- Open Access
- Total Downloads : 809
- Authors : S. Sakthivel, P. Mathiazhagi, T. K. Archana
- Paper ID : IJERTV2IS3394
- Volume & Issue : Volume 02, Issue 03 (March 2013)
- Published (First Online): 18-03-2013
- ISSN (Online) : 2278-0181
- Publisher Name : IJERT
- License: This work is licensed under a Creative Commons Attribution 4.0 International License
ATC Enhancement Through Optimal Location and Sizing of FACTS Devices Using BB-BC Algorithm
S. Sakthivel
Associate Professor
Department of Electrical and Electronics Engineering
V.R.S. College of Engineering and Technology Villupuram, Tamil Nadu, India.
P. Mathiazhagi
UG Scholar
Department of Electrical and Electronics Engineering
V.R.S. College of Engineering and Technology Villupuram, Tamil Nadu, India.
T. K. Archana
UG Scholar
Department of Electrical and Electronics Engineering
V.R.S. College of Engineering and Technology Villupuram, Tamil Nadu, India.
ABSTRACT
In an open power market, sufficient transmission capability should be made available for satisfying the demand of increasing power transactions. Certain methodologies are to be developed to enhance the power handling capacity of existing transmission lines. In this work, power flow pattern is changed by transformer tap settings and reactance of TCSCs to enhance ATC of a system. Flexible AC transmission System (FACTS) devices are inserted in electrical systems to enhance power transfer capability. Thyristor controlled series compensator (TCSC) is highly helpful in enhancing the power carrying capacity of a line by adjusting its reactance. The location and sizing of TCSC is the major issue in optimizing the benefits. The recently developed metaheuristic algorithm of Big Bang-Big Crunch (BB-BC) algorithm is proposed for optimizing the location and size of TCSC devices. The algorithm is with less number of parameters and can be easily implemented for practical applications. The proposed algorithm is tested on the standard IEEE 30 bus system and results obtained are really satisfactory.
-
INTRODUCTION
Power system networks across the world are undergoing tremendous changes to meet the growing power demand and to improve the quality of power supply. Deregulation of electric power system networks is one such changes and it ensures cheap power to the consumers. Deregulation poses several challenges that are to be solved. Insufficient transmission capability is the major challenge to be addressed [1]. Usually, there is mismatch between construction of power plants and transmission systems [2]. This is due to several socio-
economic reasons. Sufficient transmission capability may be provided by enhancing the capability of existing transmission lines.
One of the possible ways to improve the capability of a transmission line is to use FACTS devices [3]-[4]. The insertion of FACTS devices extends the possibility that current through a line can be controlled at a reasonable cost, enabling large potential of increasing the capacity of existing lines, and use of one of the FACTS devices to enable corresponding power to flow through such lines under normal and contingency conditions. Several studies [5] have found that FACTS technology not only provides solutions for efficiently increasing transmission system capacity but also increases ATC, relieve congestion, improve reliability and enhances operation and control.
The benefits of FACTS devices are maximized by optimizing their location and parameters [6]. However, it is hard to determine the optimal location and sizing of FACTS devices. Therefore a suitable optimizing technique is necessary. Recently several optimization algorithms are proposed and exploited for many power system operation optimization [7]-[8].
A method based on continuation power flow [9] incorporating limits of reactive power flows, voltage limits as well as voltage collapse and line flow limits is described. However, with this method the computational effort and time requirement are large. For very large systems, the method may be quite cumbersome. The localized linearity of the system is assumed and additional load required to hit the different limits are separately calculated and the minimum of all these is taken as ATC.
The task of calculating ATC is one of the main concerns in power system operation and planning. ATC is determined as a function of increase in power transfers between different systems through prescribed interfaces. Methods available for ATC calculations include Repeated Power Flow (RPF) and Continuation Power Flow (CPF) based methods [10]-[11], Sensitivity based methods [12] and Optimal Power Flow (OPF) based methods [13].
