A Frame Work for Over Current Relay Protection Optimization

DOI : 10.17577/IJERTV4IS090571

Download Full-Text PDF Cite this Publication

Text Only Version

A Frame Work for Over Current Relay Protection Optimization

Ukwueze V. C.

Department of Electrical Engineering, University of Nigeria Nsukka,

Enugu State, Nigeria.

Onah J. N.

Department of Electrical Engineering, University of Nigeria Nsukka,

Enugu State, Nigeria.

Madueme T. C.

Department of Electrical Engineering, University of Nigeria Nsukka,

Enugu State, Nigeria.

Abstract: Faults in electrical power systems are common and this affects the reliability and security of electrical power system. In view to address the above scenario, an optimized algorithm prototype (Differential Evolution) for relay operation was developed and implemented using non-linear integer programming. These program codes were written in MATHLAB/SIMULINK environment for proper coordination of the relay prototype. Numerical values gotten from the simulation shows that the proposed algorithm is of high precision and stability.

Keywords: Power system protection, differential evolution, constraints handling, pickup current and interaction buffer.

I. INTRODUCTION

Electrical energy system consists of equipment that generates, transmit and distribute electrical energy to the end users. The reliability of and security of electrical supply becomes an important factor in modern society [1]. However the expanding of the power system such as intense increase of transmission line capacity and increase of grids looping degree will increase the complexity of power system [1]. To improve the degree of operation of the electrical energy system, power system protection equipment is utilized for protection purposes. Power system protection equipment is used to protect power system and swiftly isolate abnormal conditions from the system [2].

Every protective system must possess the basic qualities of selectivity, reliability and dependability. Protective relay has these qualities and plays great impact in power system. Protective relays are used to detect abnormality in power system and isolate the faulty part of the system within the shortest time [1]. For the protective relay to achieve this, relay coordination study should be carried out [3]. coordination of protection is defined as the process of choosing settings or time delay characteristics of protective devices such that the operation of the device will occur in a specified order to minimize customer service interruption, reduce equipment damage or personal injury[3].

Numerical relays provide a wide range of protection functions such as over current, directional over current, under voltage and also other types of protection [1]. Over current relay are the most widely used protection system used to

detect and isolate faults in power system [3]. Over current relay protection operates with or without an intended time delay and trips the associated circuit breaker whenever a set point for the current is exceeded. For the time delay over current relays, coordination involves setting the pickup current and time multiplier parameters [3]. For decades, over current protection has been using conventional methods for over current relay protection. However according to [4], automated over current relay coordination using computer program has been proposed and tested. Recently many other automated methods for over current relay coordination have been reviewed as below.

In an effort to optimize the coordination of over current relays, some researchers used non-linear programming to solve the coordination problem but this seems to be complex and time consuming [5]. In [6] relay coordination were formulated using mixed integer non-linear programming (MINLP) and was solved using General Algebraic Modeling system (GAMs) software. Results of which were appreciative. Application of Evolution Algorithms (EAs) such as Genetic Algorithms (Gas) has drawn much attention [7]. Although some authors have shown that GAs has limitations in its operation. Limitations like premature convergence, long time of processing data among others. Various versions of GAs have been introduced to cope with the above limitations. Some of the versions are Evolutionary programming [8], Differential evolution (DE) [9] etc.

In this paper, well known differential evolution was used to solve the coordination problem of an over current relay and implemented using mixed integer non-linear programming. The result of which shows a high level of improvement in the power system over current protection.

  1. THE DIFFERENTIAL EVOLUTION (D.E)

    ALGORITHM

      1. Scenario i: Population initialization

        The initialization state of a differential evolution involves seeding of the algorithm with a population of N candidates or individuals of uniform random distribution. These candidates of particular population are the parent population and are retained within the boundary of upper and lower limits respectively.

      2. Scenario ii: Reproduction of the D.E

        i

        An offspring population can be produced by perturbing the value of each control variable in each individual parent population. It produces an offspring of kth generation by the difference vector of the parent individuals, according to equation (1) below. The current evolution of the individuals is located X t. Where i is the serial number of individuals in the population, t is the evolution generation of randomly

        Start

        Initialization

        Finding out the initial best individual

        K = 1

        Reproduction

        , X

        r1

        r2

        selected three individuals from current population X t t

        K = K + 1

        ,

        r2

        and Xr3t. The difference between two individual vectors (X t

        Fitness evaluation for each individual

        r3

        r1

        X t), were added to the r1 individual vector X t after

        Selection

        increased scaling factor Fw, yielding the updated individual as follows:

        K t+1 = X t + F (X

        t X

        t) . (1)

        Finding the best individual

        Where,

        ri w r2 r3

        ri

        Fw is the zoom coefficient and is uniformly distributed in the range of [0, 1]. X t is the control variable of the best individual.

