A Review of Various Frequency Drift Based Islanding Detection Methods

DOI : 10.17577/IJERTV6IS080035

Download Full-Text PDF Cite this Publication

Text Only Version

A Review of Various Frequency Drift Based Islanding Detection Methods

Muhammad Al Azis Bachrun, Eka Firmansyah, Muhammad Isnaeni Bambang Setyonegoro Department of Electrical Engineering and Information Technology, Universitas Gadjah Mada, Yogyakarta, Indonesia

Abstract Islanding is a phenomenon where the PV module is still trying to energize the grid, even though the grid has been disconnected. This phenomenon can cause several problems, therefore many islanding detection methods have been introduced. One of the widely used methods is the active frequency drift. Yet, this method still has some drawbacks. Hence, many studies have been done to develop the conventional active frequency drift method, which can be classified as hybrid and non-hybrid methods. This paper will review both types of various developed frequency drift based islanding detection methods and compare their performances to the conventional active frequency methods.

Keywords: Active frequency drift, islanding, hybrid methods, non- hybrid methods.

  1. INTRODUCTION

    Islanding is one of the phenomenon in electrical power system, where the PV module is still trying to energize the grid, even though the grid has been disconnected [1]. It creates several problem, such as, endanger the maintenance officers, generating a voltage and frequency that can damage electrical equipment, and when the grid is being reconnected, islanding creates an unsynchronized fault between the generator [2]. Therefore, islanding detection capability is one of essential parts in every PV inverter system.

    An active islanding detection method injects a disturbing signal into the system to notify the protective relays that an islanding is occurring, so that the relays can stop the generator that is still trying to energize the grid [3]. Active islanding detection method works faster than the passive one, therefore it has been used widely around the world [4].

    One of the active methods that are commonly used is an active frequency drift (AFD) method. When an islanding occurred, this method will either increase or decrease the frequency of the system to the value that is outside the normal frequency. Then, the protecting relays will disconnect the generator and stop the islanding [5]. However, the AFD method still has some drawbacks. It is considered not effective and is not able to detect islanding under the standard time limit [5]. Hence, many studies have been done to develop the AFD method.

    Generally, there are two ways of developing AFD method. First, there are many studies that develop an existing frequency drift based islanding detection method directly, and therefore create a novel method. In this paper, this type is called the non-hybrid methods. The other ways is by combining two existing frequency drift based islanding

    detection methods to create an improved method. In this paper, this type is called the hybrid methods. This paper will review both types of various developed frequency drift based islanding detection methods and compare their performances to the conventional active frequency methods.

  2. ACTIVE FREQUENCY METHODS AND THE MEASUREMENT STANDARDS

    The AFD method is firstly introduced in 1997 and received a warm welcome because it offers a significant improved compared to the passive islanding detection methods and can be easily implemented [6]. In AFD, a short period of zero time is added to the inverters output current, as can be seen in Fig.

    1. The ratio of the zero time (Tz) compared to half the period of the voltage waveform (Tgrid) is called the chopping fraction (cf)

    cf = Tz/Tgrid (1)

    However, this method still has some drawbacks. Reference

    [7] tested the conventional AFD method based on standard IEEE 929-2000 and this method failed to detect islanding when the load frequency is between 58.99 Hz and 60.19 Hz. Thus, many studies have developed the conventional method in order to meet the standard.

    There are two standards that are commonly used in evaluating the performance of active frequency drift methods, which are IEEE Std. 929-2000 and IEEE Std. 1547-2003. Table 1 gives the comparison between these two standards.

    Standards

    IEEE Std. 929-2000

    IEEE Std. 1547-2003

    Parameter

    Limits

    Trip Time

    Limit

    Limits

    Trip Time

    Limit

    Voltage

    V<60

    6 cycles

    V<60

    0.16 s

    60V106

    120 cycles

    60V106

    2.0 s

    106V132

    Normal

    operation

    106V132

    Normal

    operation

    132V165

    120 cycles

    132V165

    1.0 s

    165V

    2 cycles

    165V

    0.16 s

    Frequency

    59.3-60.5 Hz

    Normal

    operation

    59.3-60.5 Hz

    Normal

    operation

    Otherwise

    6 cycles

    Otherwise

    0.16 s

    THDi (%)

    <5%

    Always

    5%

    Always

    Table 1. The Comparison of Two Standards in Evaluating AFDs Performance [8]

    Fig.1 Example of a waveform in AFD [9]

  3. THE NON-HYBRID AND HYBRID METHODS

    1. Non-Hybrid Methods

      One of the improved active frequency drift method is called active frequency drift with pulsation of chopping fraction (AFDPCF) [9]. Unlike the conventional AFD method that uses a fixed value of cf, AFDPCF method uses a varied cf value based on the algorithm:

      where Tcf max_on = Tcf min_on = 20 cycles. The varied value of cf in AFDPCF method can be seen in Fig. 2. The AFDPCF method is tested based on standard IEEE 929-2000. This method can detect islanding in 0.674 1.108 s depends on the load conditions.

