudes of the active

      power component of the fundamental reference current at kth and (k1)th instants.

      The amplitude of active power current components of the reference source current is calculated by an addition of output of dc-bus PI controller and an average magnitude of the load active power component of currents

      as:

      (18)

      Similarly, AC bus voltage PI controller is used to regulate the PCC terminal voltage. The output signal of AC bus voltage PI controller is considered as . The amplitude of the reference source current is calculated by subtracting the output of voltage PI controller ( ) and average load reactive current ( ) as

      (19)

      Three-phase reference source active and reactive power components of currents are estimated using an amplitude of three phase (a, b, and c) load active and reactive power

      current components, PCC voltages in-phase, and quadrature voltage unit templates as:

      (20)

      (21) Reference source currents ( and ) are estimated by

      where AarCeMpEhEas-e20a1n6gCleosnfoefrenncthe Phroacrmeeodninicgs current in three phase load currents with their phase volatges. , , are amplitude of nth harmonic current in these phases.

      In this control approach,the amplitude of active power component of current ( ) of phase a is extracted from filtered value of distorted load current ( ) at the zero crossing of the in-phase unit template ( ) of three phase PCC voltages.

      the addition of reference active and reactive power

      components of currents as:

      (22)

      The sensed source currents ( ) and these reference source currents ( ) are compared

      for the respective phases and each phase current error is amplified using PI current regulators and their outputs are compared with a carrier signal of 10 kHz to generate the gating signals for IGBT switches of VSC used as DSTATCOM.

    2. Icosine Algorithm based Isolated Topology with Unipolar Switching [34]

      In this control algorithm a designed a new isolated topology based on zig-zag/ three single-phase transformers is used in DSTATCOM to select optimum dc voltage for proper utilization of solid state devices. An advantage of a zigzag transformer is to mitigate the zero sequence currents and triplen harmonics in its primary windings. Thus, it helps in the reduction of the devices rating of VSC connected in the secondary windings. In this control algorithm we used the sixleg VSC. The six-leg VSC of the proposed DSTATCOM operated with six gating signals has an advantage of doubling the PWM voltage frequency compared to devices switching frequency with unipoar switching as compared to bipolar switching which is used in three-leg VSC for a given switching frequency. Moreover, the dc bus voltage of VSC is also reduced as compared to three-leg VSC topology.

      The load currents ( , , ), voltages at the PCC (point of common coupling) ( , , ) and dc bus voltage ( ) of VSC are sensed as feedback control

      signals. Distorted load currents can be expressed as-

      Fig 3. Schematic diagram of DSTATCOM with zig zag transformer and six leg VSC[34].

      A zero crossing detector and a sample and hold circuit are used to extract the (amplitude of filtered load current at zero crossing of corresponding in-phase unit template). Similarly, other two phases amplitude of active power component of current and are also extracted. In the case of balanced system, the amplitude of active component of load currents can be expressed as,

      ( ) (26)

      where are the amplitude of the load active power component of currents.

      For self supporting dc bus of VSC, the error in dc bus

      voltage of VSC ) of DSTATCOM at nth sampling instant is as,

      (27)

      (23)

      (24)

      where ) is the reference dc voltage and is the

      (25)

      sensed dc bus voltage of the VSC.

      The output of the proportional integral (PI) controller

      Reference AC-bus volAtaCgeM E Ean-d20s1e6nsCeodnAfeCre-nbcuesPvroolctaeegdein gs

      which is used for regulating dc bus voltage of the VSC at the nth sampling instant can be expressed as,

      } (28) where is considered as part of active power component of reference source current. and are the proportional and integral gain constants of the dc bus PI voltage controller. Un-sampled value of ) is

      of a VSC are compared and error in AC-bus voltage at the nth sampling instant is expressed as:

      (37)

      This AC-bus voltage error is fed to a proportional integral (PI) regulator whose output is required for maintaining dc-bus voltage of the DSTATCOM. Its output at the nth sampling instant is given as:-

      represented as . The amplitude of active power component ( ) of reference source currents can be expressed as: (29)

