Comparison of Seismic Performance of Solid and Hollow Reinforced Concrete Members in RCC Framed Building with Plan Irregularity

DOI : 10.17577/IJERTV6IS060329

Download Full-Text PDF Cite this Publication

Text Only Version

Comparison of Seismic Performance of Solid and Hollow Reinforced Concrete Members in RCC Framed Building with Plan Irregularity

Sherin G Ponnachen1,

1PG scholar,Sree Buddha College of Engineering, Alapuzha Pathanamthitta cluster of APJ Abdul Kalam Technological University,

Ayathil, Elavumthitta P.O, Pathanamthitta-689625

Archana Sukumaran2

2Assistant Professer

Sree Buddha College of Engineering, Alapuzha Pathanamthitta cluster of APJ Abdul Kalam

Technological University,

Ayathil, Elavumthitta P.O, Pathanamthitta-689625

Abstract: Hollow (Box-type) reinforced concrete beams and columns help in decreasing superstructure weight and hence seismic mass is minimized as compared to conventional solid reinforced concrete beams and columns. ETABS is commonly used to analyses: Skyscrapers, parking garages, steel & concrete structures, low and high rise buildings, and portal frame structures. The case study in this paper mainly emphasizes on structural behavior of R.C.C. framed building having hollow and solid reinforced concrete members. Modelling of G+6 and G+13

R.C.C. framed building is done on the ETABS software for analysis. Post analysis of the structure, maximum storeyshear

,maximum storey drift will compute and then compared for all the analyzed cases.

Keywords: Structural behaviour, Hollow reinforced concrete member; ETABS; Storey shear; Storey overturning moment

I.INTRODUCTION

Continuous rise in the prices of steel reinforcement and cement leads, to the search for ways to reduce the weight of the concrete. This reflects on the total cost of the construction project. This also has a significant effect on environmental problems caused by use of huge amounts of cement and steel. Hollow (Box-type) members are lighter in weight and help in decreasing superstructure weight and hence seismic mass is minimized as compare to conventional solid reinforced concrete beams and columns. The economical convenience in the use of hollow reinforced concrete member is due to the cost saving afforded by reduced section area (up to 70%).An RCC framed building is basically an assembly of slabs, beams, columns and foundation inter-connected to each other as a unit. The load transfer mechanism in these structures is from slabs to beams, from beams to columns, and then ultimately from columns to the foundation, which in turn passes the load to the soil. A columns is a structural member that transmits through compression the weight of the structure above to other structural elements below.In other words column is a compression member.

A beam is structural element that primarily resists loads applied laterally to the beam's axis. Its mode of deflection is primarily by bending. The loads applied to the beam result in reaction forces at the beam's support points. The total effect of all the forces acting on the beam is to

produce shear forces and bending moments within the beam, that in turn induce internal stresses, strains and deflections of the beam. The construction of tall bridge piers using rectangular hollow reinforced concrete column is attractive means in which superstructure weight and hence seismic mass is minimized. The column strength and stiffness is maintained whilst significantly reducing the construction cost. There is currently a reluctance among bridge designers to specify the use of ductile hollow columns for tall bridge piers due to the unknown performance of the plastic hinge regions under severe seismic disturbances

  1. OBJECTIVE

    1. To carry out the seismic analysis of RCC framed building using solid and hollow concrete members and comparing results of both.

    2. To find out how number of stories influence the RCC framed building ,subjected to solid and hollow concrete members

    3. To find out the seismic behaviour of RCC framed buildings in two different seismic zones

  2. METHODOLOGY Methodology employed is response spectrum method Modelling of Building

    Here study mainly deals with the structural behaviour of G +13 and G+6 RCC framed building with Hollow (Box- type) and Solid reinforced concrete members under Seismic load using ETABS software. An RCC framed building having 4m x 4m bays is considered and storey height is taken as 3.5m.. Loads considered are taken in accordance with the IS-1893(2002). ETABS is more user friendly and versatile program that offers a wide scope of features like static and dynamic analysis, non- linear dynamic analysis and non-linear static pushover analysis, etc.

    Building Plan and Dimension Details

    Table below shows the details of building

    Table 1: Building details

    Total height of building

    49 m and 24.5 m

    No. of stories

    14 and 7

    Height of each storey

    3.5 m

    Grade of concrete

    M30

    Grade of steel

    Fe415

    Depth of slab

    150 mm

    The figure below shows the model of a RCC framed building with plan irregularity.

