Analysis of Counter Flow Induced Draft Cooling Tower using Taguchi Method
Shashank Tiwari 1 Student, SRCEM Banmore, M.P, India
Prof. Mahendra Agrawal2 Department of Mechanical Engineering, SRCEM Banmore, M.P, India
Abstract Cooling tower is a very important unit of most of plants. The capital and operating cost is often very high so we require optimizing the performance parameters of cooling tower. This work proposes the application of Taguchi method to achieve maximum cooling of outlet water of counter flow induced draft cooling tower. The experiments were planned based on Taguchis L9 orthogonal array. The trail was performed under different inlet conditions of flow rate of water, heat load, inlet water temperature and air flow rate. Signal-to-noise ratio (S/N) analysis, analysis of variance (ANOVA) and regression were carried out in order to determine the effects of process parameters on cooling tower outlet water temperature and to identify optimal factor settings of counter flow induced draft cooling tower performance with sufficient accuracy.
Keywords optimization, Cooling tower, performance, Taguchi Method
-
INTRODUCTION
Cooling towers are heat exchangers which are used to dissipate large heat loads to the atmosphere. It is equipment used to reduce the temperature of a water stream by extracting heat from water and emitting it to the atmosphere. In mechanical draft towers, air is moved by one or more mechanically driven fans to provide a constant air flow. The function of the fill is to increase the available surface in the tower, either by spreading the liquid over a greater surface or by retarding the rate of fall of the droplet surface through the apparatus. The fill should be strong, light and deterioration resistant. In this study, expanded wire mesh was used as the filling material. Its hardness, strength and composition guard against common cooling tower problems resulting from fire, chemical water treatment and deterioration. The operating theory of cooling tower was first suggested by Walker [1]. Simpson and Sherwood studied the performances of forced draft cooling towers with a 1.05 m packing height consisted of wood slats [3]. Kelly and Swenson studied the heat transfer and pressure drop characteristics of splash grid type cooling tower packing [4]. Barile et al studied the performances of a turbulent bed cooling tower. They correlated the tower characteristic with the water/air mass flow ratio [5].
There are several types of cooling towers. Wet cooling towers can work as natural or mechanical draft. Mechanical draft towers can be either forced or induced draft. Air and water flow can be countercurrent, crosscurrent or both. Therefore, some types of cooling towers are presented in details.
Mechanical draft cooling towers are predominant types of cooling towers and built in many places in the world. Therefore, the performance characteristic of a induced draft cooling tower is the subject of this paper.
The packing is the most crucial part of the cooling tower. The purpose of the packing material is to provide a large surface area for contact between air and water by distributing the water flow uniformly to enhance evaporation and heat transfer. As the water flows down the packing, it contacts air that is forced across the packing by a fan. A small percentage of the water evaporates by cooling the water. The relatively small portion of the water droplets in the air stream is called as "drift". The warm, moist air then passes through the drift eliminator and exits at the top of the tower, by carrying out some of the drifts out of the tower.
-
EXPERIMENTAL LAYOUT
The experimental study is carried out in M/s. Neelam College of Engineering & Technology, Agra (Uttar Pradesh). In this experiment counter flow induced draft cooling tower is used. As the literature and study of cooling tower in Neelam College of Engineering & Technology, Agra (Uttar Pradesh) suggested, the experimental setup is constructed for the cooling tower and the various factors and their levels are chosen, which are dependent on the following properties of the cooling tower: Heat Load, Range, Dry bulb temperature, Wet bulb temperature, Height of tower, No. of cell, Type of fill material, Air flow Rate, Inlet water temperature, Water flow rate.
Figure 2.1 Water Cooling Tower
Courtesy: Heat & Mass Transfer Lab of Neelam College of Engg. & Technology,
Agra (Uttar Pradesh)
-
TAGUCHI METHODOLOGY
In early 1950s, Dr. Genichi Taguchi, The Father of Quality Engineering, introduced the concept of off-line quality control techniques known as Taguchi parameter design. Offline quality control are those activities which were performed during the Product (or Process) Design and Development phase. The Taguchi method is statistical tool, adopted experimentally to investigate influence of cooling effectiveness by cooling parameters such as Water Flow, Air Flow and Inlet Water Temperature. The Taguchi process helps to select or to determine the optimum cooling conditions for various processes. Many researchers developed many mathematical models to optimize the cooling parameters to get highest cooling effectiveness by various processes. The variation in the water flow, air flow and other factors affecting cooling effectiveness.
Here the Taguchi design of experiments is used to optimize the cooling parameters.