      The PCC phase voltages ( ) are considered sinusoidal and their amplitude is estimated as:

      ( )

      (30)

      The unit vectors in phase with , and are derived as-

      (31)

      In-phase components of reference source currents are estimated as:

      ;

      ; (32)

      The unit vectors ( , ) in quadrature with three phase PCC voltages ( ) may be derived using a quadrature transformation of the in-phase unit vectors( ) as [30]:

      ( ) ( ), (33)

      = ( )+( ), (34)

      fig 4.Estimation of reference source current using Icos algorithm[34]

      ( )+( ) (35)

      The amplitude of reactive power component of current ( ) of phase a filtered load current ( ) is extracted at the zero crossing of the unit template quadrature-phase of the PCC voltage ( ). A zero crossing detector and a sample and hold circuit has been used to extract the (amplitude of filtered load current at zero crossing of corresponding quadrature – phase unit template). Similarly, the amplitude of reactive power component of phase b ( ) and phase c ( ) are also estimated. The amplitude of reactive power component of load currents can be expressed as:

      } (38) where and are the proportional and integral gain constants of the AC bus PI controller. and

      are the AC-bus voltage errors at nth and (n 1)th instants

      and and are the amplitudes of the

      reactive power component of the fundamental reference current at nth and (n1)th instants. is the part of

      amplitude of reactive power component of the reference source current at nth instant. is represented as in

      steady state.

      The amplitude of reactive power current components of the

      ( ) (36)

      reference source current is calculated by an addition of output of AC-bus PI controller and an average

      ACMEE – 2016 Conference Proceedings

      magnitude of the load reactive power component of currents as: (39) The quadrature or reactive power components of reference source current are estimated as:

      , (40)

      current and reference current both are tracing each other without any change even at unbalance loads.

      Three-phase voltages at the PCC are sensed and their amplitude is calculated using PCC phase voltages ( , and

      , (41)

      ( )

      (46)

      (42)

      Unit template inphase with phase voltages , and

      are estimated as

      Total Reference source currents ( and ) are

      (47)

      estimated by the addition of reference active (in phase) and

      reactive(quadrature) power components of currents as:

      (43)

      Similarly, the quadrature unit templates ( , and

      ;

      ;

      are given as:

      (44)

      ( ) ( )

      ;

      (45)

      ( )

      (48)

      .

    3. Adaptive ILST Control Algorithm[36]

    An area of adaptive control provides an automatic adjustment of the controller gains and parameters in real time, in order to achieve a desired level of performance. It provides an automatic tuning procedure in a closed loop for the controller parameters. Characteristics of this control algorithms are the ability to extract necessary information from real online data in order to tune the controller, and also used for grid synchronization.

    In this control approach, error detection accuracy and dynamic response both are related to each other. An error in the linear sinusoid tracer algorithm is affected by the high-order harmonics. Thus, this algorithm is not able to detect harmonics current accurately. For removal of this limitation, a low-pass filter (LPF) is used and this modification is named as an adaptive theory-based improved linear sinusoid tracer (ILST) where source

    Major components in the distorted load currents are fundamental active power, reactive power, harmonics components, and dc components. An adaptive theory-based ILST [54] with selectable frequency and bandwidth is used to estimate the phase a load fundamental current as shown in the block diagram of Fig. 6(b).