      However, the AFDPCF method also has some drawbacks. This method requires long time to detect islanding and ineffective in capacitive loads. The modified AFDPCF (M- AFDPCF) is introduced in [2] to overcome these drawbacks.

      The M-AFDPCF method uses different algorithm to vary the value of cf, which is,

      where cfmax and cfmin are the positive maximum and negative minimum value of cf, respectively. This algorithm will create a different pulsation of chopping fraction as can be seen in Fig. 3. When tested in standard IEEE 929-2000, the M- AFDPCF method has a significant improvement in islanding detection time, which is only 0.45 s.

      Fig. 2 The Value of cf in AFDPCF Method

      Fig. 3 The Value of cf in M-AFDPCF Method

      Another improved method is called active frequency drift with double positive feedback (AFDDPF). Ref. [10] explains that the first positive feedback will determine the frequency of the grid current commands and the second one will adjust the weight of the first feedback. This method is then tested in a structure based on standard IEEE 929-2000. The experiment result is this method can detect islanding in 0.13 s with total harmonic distortion of grid current (THDi) = 2.97%. [10]

      Reference [11] introduces an improved method that used alternate current disturbances between the odd and even cycle to drifts the frequency of inverter output current outside the range of over- and under-frequency relay (OFR/UFR. Whe tested in standard IEEE 929-2000, this method can detect islanding in 0.62 s.

    2. Hybrid Methods

    The other way of improving a conventional AFD method is by combining two developed AFD methods. This way usually creates a more effective hybrid method than each of the method when being operated separately.

    One of the current hybrid methods is developed by combining a positive feedback frequency shift (PFFS) and reactive power variation (RPV) [12]. Unlike the common PFFS method, this hybrid method can effectively detect islanding while introducing a small degradation to the quality of power system. This method is tested using standard IEEE 1547-2003 and showed a great result. The hybrid method of PFFS-RPV can detect islanding in 0.2 s.

    Another hybrid method is introduced in [13]. This hybrid method combines slip-mode frequency shift (SMS) method and reactive power versus frequency (Q-f) as active method. This method is developed to overcome the drawback in SMS method, which is poor islanding detection in constant power controlled inverter. By combining SMS and Q-f, this hybrid method has faster islanding detection time for loads with high quality factor (Qf) and smaller NDZ [13]. When tested in structure based on standard IEEE 1547-2003, both of the SMS and Q-f method cannot detect islanding in Qf 1. However, the new hybrid method can detect islanding in 0.1 0.6 s.

    The hybrid method can also be comprised of two active frequency drift methods. Reference [14] introduces a new hybrid method by combining the conventional AFD method and SMS. However, this method has slower islanding detection time compared to the aforementioned hybrid methods. When tested in standard IEEE 1547-2003, this hybrid method can detect islanding in 1.2 s.

    Reference [15] has better result in developing two active frequency drift methods. Instead of using the conventional AFD methods, [15] combined Sandia frequency shift (SFS) method with SMS method. When tested in structure based on standard IEEE 929-2000, this hybrid method can detect islanding in 0.06 s.

    The comparison of the islanding detection time of all of the reviewed methods can be seen in Fig. 4 and Fig. 5. Fig. 4 shows the islanding detection time of all of the reviewed methods that are tested in standard IEEE 929-2000 while Fig.5 displays the comparison in standard IEEE 1547-2003.

    In Fig.4 the islanding detection time of conventional AFD method is given 2 s since it is a maximum islanding detection time allowed in standard IEEE 929-2000. The other developed AFD method shows significant decrease in islanding detection time compared to the conventional AFD method. The AFDPCF method has a varied value of islanding detection time of 0.674 1.108 s depends on load conditions. However, in Fig.4 the minimum islanding detection time of AFDPCF is displayed.

    In Fig.5 the hybrid of conventional AFD method still has a slow islanding detection time compared to other hybrid methods. This is probably caused by the fixed value of cf in conventional AFD causes an inefficient performance of the method. The hybrid method of SMS and Q-f has a varied value of islanding detection time of 0.1 0.6 s. However, in Fig.5 the minimum islanding detection time of the hybrid method of SMS and Q-f is displayed.