ATC can also be calculated by using the power flow distribution factors. The distribution factors may be calculated using AC power flow or DC power flow solutions. The DC power transfer distribution factors (DCPTDFs) are derived based on DC load flow assumptions and hence are provide less accurate results [14]. The AC power transfer distribution factors [15]-
[16] (ACPTDFs) are more accurate and provides acceptable ATC values.FACTS devices are highly useful in enhancing ATC of a power system. Series connected FACTS devices are more suitable than shunt connected FACTS devices for ATC enhancement. TCSC is a series connected FACTS device which is used in this work ATC enhancement. Insertion of TCSC can increase ATC when it is located in any line. But the benefits of TCSC can be maximized by optimizing its location and size [17]-[18]. The BB- BC algorithm is exploited in this work for the optimization of TCSC parameters.
-
MODELLING OF TCSC DEVICE
TCSC is a low cost but rapid response FACTS controller and is a series connected FACTS device that decreases or increases the effective line reactance, by adding a capacitive or inductive reactance correspondingly. TCSC is highly suitable for line flow control by changing the transfer reactance of the line. The TCSC is modelled as a variable reactance, where the equivalent reactance of line Xij is defined as:
= + 1
where, Xline is the transmission line reactance before insertion of TCSC, and XTCSC is the TCSC reactance. The degree of the applied compensation of the TCSC usually varies between 20% inductive and 80% capacitive to avoid over compensation (0.8XLine XTCSC 0.2XLine ) . The load flow studies model of a TCSC is shown in figure 1.
Bus i
XL
XTCSC
Bus j
Bi Bj
Fig 1. Model of TCSC
The addition of TCSC changes only the elements corresponding to the buses i and j of the admittance matrix and therefore modelling of TCSC for load flow studies is simple.
-
ATC ENHANCEMENT PROBLEM STATEMENT
-
ATC
ATC is the transmission capability available for further transactions in a deregulated power market. ATC is a measure of the transfer capability remaining in the physical transmission network for further commercial activity over and above the already committed uses. It can be expressed as follows:
ATC = TTC Existing Transmission Commitments 2
Where, Total Transfer Capability (TTC) is defined as the amount of electric power that can be transferred over the interconnected transmission network or particular path or interface in a reliable manner while meeting all of a specific set of defined pre and post contingency conditions. ATC at the base case, between bus m and bus n using line flow limit (thermal limit) criterion is mathematically formulated using ACPTDF as given in the below equation:
= min , , 3
Where Tij, mn denotes the transfer limit values for each line in the system. It is given by the following equation:
0
; , . > 0
, =
,
; , = 0
4
0
; , < 0
,
Where the following holds true:Pijmax is the MW power limit of a line between bus i and j. Pijo is the base case power flow in line between bus i and j.NL is the total number of lines. ACPTDFij,mn is the power transfer distribution factor for the line between bus i and j when a transaction is taking place between bus m and n. ACPTDF as given in equation (3) is operating point dependent and was computed using Jacobian inverse. ACPTDFs remain fairly
constant for reasonable variations in power injections.
-
ACPTDF Formulation
ACPTDF is based on the results of AC power flow solutions. ACPTDF values provide a linearized approximation of how the flow on the transmission lines and interfaces change in response to transaction between the seller and the buyer. Considering a bilateral transaction tk between a seller bus m and buyer bus n, line l connected between bus i bus j carries a part of the transacted power. For a change in real power in the transaction between the above buyer and seller by tk MW, if the change in a transmission line quantity ql is q1 , power transfer distribution factors can be defined as follows:
,
=
5
-
Objective function
The objective of this work is to increase the total transfer capability a power system for realizing more number of power transactions by changing the power flow pattern.
Equality constraints
Power balance equations
cos = 0 6
=1
sin = 0
=1
7
Where, and are the real power generation and load at bus i; and are the reactive power generation and load at bus i.
Inequality constraints
Line real power flow limit
, 8
TCSC reactance limit
max 9
Bus voltage magnitude limit
10
-
-
BB BC ALGORITHM
-
Overview
A new nature inspired optimization technique which has low computational time and high convergence speed called BB-BC is introduced recently [17]-[18]. It has two phases,
1. Big bang phase and 2. Big crunch phase.
In Big Bang phase, candidate solutions are randomly distributed over the search space and in the Big Crunch phase, randomly distributed particles are drawn into an orderly fashion.