    In this control algorithm, phase a fundamental load current is subtracted from the load current to estimate the current error signal. The filtered value of a current error signal with the combination of band-pass filter () is added with the output signal, which is multiplied by the power frequency signal (). After integration of this signal, phase a fundamental load current is estimated. Similar procedure is adapted for phase b and phase c to extract to fundamental components of load currents. The amplitudes of three-phase fundamental load active power current components ( , and ) are extracted at the zero crossing of the unit template in – phase of PCC voltages.An output of zero crossing detector ( ) works as a trigger pulse of signal and hold logic (SCH_1 ) and fundamental current as an input signal of . The real

    ACMEE – 2016 Conference Proceedings

    Fig 6. a) Generation of reference source currents using an adaptive theory-based ILST control algorithm. (b) Estimation of the fundamental signal using an adaptive theory-based ILST control algorithm[35].

    component of the output is known as the amplitude of fundamental active power components.

    amplitude of the fundamental reactive power current component is given as:

    The average amplitude of fundamental active power

    components ( ) is estimated using amplitude sum of

    ( )

    (50)

    three-phase load active power components ( , and

    ) divided by three for load balancing.

    Fig. 6(b) shows the subsection of an adaptive theory-based

    ILST control algorithm. The transfer function (s) of a lowpass filter is as:

    First-order low-pass filters are used t separate the low-

    (51)

    frequency components. Mathematically, it is expressed as:

    ( )

    (49)

    where is the time constant of a L.P.F. and it is greater

    than zero.

    Similarly, amplitudes of reactive power components ( , and ) of fundamental load currents are extracted at the zero crossing of the quadrature unit

    The transfer function in Fig. 6(b) in terms of phase a, extracted fundamental current and load current

    canbe written as:

    template phase of PCC voltages using zero-crossing

    C(s)=

    (52)

    detector ( ) and signal and hold logic ( ). An

    output signal of SHC2 is known as the amplitude of

    where forward path transfer function :

    fundamental reactive power components of load current. The average amplitude of the fundamental reactive power

    G(s)=

    H(s) = 1.

    ; and feedback transfer function

    component I is estimated using load fundamental reactive power current components , and

    .Alow-pass filter is used to extract its smooth or ripple- free component. Mathematical expression of the average

    The characteristics equation of the transfer function is written as:

    (53)

    where = time constant of a low-pass filter, = power frequency, = frequency band of a band-pass filter.

    Stability of characteristic equation is analyzed using a RoughHurwitz criterion. Details of this analysis are given in the Appendix B.

    Reference dc-bus voltage and sensed dc-bus voltage of a VSC are compared and error in dc-bus voltage at the kth sampling instant is expressed as:

    (54) This dc-bus voltage error is fed to a proportional integral (PI) regulator whose output is required for maintaining dc-bus voltage of the DSTATCOM.Its output at the kth sampling instant is given as:-

    = 2.4, = 1.54; gaiAnsCoMfEthEe- P20C1C6 CvoonltfaegreenPcIe Pcoronctreoedllienrg:s

    = 3.1, = 0.95.

    The amplitude of reactive power current components of the reference source current is calculated by subtracting average load reactive currents from the output of voltage PI controller as

    (59)

    Three-phase reference source active and reactive power components of currents are estimated using an amplitude of three phase (a, b, and c) load active and reactive power current components, PCC voltages in-phase, and quadrature voltage unit templates as:

    (60)

    } (55) where and kid are the proportional and integral gain

    (61)

    constants of the dc bus PI controller. and

    Reference source currents ( and ) are estimated by

    are the dc-bus voltage errors at kth and (k 1)th instants

    and and are the amplitudes of the active power component of the fundamental reference current at kth and (k1)th instants.

    the addition of reference active and reactive power components of currents as:

    (62)

    (63)

    The amplitude of active power current components of the

    reference source current is calculated by an addition of

    The sensed source currents ( ) and these

    reference source currents ( ) are compared

    output of dc-bus PI controller and an average

    magnitude of the load active power component of currents

    as:

    (56)

    A reactive power component of reference source currents is required for the operation of DSTATCOM in the ZVR mode. In the ZVR mode, source currents are slightly leading from the ac mains voltages because extra leading reactive power component is required for regulating the voltage at PCC. It is zero in the operation of DSTATCOM in the PFC mode.

