Analysis of MPPT Control Scheme and Grid Fault Mitigation Strategy for Current Source Converter based Offshore Wind Farm

DOI : 10.17577/IJERTV4IS090531

Download Full-Text PDF Cite this Publication

Text Only Version

Analysis of MPPT Control Scheme and Grid Fault Mitigation Strategy for Current Source Converter based Offshore Wind Farm

R. Rajathy

Associate Professor

Department of Electrical and Electronics Engineering Pondicherry Engineering College

Puducherry 605014, India

Thasnimol C. M.

Department of Electrical and Electronics Engineering Pondicherry Engineering College

Puducherry 605014, India

Abstract- An interconnection scheme and maximum power point tracking algorithm for the current source converter (CSC) based offshore wind farm is presented in this paper. A fault mitigation strategy by utilizing the short circuit operating capability of CSC is also presented. Tip speed ratio control with speed control is used as MPPT technique. A three phase to ground fault, double line to ground fault and single line to ground fault are created very near to the grid connection point. The system is simulated using MATLAB/Simpower system toolbox with an inertia constant of 1s. It is found that the proposed fault mitigation strategy is more faster compared to other existing technique.

Index Terms: Current source converter, Maximum Power Point Tracking, Tip Speed Ratio control, faults.

  1. INTRODUCTION

    The utilization of wind energy has increased over the past few years. It is possible to use either doubly fed induction generator or permanent magnet synchronous generator for transforming wind energy into electrical energy. PMSG is preferable as the wind generator as it doesn't need gear box and excitation. Therefore, the wind turbine operation will be more reliable and maintenance will be less. The wind farms can be onshore or offshore. Nowadays the trend is towards offshore wind farms due to the unavailability of sufficient onshore sites. Also the wind availability will be steadier and heavier in offshore located wind farms. Therefore, the power output will be more from an offshore wind farm.

    There are two options for integrating an offshore wind farm to grid. Either we can go for HVAC or HVDC interconnection. As the power electronic technology is in the peak of its development, HVDC option has became more suitable and economical for integrating wind power to onshore grid. The HVDC link can be voltage source converter (VSC) based HVDC or CSC based HVDC.VSC HVDC will provide independent control of active and reactive power. But it require huge offshore substation. The step-up transformer and HVDC converters result in huge installation costs. Also the high dc-link voltage became a drawback for the VSC-HVDC converters.

    The above said disadvantages of VSC HVDC based wind farms can be overcome by using pulse width modulated CSC based HVDC.PWM CSC based offshore wind farms have independent control of active and reactive power, black start capability etc. Popat et.al proposes a cascaded connection of PWM CSC [4]. By cascading the CSC it is possible to eliminate the bulky HVDC converter and step up transformer. Therefor the offshore substation needed can be eliminated.

    Recently many articles presented the low voltage ride through techniques for VSC-HVDC base wind farms. C. Feltes et.al.[7] and Ramtharan et.al.[5] presented power set point adjustment method for active power reduction during grid faults. Akhamatov et.al.[6] and Ramtharan et.al.[8] presented an FRT method which utilizes a DC chopper and a dynamic resistor for dissipating the excess power as heat during fault conditions.

    The main challenge for CSC based offshore wind farm is the protection from fault .Since the dc link inductance of the CSC based offshore wind farm is small compared with VSC based wind farm whose dc link capacitance has a relatively larger value, the CSC based offshore wind farm requires a fast fault ride through strategy. Popat et.al. presented an FRT method which uses the zero switching state operation of the CSC-HVDC based wind energy system. [9].

  2. WIND FARM CONFIGURATION

    The wind farm is integrated to the grid by using PWM Current Source Converter (CSC) based HVDC. The CSCs are cascaded on both generator and grid side [2]. By the cascaded connection of CSC on the generator side, the high voltage required for HVDC transmission can be achieved, without a step up transformer. For the present study we are considering two wind generating units which are connected in cascaded. The output of the two grid side CSCs are integrated to the grid by using a three winding transformer. The advantage of using three winding transformer is that, the major current harmonics will get eliminated. The wind farm configuration is shown in fig.1.

    VW

    PMSG

    C

    CSR1 CSI1

    Ldc/2 Ldc/2

    C

    Gating

    HVDC CABLE

    Gating

    Grid

    CSR2 CSI2

    VW

    PMSG

    C

    C

    Fig. 4 Control scheme.

    Gating

    Gating

    Fig. 1 Wind farm Configuration.

    Figure 2 shows the topology for the current source rectifier which is used for the simulation. The input capacitance are

    meant for commutation and also for filtering purpose. FD is

    It will be easy to obtain the optimum rotational speed of the turbine corresponding to a given wind speed if we know the optimum Tip Speed ratio.