-
Signal to Noise Ratios (S/N Ratios)
Taguchi recommends the use of the criterion he calls, Signal to noise ratio as performance statistic. The change in quality characteristic of a product under investigations in response to factor induced in the experimental design is the signal of the desired effect. The effect of external affairs (Uncontrollable factors) on the outcome of the quality characteristic under test is termed the noise.
From the quality point of view, there are three possible categories of quality characteristic. They are:
-
Smaller the better.
-
Nominal is the best.
-
Larger is better.
-
-
PROCEDURE AND STEPS OF TAGUCHI PARAMETER DESIGN
Select the quality characteristic Select the Control factors & Noise factors
Select Appropriate Orthogonal Array
Conduct the Experiments Accordingly
Analyze results; Determine optimum Factor-Level combination
Predict the Optimum performance With the optimum Factor-Level combination
Confirmation of Experimental Design Comparison of Results by Regression Modelling
Figure 3.1 Procedure & Steps of Taguchi Parameter Design
3.3. Selection of Orthogonal Array
There are 9 basic types of three level arrays from standard Orthogonal Arrays (OA) from the Genichi Taguchi parameter design (Genichi Taguchi and Yu-in Wu, Offline Quality control, 1979). An L9 Orthogonal Array is selected for this study. The layout of this L9 OA is as mentioned in Table 3.1.
Experiment
P1
P2
P3
P4
1
1
1
1
1
2
1
2
2
2
3
1
3
3
3
4
2
1
2
3
5
2
2
3
1
6
2
3
1
2
7
3
1
3
2
8
3
2
1
3
9
3
3
2
1
Table 3.1 The Basic Taguchi L9 Orthogonal Array**
(** Appendix B, 2nd edition, 2005, Taguchi Techniques for Quality Engineering, Philip J Ross20, Tata McGraw-Hill Publishing Company limited)
The OA (Orthogonal Array) to be selected must satisfy the following conditions:
Since,
D.O.F. of O.A. selected ³ D.O.F. required.
The experiment under consideration has 6
D.O.F. and therefore requires an O.A with 9 or more D.O.F., Hence an O.A. with at least 9 experiments is to be selected to estimate the effect of each factor and the desired interaction.
3.4 Selection of factor levels
S.N.
Process
Parameter Design
Process Parameter
Levels
Low
Medium
High
1.
A
Water Flow
Rate (m3/hr)
0.50
1.0
1.5
2.
B
Heat Load
(kCal/hr)
300
350
400
3.
C
Inlet water
temp.(0C)
38
42
46
4.
D
Air flow rate
(m3/hr)
0.5
1.0
1.5
Table 3.2 Process Parameters and their Levels
-
-
STATISTICAL ANALYSIS
Statistical analyses (S/N ratio, regression) are carried out:
4.1. Signal to Noise Ratio or S/N Ratio
The response variable considered in this study is cooling Effectiveness, which is of larger the better kind. Therefore, signal to noise ratio is defined by
S/N RATIO (Hi) = -10 Log10 [(1/n) *_i (1/ Yi2)] — (i)
S.No.
Exp. No.
Outlet Water Temp. (°C)
( I )
Outlet Water Temp. (°C)
( II )
Mean Outlet Water Temp. (°C)
( I + II
)/2
S/N ratio (dB)
i
1
1
29.16
29.46
29.31
-29.34
2
2
32.46
33.12
32.79
-30.31
3
3
34.63
33.86
34.24
-30.69
4
4
31.60
31.31
31.45
-29.95
5
5
35.16
36.00
35.58
-31.20
6
6
30.21
31.58
30.89
-29.79
7
7
35.78
34.30
35.04
-30.89
8
8
30.48
31.26
30.87
-29.79
9
9
36.67
37.39
37.03
-31.37
Average of S/N Ratio = -30.34 dB
Table 4.1 Outlet Water temperature & S/N Ratio Summary Sheet
-
MODELLING OF PARAMETERS
To generalize the results, the Modelling of input parameters (Water Flow, Air Flow and Water Temperature) and output parameter (Cooling Effectiveness) is done using REGRESSION MODELLING and MATLAB Software R2008a.The Cooling Effectiveness is a function of Water Flow, Air Flow and Water temperature has been adopted.
Y=0.6922* (Water Flow Rate) 0.1444 * (Heat Load) 0.2147 * (Inlet Water Temp.) 0.8262* (Air flow rate) 0.3084 —– (ii)
-
DETERMINATION OF OPTIMAL FACTOR LEVELS
The values obtained from the response Table are plotted to visualize the effect of the three factors at three levels. From the Mean response graph, observational findings are illustrated as follows:
-
Level I for Water Flow Rate, A1 = 0.50 m3/hr indicated as the optimum situation in terms of Outlet Water Temperature values.