    Fig.4 Comparison of islanding detection time of all of the reviewed methods in IEEE Std. 929-2000

    Fig.5 Comparison of islanding detection time of all of the reviewed methods in IEEE Std. 929-2000

  4. CONCLUSION

This paper reviews several improved active frequency drifts methods and compares their islanding detection time. Since islanding detection time is one of the main factors in determining an islanding detection method, this paper can be used to select a proper method to be applied in a PV inverter.

However, the other factors that can be used to evaluate the performance of an islanding detection method, such as, the non-detection zone value, the degradation in power system quality, etc must also be considered.

REFERENCES

  1. S. Chowdhury, S. Chowdhury, and P. Crossley, "Islanding protection of active distribution networks with renewable distributed generators: A comprehensive survey," Electric Power Systems Research, vol. 79, pp. 984-992, 2009.

  2. L. Yuan, X.-f. Zhang, J.-y. Zheng, J. Mei, and M. Gao, "An improved islanding detection method for grid-connected photovoltaic inverters," in Power Engineering Conference, 2007. IPEC 2007. International, 2007, pp. 538-543, 2007.

  3. W.-J. Chiang, H.-L. Jou, J.-C. Wu, K.-D. Wu, and Y.-T. Feng, "Active islanding detection method for the grid-connected photovoltaic generation system," Electric Power Systems Research, vol. 80, pp. 372-379, 2010.

  4. K. N. E. Ku Ahmad, J. Selvaraj, and N. A. Rahim, "A review of the islanding detection methods in grid-connected PV inverters," Renewable and Sustainable Energy Reviews, vol. 21, pp. 756-766, 2013.

  5. L. A. Lopes and Y. Zhang, "Islanding detection assessment of multi- inverter systems with active frequency drifting methods," Power Delivery, IEEE Transactions on, vol. 23, pp. 480-486, 2008.

  6. M. E. Ropp, M. Begovic, and A. Rohatgi, "Analysis and performance assessment of the active frequency drift method of islanding prevention," Energy Conversion, IEEE Transactions on, vol. 14, pp. 810-816, 1999.

  7. L. A. C. Lopes and S. Huili, "Performance assessment of active frequency drifting islanding detection methods," Energy Conversion, IEEE Transactions on, vol. 21, pp. 171-180, 2006.

  8. A. Yafaoui, W. Bin, and S. Kouro, "Improved Active Frequency Drift Anti-islanding Detection Method for Grid Connected Photovoltaic Systems," Power Electronics, IEEE Transactions on, vol. 27, pp. 2367-2375, 2012.

  9. G. Yu, "A novel active anti-islanding method for grid-connected photovoltaic inverter," Journal of Power Electronics, vol. 7, pp. 64- 71, 2007.

  10. Q. Ding, Z. Xu, and Y.-C. Li, "A modified Active Frequency Drift method for anti-islanding of grid-connected PV systems," in Electric Utility Deregulation and Restructuring and Power Technologies, 2008. DRPT 2008. Third International Conference on, 2008, pp. 2730-2733, 2008.

  11. R. Biying, T. Xiangqian, S. Xiangdong, and Z. Yanru, "Research on an improved active frequency drift method for the grid-connected anti-islanding detection," in Electrical Machines and Systems, 2008. ICEMS 2008. International Conference on, 2008, pp. 2657-2660, 2008.

  12. S. Mostafaei, S. Beheshti, B. Wu, D. Zhang, H. Wang, and H. Xing, "A novel hybrid active anti-islanding method for multi-converter fed distributed generation systems," in Industrial Technology (ICIT), 2013 IEEE International Conference on, 2013, pp. 654-660,2013.

  13. S. Akhlaghi, A. A. Ghadimi, and A. Akhlaghi, "A novel hybrid islanding detection method combination of SMS and Q-f for islanding detection of inverter- based DG," in Power and Energy Conference at Illinois (PECI), 2014, 2014, pp. 1-8,2014.

  14. Y. Byunggyu, J. Youngseok, S. Junghun, H. Hyemi, and Y. Gwonjong, "A Robust Anti-islanding Method for Grid-Connected Photovoltaic Inverter," in Photovoltaic Energy Conversion, Conference Record of the 2006 IEEE 4th World Conference on, 2006, pp. 2242-2245, 2006.

  15. N. Boonyapakdee, T. Sapaklom, and M. Konghirun, "An implementation of improved combine active islanding detection method based on frequency and phase perturbations," in Electrical Machines and Systems (ICEMS), 2013 International Conference on, 2013, pp. 208-213,2013.

Leave a Reply