Analytical Study on Effect of Dimensions of Tapered Cover Plates and vertical stiffeners on Replaceable I-Beam to CHS Column Joint
Lijin M Varughese PG Scholar
Dept. of Civil Engineering Saintgits College of Engineering Kottayam, India
Er.Alice Johny Assistant professor Dept. of Civil Engineering
Saintgits College of Engineering Kottayam, India
AbstractThe moment resisting frames with welded beam to column connections are vulnerable to fragile failure and normally explain giant residual deformation followed by earthquakes. Because of this, a new steel structural system with good energy dissipation is required to deal with such sudden falls. Modern researches on I beam to Circular Hollow Section(CHS) column joints with exterior diaphragms and replaceable links also established their efficiency in seismic application. This research investigates the influence of dimensions of tapered cover plates(TCPs) and vertical stiffeners(VSs) on connection behavior using ANSYS software.
Keywords Tapered cover plates, vertical stiffeners, CHS column.
-
INTRODUCTION
Moment resisting frames with welded steel beam column joints are vulnerable to fragile crack and normally show large residual deformation after earthquakes. Therefore, a new steel structural system with good energy dissipation is required to deal with such sudden falls. Modern researches on I beam to Circular Hollow Section (CHS) column joints with exterior diaphragms and replaceable links also established their efficiency in seismic application. To promote the performance, researchers have used smart materials in the connection configurations.
Structures with circular sections acquire many structural and architectural advantages due to their closed geometry. They require less protection against corrosion than comparable structures made with open sections. An extra advantage is that, the internal empty space can be used to provide aeration facilities or to pack with concrete. Circular columns packed with concrete increases compressive strength and shows improved seismic resistance. Circular hollow sections are very effective when considering design resistances along with torsional resistance and bending stiffness. On the whole, even though circular columns are more costly than open sections, it offers enhanced strength-to-weight proportion that provides more cost-effective moment resistant frames with suitable design.
For those joints among CHS column and I beam, the joints with exterior diaphragm or internal diaphragm is frequently applied. The results shows that the joint with external diaphragm is more reasonable, since the diffusion of force is
clear, stress circulation of joint region is uniform and it is easy to be constructed. It has relatively large stiffness, good plasticity, and high bearing capacity. A number of researches were performed in past 20 years on exterior diaphragm joints to circular columns.
Two major problems of the joints among CHS column and I beam with exterior diaphragm are, (i) deformation in the web section, (ii) strain attentiveness and out of plane deterioration in the diaphragm plates(DPs) leads to rupture of plates, welds and columns. Moving the end of beam away from the face of the CHS column face and designing the dimensions of external diaphragm for the complete strength of beam flanges are suggested for designing connections that will offer required homogeneous stress distribution around and into the column, which will improve the two deficiencies mentioned above.
The purpose of this study is to investigate the cyclic response of an exterior diaphragm joint among a steel I beam and a CHS column. The joint consist of 2 DPs, welded to the perimeter of CHS column and bolted to the flanges of I beam with two tapered cover plates(TCPs). A web stub (WS) is welded to the face of the column and bolted to the web of I beam. TCPs were incorporated in the joint to act as disposable or replaceable sacrificial components that disperse major part of energy while rest of the joint parts remains elastic to minimize the post-seismic repair.
Chunyan Quan et al. (2017) conducted a research on replaceable connection among CHS column and I beam under cyclic loads. The pretension force on the bolts of TCPs has large effects on connection behavior. In general, reduced preloading force cause reduction in load bearing capacity, but also reduce stress demands on DPs and beam flanges. Higher energy dissipation and rotation capacity is by the action of slippage of bolts
Majd Khador et al. (2016) studied the cyclic response of exterior diaphragm connections to CHS column using replaceable links. Parametric investigation on influence of the TCP steel grade shows that grade S355 amplified the joint moment capacity compared to grade S235. On the other hand, this was accompanied by an enhancement of force demand in the beam and DP and a diminution in the maximum rotation of the plastic hinge region. Use of the weaker steel grade S235 is more favorable option than S355 grade.
-
ANALYTICAL INVESTIGATION
A. Finite element modelling
Fig 1. Joint before assembly
The connection shown in Fig 1 consists of 2 DPs, which have width of 90 mm, which is shop welded to the external circumference of a 2m CHS 244.5X10 column under satisfactory quality control, and connected to the flanges of a 2 m UKB 203X133X30 beam with 2 TCPs using 24 M22 bolts of Class10.9. A web stub plate is welded to the outer surface of the CHS column and attached to the I-beam web using 3
The loading procedure was based on the ANSI/AISC 341- 10 (2010) specifications for qualifying cyclic loading of beam to column moment joints. The entire loading procedure was separated into a number of steps. Gravitational force of joint components and Pretensioning force of the bolts were applied in 4 steps, 1/4 in each step, inorder to keep away from numerical abortion due to rapid change in forces. Vertical displacement at the end of beam was applied in the final step.