The Big Bang-Big Crunch optimization method generates random points in the Big Bang phase and shrinks these points to a single point in the Big Crunch phase after a number sequential Big Bangs and Big Crunches.
The Big Crunch phase has a convergence operator that has many inputs but only one output, which is named as the centre of mass, since the only output has been derived by calculating the centre of mass. The point representing the centre of mass is denoted by Xc and is calculated according to the following equation.
1
= =1
1
=1
11
Where Xi is the ith candidate in an D-dimensional search space, f(Xi) is a fitness function value of this point, NP is the population size in Big Bang phase.
After the Big Crunch phase, the algorithm creates new candidates to be used as the Big Bang phase of the next iteration step. This can be done in various ways, the simplest one being identifying the best candidate in the population. In this work, the new candidates are generated around the centre of mass and knowledge of centre of mass of previous iteration is used for better convergence. The parameters to be supplied to normal random point generator are the centre of mass of the previous step and the standard deviation. The deviation term can be fixed, but decreasing its value along with the elapsed iterations produces better results.
= +
12
Where r is a normal random number, is a parameter limiting the size of the search space, Xmax and Xmin are the upper and lower limits, and t is the iteration step. Since normally distributed numbers can be exceeding ±1, it is necessary to limit the population to the prescribed search space boundaries. This narrowing down restricts the candidate solutions into the search space boundaries.
-
BB-BC applied to ATC maximization:
Big Bang Big Crunch algorithm involves the steps shown below in reactive power flow control
Step 1: Form an initial generation of NP candidates in a random manner respecting the limits of search space. Each candidate is a vector of all control variables, i.e. [Tk, XTCSC]. There are 4 Tks and 2 XTCSC in the IEEE-30 system and hence a candidate is a vector of size 1×6.
Step 2: Calculate the fitness function values of all candidate solution by running the NR load flow. The control variable values taken by different candidates are incorporated in the system data and load flow is run. The total line loss corresponding to different candidates are calculated.
Step 3: Determine the centre of mass which has global best fitness using equation (11). The candidates are arranged in the ascending order their fitness (fitness) and the first candidate will be the candidate with best fitness (minimum loss).
Step 4: Generate new candidates around the centre of mass by adding/subtracting a normal random number according to equation (12). It should be ensured that the control variables are within their limits otherwise adjust the values of r and .
Step 5: Repeat steps 2-4 until stopping criteria has not been achieved.
Start
Initialize the population within the limits
Initialize the population within the limits
Calculate the fitness of each agent
Calculate the fitness of each agent
Gen=Gen+1
Gen=Gen+1
Identify the centre of mass
Form the new agents around the centre of mass
Form the new agents around the centre of mass
Run NR load flow and calculate the fitness
Run NR load flow and calculate the fitness
Is gen<= max gen?
Print the global best
Print the global best
Stop
Figure 2. Flow chart for BB-BC algorithm
-
-
RESULTS AND DISCUSSIONS
The proposed BB-BC algorithm based ATC enhancement problem is tested on the standard IEEE-30 bus test system [19]. System data are on 100MVA base. Bus 1 is taken as the reference bus. The base load condition is considered. The algorithm is coded in MATLAB
7.6 language tool. The test system has the following parameters.
Table 1. System parameters
Sl.No
Variables
Quantity
1
Buses
30
2
Branches
41
3
Generators
6
4
Shunt capacitors
2
5
Tap-Changing transformers
4
The system has 4 transmission lines with tap changer transformers. For insertion of TCSC only the lines without tap changer transformer are taken as candidate locations. ATC enhancement is done by adjusting tap positions of the 4 transformers and reactmce of 2 TCSCs.
Figure 3. Single line diagram of the test system
Two bilateral transactions are considered for proving the efficiency the proposed BB-BC based algorithm for ATC enhancement. The first transaction is from generator bus 2 to load bus 29 and the second transaction is from generator bus 5 to load bus 24. The results obtained in these two transactions are discussed below.