    The voltage error between reference PCC voltage and its sensed value is fed to the PCC voltage PI controller. The voltage error of ac voltage at the kth sampling instant is given as:

    (57)

    The output of the PCC voltage PI controller for maintaining PCC terminal voltage to a constant value at the kth sampling instant is given as:

    } (58) where is a part of the reactive power component of source current and it is named as . and are the proportional and integral gain constants of the PCC voltage PI controller.Gains of PI controller for dc-bus voltage:

    for respective phases and each phase current error is amplified using PI current regulators and their outputs are compared with a carrier signal of 10 kHz to generate the gating signals for IGBT switches of VSC used as DSTATCOM.

  4. SIMULATION RESULTS AND DISCUSSIONS

    MATLAB with Simulink and sim power system (SPS) toolboxes is used for the development of simulation model of a DSTATCOM and its control algorithm. The performance of various algorithms in time domain for the three phase DSTATCOM is simulated for PFC and ZVR modes of operation at linear and nonlinear loads using developed MATLAB model. The performance of a control algorithm is observed for time-varying linear/nonlinear loads.

    A. Performance of DSTATCOM in the PFC Mode

    The dynamic performance of a VSC-based DSTATCOM for the PFC mode at linear load is shown in Fig. 7. The performance

    indices are as phase voltages at PCC ( ), balanced source currents ( ), load currents ( , , and ), compensator currents ( , , and ), and dc-bus voltage ( ), which are shown under varying loads (at t = 1.351.45 s) conditions. It shows the functions of DSTATCOM and its control algorithm for reactive power compensation and

    load balancing. Similarly, an uncontrolled rectifier as a nonlinear load is connected to the supply system. The dynamic performance of DSTATCOM and waveforms of phase a voltage at PCC , source current , and load current are shown in Figs. 8 and 6(a)(c), respectively.

    CTF Control Algorithm[33]

    Fig7. Dynamic Performance of DSTATCOM under varying linear load in PFC mode [33]

    Fig8.. Dynamic Performance of DSTATCOM under varying nonlinear load in PFC mode[33]

    ACMEE – 2016 Conference Proceedings

    Icos based Algorithm[34]

    Fig9.. Dynamic Performance of DSTATCOM under varying linear load in PFC mode [34]

    Fig10. Dynamic Performance of DSTATCOM under varying nonlinear load in PFC mode[34]

    ILST Algorithm[35]

    Fig13. Dynamic Performance of DSTATCOM under varying linear load in PFC mode [35]

    ACMEE – 2016 Conference Proceedings

    Fig14. Dynamic Performance of DSTATCOM under varying nonlinear load in PFC mode[35]

    C. Performance of DSTATCOM in the ZVR Mode

    In the ZVR mode, the amplitude of PCC voltage is regulated to the reference amplitude by injecting the leading reactive power components. Fig. 7 shows the dynamic performance of the DSTATCOM used for reactive power compensation to achieve ZVR and load balancing under linear loads (at t = 1.35 1.45 s). The performance indices are as PCC phase voltages ( ), balanced source currents ( ), load currents ( , , and

    , compensator currents ( , , and ), amplitude of voltages at PCC ( ), and dc-bus voltage ( ) under time- varying linear loads. The performance of DSTATCOM is also studied under uncontrolled rectifier-based nonlinear loads. The dynamic performance of DSTATCOM in terms of waveforms and harmonics spectra of phase a voltage at PCC , source current , and load current are shown in Figs. 8 and 9(a)(c), respectively.

    CTF Control Algorithm[33]

    Fig15. Dynamic Performance of DSTATCOM under varying linear load in ZVR mode [33].

    Fig16. Dynamic Performance of DSTATCOM under varying non linear load in ZVR mode [33]

    Icos based Algorithm [34]

    Fig17. Dynamic Performance of DSTATCOM under varying linear load in ZVR mode [34].

    Fig18. Dynamic Performance of DSTATCOM under varying nonlinear load in ZVR mode [34]

    ILST Algorithm [35]

    Fig21. Dynamic Performance of DSTATCOM under varying linear load in ZVR mode [35].