C. Bolts preloading force
Bolt preloading force (Fp,Cd) acting on them was designed according to the specifications of Eurocode 3, BS EN 1993:1:8 ,2005 for slip-resistant connections:
F= 0.7 × fub × As
Where, fub is ultimate strength of the bolts; As is the tensile stress area of a bolt.
-
RESULTS AND DISCUSSIONS
The cyclic analysis of models were analyzed in ANSYS Workbench. Results obtained from analysis were tabulated and shown in the table below. Stress values of the joint parts of 7 models are shown in Table1.
Table 1.Stress on joint components
SPECIMEN
STRESS(N/mm2)
I-Beam
TCP
DP
CHS
Column
Web stub
TCP12-VS40X12
518
356
426
278
414
TCP12-VS30X12
483
385
364
276
370
TCP12-VS30X8
468
384
347
273
382
TCP12-VS30X6
435
410
349
275
372
TCP12-No VS
411
387
376
303
333
TCP15-No VS
425
345
409
304
337
CP20-No VS
475
371
479
325
364
M16 bolts of Class10.9 to transmit the shear forces. The grade
of steel joint parts was S355 in all models. The only exemption was TCP, which is with a steel grade of S235. Seven models are taken for study by varying the dimensions of TCPs and VSs.
Symmetric model is used in order to save analyzing time.
Fig 2. Symmetric model
-
Loading procedure
Cyclic displacement up to 80mm is provided in 30 cycles
The specimen name TCP12-VS40X12 denotes the thickness of TCP and dimensions of VS.
Cycle number
Vertical displacement da (mm)
1 to 6
± 7.5
7 to12
± 10
13 to 18
± 15
19 to 22
± 20
23 to 24
± 30
25 to 26
± 40
27 to 28
± 60
29 to 30
± 80
Fig 3. Mises stress contours of TCP12-VS40X12
Fig 4. Mises stress contours of TCP12-No VS
The hysteric response of the joint with varying dimensions of TCPs and VSs are shown in Fig 5. Hysteresis curve is drawn between normalized moment and rotation. Moment reaction of the connection is normalized with plastic moment capacity of I beam.
TCP12-VS40X12 & TCP12-VS30X12
TCP12-VS30X8 & TCP12-VS30X6
TCP12-No VS & TCP15-No VS
TCP20-No VS
Fig 5. Normalized moment- rotation curves
-
-
CONCLUSION
In this study all the parameters are made constant except the dimensions of tapered cover plates and vertical stiffeners. Steel grades of both TCP and VS are S235, while steel grade of all the other joint components are S355.
From the obtained information it is obvious that the diminution of cross sectional area of vertical stiffener decreases the stress demands on the joint components and from the normalized moment rotation curves we can found that the diminution in stiffness of joint improves the hysteric behavior of joint. Increase in thickness of TCP without VS, increases the stress demands and decreases the rotation capacity.
In the model without vertical stiffener (TCP12-No VS) all the joint components except the sacrificial element TCP are within the elastic limit. Rotational capacity of this model is greater than the models with vertical stiffeners. This increases the energy dissipation capacity of the joint.
REFERENCES
-
Chunyan Quan et al.(2017),FE modelling of replaceable I-beam-to- CHS column joints under cyclic loads,Journal of Constructional Steel Researcp38, 221-234.
-
M. Khador, T. Chan,(2016),Cyclic behaviour of external diaphragm joint to CHS column with built-in replaceable links,Steel Construction. 9 (4),331- 338..
-
W. Wang, T.M. Chan, H. Shao (2015) Seismic performance of beam column joints with SMA tendons strengthened by steel angles,J. Constr. Steel Res. 109, 61-71.
-
W. Wang et al.(2011), Bidirectional seismic performance of steel beam to circular tubular column connections with outer diaphragm,
Earthq. Eng.Struct.Dyn. 40 (10) 1063-1081
-
A.Y. Elghazouli et al.(2009), Experimental monotonic and cyclic behaviour of blind-bolted angle connections, Eng. Struct. 31 (11) 2540-2553.
-
X. Li, Y. Xiao, Y.T. Wu,(2009) Seismic behavior of exterior connections with steel beams bolted to CFT columns, J. Constr. Steel Res. 65 (7) 1438-1446.
-
Chunyan quan et.al,(2016)Cyclic behavior of stiffened joints between concrete-filledsteel tubular column and steel beam with narrow outerdiaphragm and partial joint penetration welds ,Front. Struct. Civ. Eng.
-
Eurocode 3 Design of Steel Structures: Part 1-8,Design of Joints,EN 1993-1-8, 2005.
-
ANSI/AISC 340-10 Seismic Provisions for Structural Steel Buildings, American Institution of Steel Construction 2010