Transaction-1: Bus 2-Bus 29
Bus 2 is the GENCO and bus 29 is the DISCO in this transaction. 10 MW power transaction is considered. ATC available before optimization was only 1.1239 MW. This is a low value of ATCof the system and needs to be enhanced. ATC is enhanced by adjusting the transformer tap positions and properly setting the values for TCSC parameters.
The BB-BC algorithm is run with 50 individuals and for 200 iterations. The algorithm takes line 22-24 and line 4-6 as suitable locations for ATC enhancement. Table 2 compares the ATC values before and after insertion of TCSCs. ATC of the system is improved from 1.1239 MW to 1.74 MW.
Table 2. Optimal values of transformer tap settings (Bus 2-Bus 29)
Sl no
Transformer tap
Before
After
1
T6-9
1.078
1.0306
2
T6-10
1.069
1.0567
3
T4-12
1.032
1.1000
4
T28-27
1.068
0.9000
Table 3 indicates the size and location of the two TCSCs used. In this case both TCSCs are operated in capacitive mode.
Table 3. Optimal settings of FACTS devices (Bus 2-Bus 29)
Sl. No
Transaction Between buses
ATC
without TCSC
ATC
with TCSC
Location of TCSCs
Degree of compensation
TCSC1
TCSC2
TCSC1
TCSC2
1
2-29
1.1239
1.7400
21-23
1-3
-0.4829
-0.7176
ATC enhancement results in changed power flows through the lines. Table 4 compares the power flow before and after optimization. Line 1 is relieved much from nearly overloaded condition and the underutilized lines are forced to carry increased power. Line flow limits of all the lines are respected.
Table 4. Line power flows (Bus 2-Bus 29)
Line number
Flow (before)
Flow (after)
MVA
limit
Line number
Flow (before)
Flow (after)
MVA
limit
1
121.130
97.524
130
22
7.105
6.205
16
2
60.881
83.129
130
23
3.827
2.958
16
3
29.841
14.670
65
24
5.689
-6.549
32
4
56.957
77.797
130
25
7.974
8.870
32
5
46.125
40.743
130
26
3.459
5.149
32
6
40.853
28.732
65
27
19.733
18.229
32
7
48.207
60.256
90
28
9.797
5.187
32
8
0.977
-4.206
70
29
2.041
0.563
32
9
21.967
27.235
130
30
7.592
4.098
16
10
14.403
14.160
32
31
9.705
5.164
16
11
14.569
12.513
65
32
6.311
1.441
16
12
12.193
10.723
32
33
7.094
-2.155
16
13
20.000
-20.000
65
34
3.559
3.547
16
14
34.569
32.513
65
35
3.416
-6.011
16
15
30.098
23.662
65
36
29.013
27.470
65
16
20.000
-20.000
65
37
19.826
11.842
16
17
8.854
7.585
32
38
12.573
9.334
16
18
20.797
17.429
32
39
1.298
1.544
16
19
9.247
7.448
32
40
4.379
4.136
32
20
2.534
1.305
16
41
24.751
23.466
32
21
5.603
3.889
16
—-
—–
——
—
The optimization is carefully achieved that the change in power flow pattern does not result in much increased line losses.
Transaction 2: Bus 5-Bus 24
This bilateral transaction is between GENCO 5 and DISCO 24. ATC before insertion of TCSC was 2.2251 MW. Optimization of control parameter values (table 5) maximized the ATC to 3.5287 MW.
Table 5. Optimal values of transformer tap settings (Bus 5-Bus 24)
Sl no
Transformer tap
Before
After
1
T6-9
1.078
1.0730
2
T6-10
1.069
1.0923
3
T4-12
1.032
0.9592
4
T28-27
1.068
1.0986
In this case one TCSC is in capacitive mode and the other one is in inductive mode. Table 6 shows the optimal location and size of TCSCs.