-
Level I for Heat Load, B1 = 300 kcal/hr indicated as the optimum situation in terms of Outlet Water Temperature values.
-
Level I for Inlet Water Temperature, C1 = 38 °C indicated as the optimum situation in terms of Outlet Water Temperature values.
-
Level III for Air flow rate, D3 = 1.5 °C indicated as the optimum situation in terms of Outlet Water
Temperature values.
Graph 6.1 Mean Response Graph for four Cooling Factors
-
COMPARISON OF RESULTS
The results obtained from the confirmation experiments are hereby compared by the predicted result of Taguchi Design experiment.
-
Actual Result
Mean of Response value (Outlet Water temperature) = 29.27 C
-
Predicted Result (By Taguchi Method)
Predicted mean = A1 + B1+ C1 + D3 3* Y
= 32.14 + 31.90 + 30.34 + 32.22 (3 * 33.06)
Predicted mean Breaking Strength = 27.40 C Variation % = + {(27.92 27.40) / 27.92} × 100
= 1.862 %
-
Predicted Result (By Mathematical Regression Modelling)
From the factor level combinations to validate the optimum cooling conditions (A1, B1, C1 and D3); the result is predicted by using the regression Modelling:
4
Average Outlet Water Temperature = Co (Flow Rate)C1 (Heat Load)C2 (Inlet Water temperature)C3 (Approach)C
Y=0.6922* (Flow Rate) 0.1444 * (Heat Load) 0.2147 * (Inlet Water Temp.) 0.8262* (Approach)-0.3084 —- (xi)
By putting the values of A1, B1, C1 and D3 in above equation (xi), we get
Mean Response value (Outlet Water temperature) is found to be;
Y=0.6922*(19.5) 0.1444 * (28.2) 0.2147 *(38.20) 0.8262*
(4.52)-0.3084 —-(xii)
Y= 27.73 C
% Variation = {(27.92-27.73)/27.92} * 100 = 0.680 %
The final comparison of the confirmation experiment for cooling effectiveness with the values obtained from Taguchi parametric design & Regression modelling is obtained in Table 8.1. The comparison is also shown in Graph 7.1 as given below.
Graph 7.1 Comparisons of Results for Lowest Outlet Water Temperature
-
-
CONCLUSIONS
-
The outcome of the calculations and formulation for the optimization by the methods i.e. Prediction by Taguchi Method and By MATLAB regression modelling. By using the optimum factor level combination suggested by Taguchi methodology the experiments are conducted and the results are summarized in the Table 8.1
parameters |
Prediction (Taguchi Method) |
Prediction (Regression Modelling) |
Actual Experiment al Values |
Level |
A1B1C1D3 |
A1B1C1D3 |
A1B1C1D3 |
Outlet Water Temperature (C) |
27.40 |
27.72 |
27.92 |
Table 8.1 Final Comparison of the Confirmation Experiment for Outlet Water Temperature
REFERENCES
-
1. Walker, W.H., Lewis, W.K., MCACADAMS, W.H., and Gilliland, E.R., Principle of chemical Engineering, 3rd ed. McGraw-Hill Inc, New York, 1923.
-
London, A.L., MASAON, W.E. and BOELTER, L.K., Performance characteristic of a mechanically induced draft, counter flow, packed cooling tower, ASME Trans.,1940, 62:41-50.
-
Simpson, W.M., Sherwood, T.K., Performance o small mechanical draft cooling towers, American Society of Refrigerating Engineering, 52, 1946, pp. 535543, pp. 574576.
-
Kelly, N.W., Swenson, L.K., Comparative performance of cooling tower packing Arrangements, Chemical Engineering Progress, pp .263268, 1956.
-
Barile, R.G., Dengler, J.L., Hertwig, T.A., Performance and design of a turbulent bed cooling tower, AICHE Symposium Series, pp. 154162, 1974.
-
6. Taguchi, G., On-Line Quality Control during Production. Japan Standard association, Tokyo, 1981.
-
Philip. J. P., Taguchi Techniques for quality engineering, McGraw-Hill Book Company, 1988.
-
Phadke, S.M., Quality Engineering Using Robust Design, Prentice Hall, Englewood Cliffs, New Jersey, 1989.
-
Taguchi, G., Elsayed, E.A., Hsiang, T., Quality Engineering in Production System, McGraw- Hill,New York,1989.