    The relation between them is given as:

    optvwind

    the freewheeling diode.

    CSR

    ref

    m _ opt

    R

    (1)

    FD

    The output of the speed controller will be the torque reference. From the torque reference we will get the quadrature axis component of generator current iqg. The direct axis component of generator current idg is fixed as zero.

    C

    C

    The PWM generator current can be obtained after

    C subtracting the capacitor current from the d and q axis component of generator current as given below.

    Fig. 2 Topology for current source rectifier.

  3. GENERATOR SIDE CONTROL SCHEME

    iwrd *

    igd *

    • icrd

    As the wind speed is varying widely it is very important to extract the maximum possible power from the wind corresponding to the available wind speed. There are mainly two types of Maximum Power Point Tracking (MPPT)

    iwrq* igq* icrq

    Where the capacitor current can be found as follows:

    (2)

    methods are available. Methods which needs wind speed measurement and methods which doesnt need wind speed measurement. Although the Anemo meters which is needed for wind speed measurement is expensive, MPPT with wind speed measurement will give faster control response. Therefore this method is preferable for large capacity

    icrd icrq

    gCrvgq

    gCrvgd

    (3)

    systems. A Maximum Power Point Tracking control which is based on Optimum Tip Speed ratio, with speed control is used in this study. The system configuration and control scheme of generator side converter control [3] are shown in figure 3 and 4.

    CSR CSI

  4. GRID SIDE CONTROL SCHEME

    It is assumed that the grid voltage vector is in line with the direct axis component of synchronous frame. Therefore the grid voltage will have only d axis component Vsd but the q axis component Vsq will be equal to zero

    CSR CSI

    PMSG

    C

    g

    Ls

    Ldc/2

    HVDC CABLE

    Ldc/2

    Rd Rd

    C

    Gating

    Gating

    Fig. 3 System configuration.

    Grid

    Ldc/2

    HVDC CABLE

    Ldc/2

    VW

    PMSG

    PLL

    C C

    g

    Gating

    Grid

    Where Rd is the damping resistor whose valu is normally chosen as 1.5 pu. The purpose of damping resistor is to damping out the resonant oscillations created by the commutation capacitance and PMSG inductance.

    Fig. 5 System configuration.

    Fig. 6: Control scheme.

    Therefore, it will be possible to achieve independent control of active and reactive power output to grid by regulating the current output to grid as given below.

    3

    vsdisd vsqisd

    3

    2

    2

    3

    vsqisd vsdisq

    3

    vs

    2

    2

    P

    system configuration and control scheme of the grid side converter control are shown in figure 5 and 6.

  5. FAULT RIDE THROUGH SCHEME

    Many nations enforce grid code specifications for FRT capabilities inorder to avoid disconnection of wind farm on the incidence of grid faults. The present study has been carried out based on E. ON grid code as shown in the figure 7 [1]. The curve shows that grid voltage drops to zero for 150 ms due to a short circuit fault and then recovers gradually back to its lower voltage level. The wind farms should remain in operation as long as voltage at the grid is above the solid line [1]

    o vsdisd

    Q

    O disq

    (4)

    The main objective of grid side control scheme is to regulate dc link current. The dc link current error will be minimised by a current PI controller. The output of current controller will give the d axis component of grid current ids. The dc link current reference can be found by the following formula.

    i * 2

    2 2Pdc

    2Q * 2

    2

    o

    2

    Fig. 7 Grid fault ride-through requirement in E.ON grid codes.

    dc

    (1 s LSCi)

    3v

    sCivsd (1 s LSCi)

    sd

    Where Pdc=Vdci*idc

    vdci 1.5VLLmi cos(i)

    3vsd

    (5)

    (6)

    During grid faults the grid side inverter loses its control

    ability. The power flow will become unbalanced. Therefore the dc link current will (rise above the normal value. This will lead to the de5struction of the converter units. To avoid the quick rise of d)c link current, the power output to the dc link

    from the wind generation system must be reduced.

    When the dc link current rises above the normal operating range, the generator side control will be switched to fault ride through scheme. In this control scheme CSCs are

    The other control objective of the grid side controller is the reactive power regulation. The reactive power error will be minimised by using reactive power controller, which is a PI controller. The output of the reactive power controller will give the q axis component of grid current iqs.