Table 6. Optimal settings of FACTS devices (Bus 5-Bus 24)
Sl. No
Transaction Between buses
ATC
without TCSC
ATC
with TCSC
Location of TCSC
Degree of compensation
TCSC1
TCSC2
TCSC1
TCSC2
1
5-24
2.2251
3.5287
3-4
1-3
0.1927
-0.4823
Line MVA flows are compared in table 7. Line 1 carries only 77.076 MVA against 121.130 MVA after optimization. This is a much relief for the line from congestion and it is left with sufficient capability. This relief ensures adequate transmission corridor and still more transaction are also possible.
Table 7. Line power flows (Bus 5-Bus 24)
Line number
Flow (before)
Flow (after)
MVA
limit
Line number
Flow (before)
Flow (after)
MVA
limit
1
121.130
77.076
130
22
7.105
7.570
16
2
60.881
67.615
130
23
3.827
4.270
16
3
29.841
27.650
65
24
5.689
-5.256
32
4
56.957
63.338
130
25
7.974
7.527
32
5
46.125
67.315
130
26
3.459
2.983
32
6
40.853
39.371
65
27
19.733
17.496
32
7
48.207
50.832
90
28
9.797
7.618
32
8
0.977
-18.869
70
29
2.041
-0.144
32
9
21.967
2.368
130
30
7.592
7.930
16
10
14.403
11.586
32
31
9.705
7.554
16
11
14.569
11.341
65
32
6.311
4.382
16
12
12.193
10.083
32
33
7.094
1.769
16
13
20.000
-20.000
65
34
3.559
3.558
16
14
34.569
31.341
65
35
3.416
-1.807
16
15
30.098
31.611
65
36
29.013
15.180
65
16
20.000
-20.000
65
37
19.826
6.228
16
17
8.854
9.220
32
38
12.573
7.141
16
18
20.797
21.347
32
39
1.298
3.715
16
19
9.247
9.843
32
40
4.379
1.566
32
20
2.534
2.886
16
41
24.751
13.649
32
21
5.603
6.130
16
—-
—–
——
—
-
CONCLUSIONS
This work proves the effectiveness of the BB-BC algorithm in ATC enhancement incorporating TCSC devices. ATC of the system is enhanced by changing the power flow pattern by inserting TCSCs and adjusting tap positions of transformers. It is obvious from the numerical results that the ATC improvement is very much encouraging. The system operator can use this method to facilitate more power transfer agreements for the future power markets. Further, all the lines in the system are left with sufficient ATC and therefore the
system becomes capable of transmitting increased amount of power flows and with sufficient security.
In a deregulated environment, the very purpose of supplying power to consumers at competitive price can be ensured. Moreover, the BB-BC algorithm is simple, has less number of parameters and it can be implemented easily.
REFERENCES
-
B.V. Manikandan, S. Charles Raja, P. Venkatesh, Available Transfer Capability Enhancement with FACTS Devices in the Deregulated Electricity Market, Journal of Electrical Engineering & Technology, Vol. 6, No. 1, pp. 14-24, 2011.
-
E. Hirst, U.S. Transmission Capacity: Present Status and Future Prospects, Edison Electric Institute and Office of Electric Transmission and Distribution, U.S. Department of Energy, 2004.
-
K. S. Verma, S. N. Singh, H. O. Gupta, Facts Devices Location for Enhancement of TTC, Power Engineering Society Winter Meeting, IEEE. 2, pp. 522-527, 28 January- 1 February.
-
H. Sawhney, B. Jeyasurya, Application of Unified Power Flow Controller for Available Transfer Capability Enhancement, Electric Power Systems Research, Vol. 69, No. 2-3, pp. 155-160, 2004.
-
J. Weber, Efficient Available Transfer Capability Analysis using Linear Methods,
PSERC internet seminar, UL, USA, Nov 7, 2000.
-
S. Gerbex, R. Cherkaoui and A.J. Germond, Optimal Location of Multi-type FACTS devices by Means of Genetic Algorithm, IEEE Transactions on Power Systems, Vol. 16, No. 3, pp. 537-544, 2001.