    Fig22. Dynamic Performance of DSTATCOM under non varying linear load in ZVR mode [35].

    It may be seen that the THD of the source current and PCC voltage are within IEEE519-1992 standard limit of 5%. PCC voltage is also reguated even at unbalanced loads. Table I shows the summarized results demonstrating the performance of STATCOM. These results shows satisfactory performance of DSTATCOM for reactive power compensation, harmonic elimination, and load balancing of linear and nonlinear loads.

    ACMEE – 2016 Conference Proceedings

    CTF Co

    CTF Co

    ntrol Algorithm [33]

    TABLE I

    TABLE PERFORMANCE OF DSTATCOM

    Operating Mode

    Performance parameters

    Nonlinear load (3 uncontroled rectifier with R-L load)

    PFC mode

    PCC voltage (V),%THD

    236.38V,3.45%

    Supply current (A),%THD

    36.03A,3.06%

    Load current (A),%THD

    35.39A,25.56%

    ZVR mode

    PCC voltage (V),%THD

    239.49V,3.84%

    Supply current (A),%THD

    36.71 A,3.26%

    Load current (A),%THD

    35.87A,25.43%

    DC bus voltage (V)

    700v

    Icos based Algorithm [34]

    TABLE II

    TABLE PERFORMANCE OF DSTATCOM

    Operating Mode

    Performance parameters

    Linear Load

    Nonlinear load (3 uncontroled rectifier with R-L load)

    PFC mode

    PCC voltage (V),%THD

    237.3V,1.15%

    237.72V,2.39%

    Supply current (A),%THD

    41.64A,0.99%

    23.75A,2.13%

    Load current (A),%THD

    52.83A,0.07%

    24.06A,40.75%

    ZVR mode

    PCC voltage (V),%THD

    239.6V,1.44%

    239.63V,2.88%

    Supply current (A),%THD

    42.41A,0.96%

    24.03 A,2.25%

    Load current (A),%THD

    53.34A,0.10%

    24.23A,40.83%

    DC bus voltage (V)

    700v

    700v

    ILST Algorithm [35]

    TABLE IV

    TABLE PERFORMANCE OF DSTATCOM

    Operating Mode

    Performance parameters

    Linear Load

    Nonlinear load (3 uncontroled rectifier with R-L load)

    PFC mode

    PCC voltage (V),%THD

    233.6V,2.43%

    237.23V,2.86%

    Supply current (A),%THD

    55.07A,1.55%

    29.21A,3.19%

    Load current (A),%THD

    67.7A,0.17%

    28.53A,25.98%

    ZVR mode

    PCC voltage (V),%THD

    239.5V,2.37%

    239.56V,3.14%

    Supply current (A),%THD

    57.14 A,1.48%

    29.67 A,3.27%

    Load current (A),%THD

    69.4A,0.19%

    28.77A,26.15%

    DC bus voltage (V)

    700v

    700v

  5. CONCLUSION

In this paper, a comparative performance evaluation of the

V. CONCLUSION

In this paper, a comparative performance evaluation of the CTF, Icosine based Isolated Topology with Unipolar Switching control algorithm and adaptive theory based Improved Linear Sinusoidal Tracer control algorithm(ILST) is presented. The results are analyzed considering the THD (%) in PFC and in the ZVR mode. The target for all these compensation techniques is to achieve the sinusoidal source current in phase with positive sequence component of the supply fundamental voltage. A three-phase DSTATCOM has been implemented for compensation of linear and nonlinear loads using CTF, Icosine based Isolated Topology with Unipolar Switching control algorithm, and adaptive theory based Improved Linear Sinusoidal Tracer control algorithm (ILST). Various functions of DSTATCOM such as reactive power compensation, harmonic elimination, and load balancing have been demonstrated in PFC and ZVR modes for all the algorithms. From these results, it is concluded that ILST control algorithm have been found most suitable for time- varying loads among all discussed algorithms. PCC and DC bus voltages of the DSTATCOM have also been regulated to reference values under unbalanced loads.