    The PWM grid current can be obtained from the d and q

    axis component of grid current after subtracting the the d and q axis component of capacitor current a follows.

    fired by its zero switching states. In zero switching state the two switches in the same leg will conduct together, there by act as a short circuit across the wind turbine generator unit, as shown in figure8.As a result the power output of that permanent magnet synchronous generator will be dropped to zero, thereby protecting the wind turbine generator unit from the faulty grid.

    iwid *

    iwiq*

    isd * icid isd * sCivciq

    isq* iciq isq* sCivcid

    (7)

    Where the capacitor voltage can be expressed as:

    vcid Rsisd sLsisq vsd vciq Rsisq sLsisd

    (8)

    Where Ls is the grid-side line inductance, while Rs represents the transformer and line losses together. The

    Fig. 8 Zero switching state operation of CSC.

  6. SYSTEM PERFORMANCE INVESTIGATION BY SIMULATION

    In order to investigate the performance of the wind generation system under the control schemes discussed above, two cascaded wind turbine generator units are considered. Direct driven wind turbine is considered for the study. A variable speed permanent magnet synchronous generator with multiple poles is considered as the wind generator. The simulation is performed using Matlab/Simulink with the SimPowerSystem toolbox. The main simulation parameters are listed in Table1. For the present study, the turbine-generator inertia constant is assumed to be 1 sec. Both generator and grid side converter are fired by space vector modulation (SVM) technique. Switching frequency is assumed to be 540 Hz. The performance of the system under steady state is given in fg.9. In order to verify the dynamic behaviour of the system a step down change and step up change of wind speed is applied to the system. The results are shown in fig 10 and 11.

    1. Generator and DC Link Response Under Steady State

      It is found that under rated wind speed of 12m/s the rms generator voltage is 3200V,rms current is 300A and the DC link current is 500A as shown in figure 9.

      Fig. 9 PMSG voltage, current, rms voltage, rms current output power

      ,Electromagnetic torque and DC link current response at wind speed of 12m/s..

    2. Generator and Dc Link Response to a Step Change in Wind Speed from 12m/s to 8 m/s

      Corresponding to a step change in wind speed from 12m/s to 8m/s the dc link current will change from 500A to 200 A. figure 10 shows the corresponding waveforms.

      Fig. 10 PMSG voltage, current, rms voltage, rms current output power

      ,Electro magnetic torque and DC link current response to a step change in wind speed from 12m/s to 8m/s

    3. Generator and DC Link Response to a Step Change in Wind Speed from 8m/s to 11m/s

      It is seen that when the wind speed changes from 8m/s to

      11 m/s the dc link current will change from 200A to 400A.Figure 11 shows the corresponding waveforms.

      Fig. 11 PMSG voltage, current, rms voltage, rms current, output power , Electro magnetic torque and DC link current response to a step change in wind speed from 8m/s to 11m/s.

    4. Torque and speed response to a step change in wind

      speed

      Figure 12 shows the torque and speed response for a step change in wind speed from 12m/s to 7m/s. When the wind speed change from 12m/s to 7m/s, the generator speed is changed from 16rad/s to 10rad/s.

      Fig.12 Mechanical torque, Electromagnetic torque and generator speed response to a step change in wind speed.

    5. Power output corresponding to different wind speed

      Figure 13 shows the active and reactive power output of wind farm at different wind speed

      Fig. 13. Active and Reactive power output corresponding to different wind speed

    6. Verification Of Mppt Control Scheme

      Tip speed ratio (TSR) control with speed control is used in this study. The TSR control will give the optimum rotor speed which will give the maximum power corresponding to each wind speed. The speed error will be processed by a PI controller. The power and rotor speed for different wind speed are given in table1. Figure 14 shows the wind turbine power characteristics that is wind power versus generator speed for different wind speed. The maximum power versus wind speed curve is give in figure 15.

      Fig.14 wind turbine power characteristics Table.1Maximum power and optimum rotor speed for different wind speed

      Wind speed(m/ s)

      Pmax (Theoretica l)

      Pmax(Actua l)

      Optimum Rotor speed(theoretica l)

      Optimum Rotor speed(Actua l)