-
Acharya N, Mithulananthan N. Locating Series FACTS Devices for Congestion Management in Deregulated Electricity Markets, Electric Power System Research, Vol. 77, pp. 35260, 2007.
-
M. Saravanan, S.M.R. Sulochanal, P.Venkatesh and J.P.S.Abraham, Application of Particle Swarm Optimization Technique for Optimal Location of FACTS Devices Considering Cost of Installation and System Loadability, Electric Power Systems Research, Vol. 77, No. 3-4, pp. 276-283, 2005.
-
A. M. Leite da silva, J. G. C. Costa, L. A. F. Manso and G. J. Anders, Evaluation of Transfer Capabilities of Transmission Systems in Competitive Environments, Electrical Power and Energy systems, Vol. 26, No. 4, pp. 257-263, 2004.
-
H. D. Chiang, A. J. Flueck, K. S. Shah, N. Balu, CPFLOW: A Practical Tool for Tracing Power System Steady State Stationary Behaviour due to Load and Generation Variation, IEEE Transactions on Power Systems, Vol. 10, pp.623-634, May 1995.
-
G. C. Ejebe, J. Tong, G.C.Waight, J.G. Frame, X. Wang and W.F.Tenney, Available Transfer Capablity Calculations, IEEE Transactions on Power systems, Vol. 113,No. 4, pp.1521-1527, November 1998.
-
G. C. Ejebe, J. G. Waight, M. Santos-Nieto, and W. F. Tinney, Fast Calculation of Linear Available Transfer Capability, IEEE Transactions on Power Systems, Vol. 15, pp. 11121116, Aug. 2000.
-
G. Hamoud, Assessment of Available Transfer Capability of Transmission Systems,
IEEE Transactions on Power systems, Vol.15, No. 1, pp.27-32., February 2000.
-
R. D. Christie, B. F. Wollenberg, I. Wangstien, Transmission Management in the Deregulated Environment, Proc. of the IEEE, Vol. 88, No. 2, pp. 170-195, Feb. 2000.
-
A.Kumar, S.C. Srivatsava, AC Power Distribution Factors for Allocating Power Transactions in a Deregulated Environment, IEEE Power Engineering Review, pp. 42-43, 2002.
-
A. Kumar, S. C. Srivatsava, S. N. Singh, ATC Determination in a Competitive Electricity Market using AC Distribution Factors, Electrical Power components and Systems, Vol. 32, No. 9, pp. 927-939, 2004.
-
K. Erol Osman, Ibrahim Eksin, New optimization method : Big Bang-Big Crunch,
Elsevier, Advances in Engineering Software 37, pp. 106111, 2006.
-
S. Sakthivel, D. Mary, Reactie Power Optimization Incorporating TCSC Device through Big Bang-Big Crunch Algorithm for Voltage Stability Limit Improvement, Wulfenia Journal, Vol. 19, No. 10, 2012.
-
Power Systems Test Case, 2000, The University of Washington Archive, http://www.ee.washington.edu/research/pstca.
Author Biographies
S. Sakthivel received the Degree in Electrical and Electronics Engineering in 1999 from Madras University and Master Degree in Power Systems Engineering in 2002 from Annamalai University. He is pursuing the Ph.D., Degree in Electrical Engineering faculty from Anna University of Technology, Coimbatore, India. He is presently working as an Associate Professor in Electrical and Electronics Engineering at V.R.S.College of Engineering and Technology, Villupuram, Tamil Nadu, India. His research areas of interest are Power System control,
Optimization techniques, FACTS, Economic load dispatch, Power system deregulation and Voltage stability improvement.
P. Mathiazhagi is an undergraduate student with the Department of Electrical and Electronics Engineering at VRS College of Engineering and Technology, Villupuram, Tamil Nadu, India. Optimal power flow using evolutionary algorithms is her important area of interest.
T. K. Archana is an undergraduate student in the Department of Electrical and Electronics Engineering at VRS College of Engineering and Technology, Villupuram, Tamil Nadu, India. She is interested in power system operation optimization by using intelligent techniques.