This condition satisfieAsCthMeEsEta-b2il0i1ty6 CofonthfeerecnocnetProrlolceer.edFinogrs this application, consider values of time constant = 0.1 s, power frequency = 314.15 rad/sec, and frequency band of band-pass filter = 250 rad/sec. After putting these values in Table II, there are no changes in the sign of the elements in the first column and it is observed that the control algorithm is stable with a wide range of internal parameter variations.

Design of DSTATCOM

The design of DSTATCOM with transformer configuration based new topology is given in this section.

  1. Selection dc Voltage

    DC bus voltage ( ) = 2 /m (64) where, m (modulation index) considered as 1 and L (138.33 V) is the ac line output voltage of VSC used in STATCOM. Calculated value of dc bus voltage is 195.63 V and its selected value is 230V.

  2. Selection of dc bus Capacitor

    The value of dc bus of VSC of DSTATCOM is computed as,DC bus capacitor

    { }

    APPENDIX A

    (

    (65)

    AC supply source: three-Phase, 415 V (LL), 50 Hz; source

    impedance: = 0.07 , = 2 mH; Load: 1) Linear: 50 kVA, 0.8 p.f. lagging; 2) Nonlinear: three-phase full-bridge uncontrolled rectifier with R = 15 and L = 100 mH; ripple filter: = 5 , = 7 F; dc-bus capacitance: 12000 F; reference dc-bus voltage: 700 V; interfacing inductor Lf = 2.5 mH; gains of PI controller for dc-bus voltage:

    = 2.4, = 1.54; gains of the PCC voltage PI controller:

    = 3.1, = 0.95.

    APPENDIX B

    The stability of the ILST control algorithm is analyzed using eq (72) .

    Its Routh array formation is shown as:-

    TABLE V

    S2

    +

    S1

    +1

    0

    S0

    +

    TABLE:- ROUTH ARRY FORMATION

    In Table, there are no changes in the sign of the elements in the first column for any positive value of , , and . For this condition, it is concluded that there is none of roots in the characteristic equation with a positive real number.

    where, is the nominal dc voltage and is the minimum voltage level of dc bus, k is the over loading factor, is the supply phase voltage, factor r is varying between 0.04 to 0.15. is the phase current of the VSC and t is time for which dc bus voltage is to be recovered. Calculated value of dc bus capacitor is 7160.01F and its selected value is 8500 F.

  3. Selection of ac Inductor

    The value of interfacing inductor is estimated as,

    AC inductance

    ( ) = / (8*k*fs* (66) where is the dc bus voltage, k=1.2, m=1, fs is the switching frequency and is the acceptable % range of current ripple.

    For a considered value of 2% of current ripple in

    DSTATCOM current. Calculated value of ac inductor is 1.77

    mH and its selected value is 2 mH.

  4. Voltage Rating of the IGBTs

    The voltage rating ( ) of IGBT under dynamic conditions as, = + (67) where is the 15% overshoot in the dc bus voltage under dynamic condition. The voltage rating of switch is calculated as 264.45 V.

  5. Current Rating of the IGBT

The current rating ( ) of IGBT under dynamic conditions as, =1.2( + ) (68)

where (2 ) and (5% of ) are the peak value of DSTACOM current and value of allow ripple currents. The minimum current rating of switch is 73.32 A

REFERENCES

  1. M. Aredes, H. Akagi, E. H. Watanabe, E.V. Salgado, L. F. Encaracao, "Comparison between the p-r and p-q-r theories in three phase four wire systems, " IEEE Trans. Power Electronics, vol. 24, No. 4, pp. 924-933,Apr. 2009.

  2. A Moreno-Munoz, Power Quality: Mitigation Technologies in a Distributed Environment. London, U. K.: Springer-Verlag, 2007.