      3. Scenario iii: The evaluation of the individual:

    K < max generation size No

    Finish

    Yes

    A fitness function is defined for evaluating the fitness of each individual as:

    Figure 1.0 The flow chart of the D.E Algorithm

    F( xi(k)) = Where,

    h

    1 fv xci

    i1

    ti l

    . (2)

    2.6 Constraints handling of the optimized model of the relay. To minimize the total operating time of a protective relay system under different fault zones, its operating time is taken as the objective function for the optimal coordination of the relay.

    Fv equals a penalty coefficient, h is the number of constants and ci is the penalty value which is equal to 1 (one) when it meets the constraints and 0 (zero) otherwise, til is the operating time.

      1. Scenario iv: Selection:

        Selection strategy of the differential evolution can be

        The optimal coordination determines three parameters; the

        pickup current setting, the time setting multiplier and the time coordination interval of the protective relay as the major constraints.

        The objective function can thus be expressed as:

        Np

        wi til

        j

        described as one on one search, where an offspring individual X i(k) is compared with its parent. After the comparison,

        minJ = Where,

        i1 . . (4)

        better won and was upated for the next generation as described

        below.

        (3)

      2. Scenario v: Termination.

    The procedure terminates if it meets a set point or after a number of specified generations. Figure 1.0 depicts the flow chart of the differential evolution.

    NP is the number of primary and back up relays, Wi is the coefficient representing the ability of recurrence of a fault and could be set to 1 (one) for all possible faults if reliable data are available. ti is the operating time of the ith relay when a fault occurs in zone L. The current/time characteristics of a directional over current relay under the institute of Electrical and Electronic Engineering (IEEE) standard C37.112-1996 and IEC255-3 can be expressed as [10].

    Where,

    Tmi is the time setting multiplier, IiL is the short

    circuit current passing through the relay when faults occurs in zone L. Ipi is the pickup current setting of the ith relays and and y are all constants. The constraints on the time setting multiplier and the operating time in this model are described as

    Tmi min Tmi Tmi max . . (6) ti min ti ti max . . . (7)

    Where,

    Tmi is in the range of 0.01 to 1.

      1. Constraints on the pickup current setting:

        The pickup current setting of each protective relay is discrete, a 0 1 variable of ymi. The setting were expressed as the product of the pickup current and the specified binary variable, thus

        Ipi = ymi .Pai . . . (8) Where, Pai are the available pickup current specified values.

        Generally,

        Where, i = 1, 2, . . . , n

        In addition, the pickup current setting (Ipi) of each current relay meet the following conditions.

        (11)

      2. Constraints on the coordination interval of the protective relay:

    For the constraints on the coordination interval of the protective relay,

    Tbl – til CTi . . (12) Where, Tbl is the operating time of the backup relay Ri when a fault occur in zone L and CTi is the coordination time interval usually specified between 0.2 seconds to 0.5 seconds.

  2. THE POWER SYSTEM MODEL

    For the evaluation of the protection system, the model of the power system is required. The generator model, voltage transformer model, current transformer model are realized using the MATLAB/SIMU-LINK SIM power system TOOL box. This was done in MATLAB/ SIMU-LINK environment as shown in figure 2.0 below.