      16

      1.642

      1.7

      14.83

      15

      15

      1.672

      1.62

      15

      16

      14

      1.482

      1.6

      14.51

      15.3

      13

      1.531

      1.56

      14.93

      15.5/p>

      12

      1.501

      1.5

      14.89

      15

      11

      1.419

      1.17

      14

      14

      10

      1.221

      .89

      12.84

      12.5

      9

      1.003

      .66

      11.32

      11

      8

      .7544

      .47

      10.8

      10

      7

      .506

      .33

      8.68

      8.5

      6

      .31

      .22

      7.466

      7.5

      5

      .1835

      .13

      6.345

      6

  7. ANALYSIS OF GROUND FAULTS

    The system performances with the discussed fault ride through scheme against three phase fault, double line to ground fault, and single line to ground fault are investigated by simulation .The ground faults are assumed at the grid connection point of the wind farm. The fault lasts for 120 ms from 3.6s to 3.72s as shown in Fig 16 to 18. On the occurrence of the fault, due to the power difference between the generator side and grid side converter the dc link current will rise to a high value. Whenever the dc link current rise above the normal operating range the generator side converter control will switch to the fault ride through mode. The generator side converter will be operating in the zero switching state. dc link current will bypass through shorted leg of the CSC. Also the generator output power will drop to zero, and the wind turbine generator unit will get isolated from the grid. It is seen that in all the faults the under this protection scheme the dc link current under fault conditions is limited to 2pu.When the dclink current rises above this value protection system will be active and the wind farms will be isolated.

    1. Double Line To Ground Fault

      Fig. 16 Grid voltage, grid current, dc link current, by pass signals for CSC and generator output power during double line to ground fault.

    2. Single Line To Ground Fault

      Fig.15 maximum power versus wind speed

      Fig. 17 grid voltage, grid current, dc link current, bypass signals for CSC and generator output power during singe line to ground fault.

    3. Three Phase to Ground Fault

    Fig. 18 grid voltage, grid current, dc link current, bypass signals for CSC and generator output power during three phase to ground fault.

  8. CONCLUSION

In this paper the application of CSC for the offshore wind farm is presented. The generator and grid side converter control schemes are discussed and verified through simulation. Due to the low dc link inductance CSC based wind farms requires a fault ride through scheme which must be faster than that is required for VSC based wind energy conversion system. A fault ride through scheme, which is developed based on the zero switching state operation of the CSC is discussed and verified through simulation.

System parameters

Power

1.56MW

Voltage

3200V

Current

300A

Frequency

60Hz

Generator parameters

Frequency

60Hz

Synchronous inductance

0.4pu

Stator resistance

0.01pu

Number of poles

32

Converter parameters

Generator side capacitance

0.3pu

Grid side capacitance

0.5pu

Grid side line inductance

0.1pu

DC link inductance

1pu

Device switching frequency

540Hz

TABLE 2 SIMULATION PARAMETERS

REFERENCES

[1]. E. ON Netz Gmb, Grid Code: High and Extra High Voltage, H Tech. Rep., 2006.

[2]. M. Popat, B. Wu, and N. Zargari, A novel decoupled interconnecting method for current-source converter-based offshore wind farm, IEEE Trans. Power Electron., vol. 27, no. 10, pp. 42244233, Oct. 2012.

[3]. M. Popat, B. Wu, F. Liu, and N. Zargari, Coordinated control of cascaded current source converter based offshore wind farms, IEEE Trans. Sustain. Energy, vol. 3, no. 3, pp. 557565, Jul. 2012.

[4]. E. Veilleux, Interconnection of Direct-Drive Wind Turbines Using a Series Connected DC Grid, M.S. Thesis, Univ. of Toronto, Toronto, Canada, 2009.

[5]. G. Ramtharan, N. Jenkins and O. AnayaLara, "Modelling and control of synchronous generators for widerange variablespeed wind turbines," Wind Energy, vol. 10, pp. 231-246, 2007

[6]. V. Akhmatova, A. H. Nielsenb, J. K. Pedersenc and O. Nymannc, "Variable-speed wind turbines with multi-pole synchronous permanent magnet generators. Part I: Modelling in dynamic simulation tools." Wind Eng, vol. 27, pp. 531-548, 2003

[7]. C. Feltes, H. Wrede, F. W. Koch and I. Erlich, "Enhanced Fault Ride-Through Method for Wind Farms Connected to the Grid Through VSC-Based HVDC Transmission," Power Systems,

IEEE Transactions on, vol. 24, pp. 1537-1546, 2009

[8]. G. Ramtharan, A. Arulampalam, J. Ekanayake, F. Hughes and N. Jenkins, "Fault ride through of fully rated converter wind turbines with AC and DC transmission," Renewable Power Generation,

IET, vol. 3, pp. 426-438, 2009

[9]. Miteshkumar Popat, Bin Wu and Navid R. Zargari, Fault Ride- Through Capability of Cascaded Current-Source Converter-Based Offshore Wind Farm, IEEE Transactions on Sustainable Energy, Vol.4, No.2, April 2013, pp 314-323.

[10]. A Reliability Model for a Doubly Fed Induction Generator Based Wind Turbine Unit Considering Auxiliary Components, Mahdi Maaref *, Hasan Monsef , Maziar Karimi, Indian Journal of Science and Technology, Volume 6, Issue 9, September 2013,

5281-5288

Leave a Reply