  3. H. Akagi, E. H. Watanabe, and M. Aredes, instantaneous Power Theory and Applications to Power Conditioning, Hoboken, NJ:

    Wiley, 2007

  4. L. H. Tey, P.L. So and Y.C. Chu,Improvement of power quality usingadaptive shunt active filter, IEEE Transactions on Power Delivery, vol. 20, no.2, pp. 1558-1568, April 2005

  5. Bhim Singh and Jitendra Solanki,An improved control approach for DSTATCOM with distorted and unbalanced AC mains,Journal of Power Electronics, vol. 8, no. 2, pp. 131-140, April 2008

  6. R.R. Sawant and M.C. Chandorkar,A multifunctional four-leg grid connected compensator,IEEE Transactions on Industry Applications, vol.45, no.1, pp.249-259, Jan.-Feb. 2009.

  7. R. Crosier and S. Wang,DQ-Frame Modeling of an active power filter integrated with a grid-connected, multifunctional electric vehicle charging station,Accepted for publication IEEE Transactions on Power Electronics

  8. A. Bueno, J. M. Aller, J.A. Restrepo, R. Harley and T.G. Habetler,Harmonic and unbalance compensation based on direct power control for electric railway systems,Accepted for publication IEEE Transactions on Power Electronics.

  9. Bhim Singh and V Rajgopal,Decoupled Solid State Controller for Asynchronous Generator in Pico-Hydro Power Generation,IETE Journal of Research, pp. 139-145, vol. 56, no.3, May/Jun. 2010

  10. Bhim Singh and Shailendra Sharma,Neural Network Based Voltage and Frequency Controller for Isolated Wind Power Generation,IETE Journal of Research, vol. 57, pp. 462-472, Sept-

    Oct. 2011

  11. Alkha Singh,Performance evaluation of three different configuration of DSTATCOM with nonlinear loads,IETE Journal of Research, vol. 56 , no. 6, pp. 313-326, Nov-Dec. 2006

  12. H. Akagi, Y. Kanazawa and A. Nabae,Instantaneous reactive power compensators comprising switching devices without energy storage components,IEEE Trans. Industry Applications, vol. IA- 20, no. 3, pp.625-633, 1984.

  13. Shiguo Luo and Zhencheng Hou,An adaptive detecting method for harmonic and reactive currents,IEEE Trans. Industrial Electronics,vol.42, pp. 85-89, 1995.

  14. Katsumi Nishida, Md Rukonuzzaman and Mutsuo Nakaoka,A novelsingle-phase shunt active power filter with adaptive neural network based harmonic detection,IEEE Trans. LA, vol.125, pp. 9- 15, 2005

  15. R.L. de Araujo Ribeiro, C.C. de Azevedo and R.M. de Sousa,A robust adaptive control strategy of active power filters for power- factor correction, harmonic compensation, and balancing of nonlinear loads,IEEE Trans. on Power Electronics, vol. 27, no. 2, pp.718-730, Feb.2012.

  16. Qun Wang, Ning Wu and Zhaoan Wang,A neuron adaptive detecting approach of harmonic current for APF and its realization of analog circuit,IEEE Trans. Ins. Measure, vol. 50, pp.77-84, Feb 2001.

  17. Romuald Rocher, Daniel Menard, Olivier Sentieys and Pascal Scalart,Digital Signal Processing, vol. 20, pp. 640652,2010.

    ACMEE – 2016 Conference Proceedings

  18. Karuppanan P and Kamala Kanta Mahapatra,PI and fuzzy logic

    controllers for shunt active power filter-A report, Journal of ISA Transactions, vol. 51, pp. 163-169,2012.

  19. Deepika Masand, Shailendra Jain and Gayatri Agnihotri,Control strategies for distribution static compensator for power quality improvement, IETE Journal of Research, vol. 54 , no. 6, pp. 421- 428, Nov-Dec. 2008.