    v2

    Continuous

    To Workspace5

    powergui

    + v

    Voltage Measurement

    + v

    Voltage Measurement2

    a a

    Scope

    1

    com a + i

    A B

    C

    A

    b + i

    b Trip

    c

    RA

    1

    Constant

    b Trip

    c

    RB

    R

    Y

    B

    a

    com

    + i

    A

    b

    + i

    B

    1. c

      C

      i i

      16

      2

    2. c + –

    + –

    Busbar

    Three phase breaker

    + i

    Current Measurement

    + i

    + i

    + i

    3

    Scope1

    Pi Section Line

    a b

    c

    RA1

    Three phase breaker

    v1

    To Workspace3

    Clock

    Trip

    4

    Trip2

    Scope2

    + v

    Voltage Measurement1

    A B

    C

    A B C

    t2

    To Workspace1

    69

    ip

    To Workspace4 Trip

    To Workspace

    v

    To Workspace2

    Figure:2.0 SIMULINK MODEL OF THE POWER SYSTEM 1 68

    FOR THE PROTECTION SYSTEM EVALUATION

    To Workspace6

    The transmission line parameters were calculated by MATLAB power system transient solvers. The power system network under study consists of one three phase power supply as a power station supplying 400km transmission line. The bus bars are equipped with current measurement and voltage measurement devices. At the sending end and receiving end are circuit breakers. The relay model developed in SIMU-LINK is integrated with the power system model in the MATLAB/SIMU-LINK environment.

    The mixed integer optimization model for the protection performance evaluation is coded in the MATLAB m-file, using the MATLAB workspace to integrate it with the power system model. The interaction buffer in the MATLAB workspace is coded to structure data exchanges between the power system model, relay model and optimization evaluation model.

  3. SIMULATION AND RESULTS.

    Simulation studies were carried out to test and evaluate the performance of the protection evaluation model. Two different events tests, optimized and un-optimized, were carried out to ascertain the performance of the proposed

    0.9

    0.8

    0.7

    0.6

    0.5

    0.4

    0.3

    0.2

    0.1

    Current (A)

    0

    0 1 2 3 4 5 6 7 8 9 Time(s)

    Figure 4.0: Trip transition of relay with 3-phase fault transition set at 5.0 seconds

    frame work. For un-optimized event, evaluation of the signal profile of the system and the transition of the relay trip signal when a 3- phase fault was triggered at time 5.0 seconds from the start of simulation was captured, figure 3.0 and 4.0. The rise in current at the start up of simulation was as a result of current inrush and harmonics in the transformer which settled within 3.0 seconds. At 5th seconds, a three face ground fault was introduced evidenced by the rise in current up to 800A and was cleared at 8.8659 seconds.

    For the evaluation purpose, based on the hypothetic

    evaluation of the optimization algorithm, the expected trip time of the relay was estimated at 8.5232 seconds, figure 5.0. However the relay tripped at 8.8659 that is a variance of 0.3427 seconds.

    Current

    (A)

    0.9

    800

    600

    400

    200

    0

    -200

    -400

    -600

    -800

    0.8

    0.7

    0.6

    0.5

    0.4

    0.3

    0.2

    0.1

    0

    0 1 2 3 4 5 6 7 8 9

    Time(s)

    Figure 5.0: Expected relay trip transition based on optimization

    evaluation algorithm with fault transition set at 5.0 seconds

    10000 1 2 3 4 5 6 7 8 9

    Figure 3.0 Signal profile with 3-phase fault transition time set to 5.0 seconds

    Time(s)

    This shows that the relay action falls short of optimal response. The fault event was repeated at 5.25, 5.5, 5.75 and

    6.0 seconds respectively. Results of which are shown in the table 1.0 below.

    Scenarios

    II

    III

    IV

    V

    VI

    Fault transition time

    (seconds)

    5.00

    5.25

    5.50

    5.75

    6.00

    Expected relay trip

    time based on optimizat- ion technique

    (seconds)

    8.5232

    8.7651

    9.0272

    9.2692

    9.5212

    Actual relay trip time

    (seconds)

    8.5736

    8.8165

    9.0675

    9.3196

    9.5716

    Expected fault clearing time

    (seconds)

    3.5232

    3.5151

    3.5272

    3.5192

    3.5212

    Actual fault

    clearing time (seconds)

    3.5736

    3.5655

    3.5675

    3.5696

    3.5715

    Variance

    (seconds)

    0.0504

    0.0504

    0.0403

    0.0504

    0.0504

    Table 1.0 Evaluation of expected and actual relay response.

    Adjustment was made in the relay settings based on the trend in the response expectations of the optimization evaluation technique. By giving the trend either upwards or downwards) in the deviation of the actual relay response from that of the evaluation expectation, the proper adjustment in the relay zone settings was done. On the basis of evaluation, the expected relay trip times indicates lower values than the actual relay trip times (as can be inferred from table 1.0). This gives the indication of downward adjustment in the relay zone settings. Hence the expectation is downward adjustment of the setting based on the percentage variance (since zone setting is in percentage). The percentage value for downward adjustment in relay zone reach can be found as follows [49]:

    . (13)

    = (1.7131/46.8196) x 100%

    = 3.6602%

    = 3.66%.