-
Stanley, D.O. and Unal, R., Application of Taguchi methods to dual mixture ration propulsion system optimization for SSTO Vehicles. 30th Aero Space Sciences meeting and exhibit, Jan. 6- 9, Reno, Nevada, 1992.
-
Nimr, Al., "Dynamic Thermal Behaviour of Counter Flow Cooling Towers that Contain Packing Material", Journal of Heat Transfer Engineering, Vol. 20, Issue 1, pp. 91-96, 1999.
-
Goshayshi, H.R., Missenden, J.F., The investigation of cooling tower packing in various Arrangements, Applied Thermal Engineering, .20(2000), pp. 6980, 2000.
-
Nicolo Belavendram, Quality by Design- Taguchi Technique for Industrial Experimentation, Prentice Hall, Great Britain, 2001.
-
Khan, J.R., and Zubair, S.M., An improved design and rating analyses of counter flow wet cooling towers, ASME Journal of Heat Transfer, 123(4):770778, 2001.
-
Stefanovic, V., ILIC, G., Vukic, M., Radojkovic, N., Vuckovic, G., and Zivkovic, P., 3D Model in simulation of heat and mass transfer processes in wet cooling towers, Scientific Journal Facta Universitatis, Series Mechanical Engineering, 8:10651081, 2001.
-
Sultan, G., I., Hamed, A., M., and Sultan, A., A., The effect of inlet parameters on the performance of packed tower- regenerator, Renewable Energy, 26:271283, 2002.
-
Khan, J.R., Yaqub, M., and Zubair, S.M., Performance characteristics of counter flow wet cooling towers, Energy Conversion and Management, 44:2073-91, 2003.
-
Khan, J.R., Qureshi, B., A., and Zubair, S.M., A comprehensive design and performance evaluation study of counter flow wet cooling towers, International Journal of Refrigeration, 27:914-923, 2004.
-
Fisenko, S., P., Brin, A., A.,and Petruchik, A., I., (2004), Evaporative cooling of water in a mechanical draft cooling tower, International Journal of Heat and Mass Transfer, 47:165-177.
-
Söylemez, M.S., On the optimum performance of forced draft counter flow cooling tower, Energy Conversion and Management, 45(2004),15-16, pp.2335-2341, 2004.
-
AL-WAKED, and R. BEHNIA, M., The effect of windbreak walls on the thermal performance natural draft dry cooling towers, Heat Transfer Engineering, 26(8):50-62, 2005.
-
Kaiser, A., S., Lucas, M., Viedma, A., and Zamora, B., Numerical model of evaporative cooling processes in a new type of cooling tower, International Journal of Heat and Mass Transfer, 48:986999, 2005.
-
Phillip J Ross, Taguchi Techniques for Quality Engineering Tata Mc-Graw Hill 2nd edition, 2005.
-
Elsarrag, E., Experimental study and predictions of an induced draft ceramic tile packing cooling tower, Energy Conversion and Management, 47:2034-2043, 2006.
-
Bagci, E., Aykut, S., A study of Taguchi optimization method for identifying optimum surface roughness in CNC face milling of cobalt-based alloy(satellite 6), International Journal of Advance Manufacturing Technology, 29 (2006), pp.940-947, 2006.
-
Jinkun, L., Inyoung, Y., Sooseoki, Y., Jae Su, K., Uncertainty analysis and ANOVA for the measurement reliability estimation of altitude engine test, Journal of mechanical science and technology, 21(2007), pp.664-671, 2007.
-
Avanish, K.D., Vinod, Y., Simultaneous optimization of multiple quality characteristics in laser beam cutting using Taguchi method, International Journal of Precision Engineering and Manufacturing, 8(2007), 4, pp.10-15, 2007.
-
Muangnoi, T., Asvapoositkul, W., and Wongwises, S., An exergy analysis on the performance of a counterflow wet cooling tower, Applied Thermal Engineering, 27:910-917, 2007.
-
Hosez, M., Ertunc, H., M., and Bulgurcu, H., Performance prediction of a cooling tower using artificial neural network, Energy Conversion and Management, 48:13491359, 2007.
-
Giorgia, F.C., José. L. P., Tah. W. S., José. M. P., A systemic approach for optimal cooling tower operation, Energy Conversion and Management, pp. 2200-2209, 2009.
-
Ramkumar, R., Ragupathy, A : Optimization of Cooling Tower Performance Analysis …THERMAL SCIENCE: Year 2013, Vol. 17, No. 2, pp. 457-470,2013.