  20. Bhim Singh and Jitendra Solanki,A comparison of control algorithms for DSTATCOM, IEEE Transactions on Industrial Electronics, vol. 56, no. 7, pp.2738-2745, July 2009

  21. Bhim Singh, P. Jayaprakash, Sunil Kumar and D. P. Kothari,Implementation of neural network-controlled three-leg VSC and a transformer as three-phase four-wire DSTATCOM,IEEE Transactions on Industry Applications, vol. 47, no. 4, July 2011

  22. T. L. Lee and S. H.Hu, Discrete frequency-tuning active filter to suppress harmonic resonances of closed-loop distribution power systems, IEEE Trans. Power Electron., vol. 26, no. 1, pp. 137 148, Jan. 2011.

  23. F. Barrero, S.Mart´ýnez, F.Yeves, and P. M.Mart´ýnez, Active power filters for line conditioning: A critical evaluation, IEEE Trans. Power Delivery, vol. 15, no. 1, pp. 319325, Jan. 2000.

  24. J.-C. Wu, H.-L. Jou, Y.-T. Feng, W.-P. Hsu, M.-S. Huang, and W.- J. Hou, Novel circuit topology for three-phase active power filter, IEEE Trans. Power Delivery, vol. 22, no. 1, pp. 444449, Jan. 2007.

  25. IEEE recommended practices and requirement for harmonic control on electric power System, IEEE Std. 519, 1992.

  26. B. Singh, P. Jayaprakash, T. R. Somayajulu,D. P.Kothari,A.Chandra, and K. Al-Haddad, Integrated three- eg VSC with a zig-zag transformer based three-phase four-wire DSTATCOM for power quality improvement, in Proc. 34th IEEE Annu. Conf. Ind. Electron., 2008, pp. 796801.

  27. N. Mariun, A. Alam, S. Mahmod, and H. Hizam, Review of control strategies for power quality conditioners, in Proc. Nat. Power Energy Conf., 2004, pp. 109115.

  28. Y. F. Wang and Y. W. Li, A grid fundamental and harmonic components detectionmethod for single- phase systems, IEEE Trans. Power Electron., vol. 28, no. 5, pp. 22042213, May 2013.

  29. Bhim Singh, Alka Adya, A.P. Mittal and J.R.P. Gupta, Power quality enhancement with DSTATCOM for small isolated alternator feeding distribution system,in Proc. of IEEE International conference on Power Elctronics,Drives and Energy Systems,2005,pp 274-279.

  30. B. Singh and S. Kumar,Control of DSTATCOM using Icos algorithm, in Proc. of 35th Annual Conference of IEEE Industrial Electronics, 2009, pp.322-327.

  31. Singh, B., Jayaprakash, P., Kothari, D.P.: Magnetics for neutral current compensation in three-phase four- ire distribution system. Proc. Joint Int. Conf. on Power Electronics, Drives and Energy Systems and Power India, 2010, pp. 17.

  32. Cardenas, V., Moran, L., Bahamondes, A., Dixon, J.: Comparative analysis of real time reference eneration techniques for four-wire shunt active power filters. Proc. IEEE 34th Annual Power Electronics Specialist Conf., 2003, vol. 2, pp. 791796

  33. Sabha Raj Arya, and Bhim Singh,CTF control algorithm of DSTATCOM for power factor correction and zero voltage regulation, in Proc. of IEEE Third International Conference on Sustainable Energy Technologies, pp. 157-162, 2012. Kathmandu (Nepal) Sept.

  34. Bhim Singh and Sabha Raj Arya,A new isolated topology of DSTATCOM with Unipolar Switching,in Proc. of National Power System Conference, pp.1-6, 2012. BHU ,IIT Varanasi Dec 2012.

  35. Bhim Singh and Sabha Raj Arya Adaptive theory-based improved linear sinusoidal tracer control algorithm for DSTATCOM,IEEE Transactions on Power Electronics, vol. 28, no.8, pp.3768-3778, Aug. 2013.