    Hence, the relay zone setting is reduced by 3. 6602 %. The simulations are repeated based on the relay adjustable settings. The new protection system (optimized) response shows a reduction of fault clearing times and variances for the fault transition times of 5.0, 5.25, 5.50, 5.75 and 6.0 seconds, table 2.0 below. Figure 6.0 below shows the mean variances of the two fault events.

    Table 2.0 Comparison of expected and actual relay responses after optimization.

    Scenarios

    II

    III

    IV

    V

    VI

    Fault transition time

    (seconds)

    5.00

    5.25

    5.50

    5.75

    6.00

    Expected relay trip time based on optimizat-ion

    technique (seconds)

    8.5232

    8.7651

    9.0272

    9.2692

    9.5212

    Actual relay

    trip time (seconds)

    8.8659

    9.1079

    9.3599

    9.6119

    9.8740

    Expected fault

    clearing time (seconds)

    3.5232

    3.5151

    3.5272

    3.5192

    3.5212

    Actual fault

    clearing time (seconds)

    3.8659

    3.8579

    3.8599

    3.8619

    3.8740

    Variance (seconds)

    0.3427

    0.3428

    0.3327

    0.3427

    0.3528

    Variance after

    optimization (s) Variance before optimization (s)

    mean variance after optimization

    mean variance before optimization

    0.4

    0.35

    0.3

    0.25

    0.2

    0.15

    0.1

    0.05

    0

    Figure 6.0 Comparison of variances of optimized and un-optimized trip time of the relay response.

  4. CONCLUSION.

    Different protection schemes have been reviewed. The review on relay coordination shows that there is always a mismatch between the actual and expected relay coordination time. In other words the actual trip time of a relay is never the real/expected time of tripping. Thus some adjustments are deemed necessary to overcome the mirage.

    Implementation of Differential Evolution solved by mixed integer non-linear programming was able to reduce the mismatch in relay coordination interval between the actual and expected trip times. The extent to which the reduction was made was arrived at after evaluating the percentage variances in trip time as against the total actual trip time of a relay. The results of the evaluation were encouraging as it shows a reasonable improvement (7.6%) in the relay time coordination.

  5. REFERENCES.

[1]. Yin Lee Goh,Agilesnari K. Ramasamy Farrukh Hafiz Nagi, Aidil Azwin Zainul Abidin Evaluation of DSP based numerical relay for over current protection International Journal of System Application, Engineering and development Issue 3, vol. 5, pp 396-403, 2011.

[2]. Anderson, P.M. Power system protection McGraw-Hill, New York, 1999.

[3]. N.M. Stenane, K.A. folly. Application of evolutionary algorithm for optimal directional over current relay coordination Journal of computer and communication, Issue 2, pp 103-111, 2014.

[4]. Tsien, H.Y An automatic digital computer program for setting transmission line directional over current relays IEEE transaction in power apparatus and systems, 83, 1048- 1053, 1964.

[5]. H.A Abyneh, M.Al-Dabbgh, H.K karegar, S.H.H Sadeghi,

R.A.H Kham A new optimal approach for coordination over current relays in interconnected power system IEEE transaction on power delivery, vol. 18, pp. 430-435, 2003.

[6]. A. J. Urdaneta, R. nadira, L. Perez Optimal coordination of directional over current relay in interconnected power system IEEE transaction on power delivery, vol. 3, pp. 903- 911, 1988.

[7]. Coello Coello, C. A Theorical and numerical constraint- handling techniques used with evolutionary algorithm: a survey of the state of the art Computer Methods in Applied Mechanics and Engineering 191, 1245-1287.

[8]. So, C. W and Li, K. K Over current relay coordination by evolutionary program Electric Power Systems Research, 53, 83-90,2000.

[9]. Thangaraj, R, Pant, M. and Abrahim A. New mutation scheme for differential evolution algorithm and their application to the optimization of directional over current relay settings Applied Mathematics and Computation , 216, 532-544, 2010.

[10].Xinke Gao, Yapeng Liv, Congying Wang, Impact of protective relays on voltage sag index PRZEGLAD ELEKTROTECHNICZING, Issue 0033-2007, R-89NR.5, pp 55, 2013.

[11].Hossami Kahlkhalis, Hohl Harmsen Evaluation of digital relay for over-current protection of power systems Innovative power engineering, pp. 88, 2008.

Leave a Reply