    Fig 1. Plan of the RCC framed building T ABLE II. Column Details

    TABLE III. Beam Details

  3. COMPARISON OF RESULTS

    After analysing the results obtained then it will be compared and find the seismic performance of the building. Graphical representation of storey drift and base shear values are shown in figure below.

    Maximum Storey Drift-14 storey

    0.05

    0.045

    0.04

    0.035

    0.03

    0.025

    0.02

    0.015

    0.01

    0.005

    0

    Max Story

    Drift-14 stry

    Hollow Solid

    building building

    Model 1 model 2

    Fig 2:Maximum storey drift for seismic zone V

    From figure 3 it is observed that Hollow beams and columns in RCC framed building help in reducing storey drift as compared to solid beams and columns. There is 37% reduction in the storey drift due to Hollow members.In the case of seismic zone III also building with hollow nembers have less storey drift.There is 21% reduction in storey drift when hollow members are used.The same pattern is observed in the case of 7-storied building.ie,story drift is less for RCC building with hollow members.

    Maximum Base shear-14 storey

    72000

    70000

    68000

    66000

    64000

    62000

    60000

    58000

    Max base shear-

    14stry

    hollow solid building

    building

    Model 1

    model 2

    Fig 3 :Maximum base shear for seismic zone V

    Maximum Storey Drift- 7 storey

    0.04

    0.035

    0.03

    0.025

    0.02

    0.015

    0.01

    0.005

    0

    Max Story Drift-

    7 stry

    Hollow Solid

    building building

    Model 1

    model 2

    Fig 4 :Maximum storey drift for seismic zone V

    Maximum base shear-7storey

    70000

    60000

    50000

    40000

    30000

    20000 Max base shear-

    7stry

    10000

    0

    hollow solid building building

    Model 1

    model 2

    Fig 5 :Maximum base shear for seismic zone V

    Base shear is less in case of Hollow members than solid members in RCC framed building. It is observed that the storey shear for RCC framed building having hollow members is decreased by 12% as compared to solid member in 14 storied building. It is observed that the storey shear for RCC framed building having hollow members is decreased by 27% as compared to solid member in 7storied building.

    Maximum StoreyDrift- 7 stry

    0.0035

    0.003

    0.0025

    0.002

    0.0015

    0.001

    0.0005

    0

    Max Story Drift-

    7 stry

    Hollow Solid

    building building

    Model 1

    model 2

    Fig 6. Maximum storey drift for seismic zone III

    Maximum base shear-7storey

    70000

    60000

    50000

    40000

    30000

    20000

    10000

    0

    Max base shear-

    7stry

    hollow solid

    building building

    Model 1 model 2

    Fig 7. Maximum base shear for seismic zone III

  4. CONCLUSIONS

    On the basis of results obtained from structural analysis of

        1. framed building using ETABS the following conclusions can be drawn:

          • There is 27% to 37% reduction in maximum storey drift (seismic zone V) and 21%-33% reduction in maximum storey drift (seismic zoneIII) due to Hollow members in RCC framed building.

          • There is 12% to 29% reduction in base shear(seismic zone V) and 2%-11% reduction in base shear (seismic zoneIII) due to Hollow members in RCC framed building .

          • Maximum storey shear ,storey drift increases as number of stories increases in the case of both solid and hollow members provided

          • The value of storey drift ,storey shear is more in seimic zone V when compared to seismic zone III.

          • In storey shear,storey drift point of view buildings with hollow members performs better than buildings with solid members

  5. FUTURE SCOPE

Further study can be carried out by changing the shape of columns provided Also study can be carried out in seismic zones II and IV

REFERENCES

  1. Thanuja H.P, E.Ramesh Babu and Dr N S Kumar, A Study on Behaviour of Circular Stiffened Hollow Steel Column Filled with Self Compacting Concrete Under Monotonic Loading, INDIAN JOURNAL OF APPLIED RESEARCH, Volume : 4, Issue : 8, August 2014, ISSN – 2249-555X.

  2. Waleed AboEl-Wafa Mohamed, Seismic Capacity of RC hollow block slab building and retrofitting systems, Journal of Engineering Sciences, Assiut University, Faculty of Engineering, Vol.42, No. 3, May 2014.

  3. Dr. T. ChandraSekharRao, Dr. T. D. GunneswaraRao, Dr. N. V. RamanaRao, Ch. Rambabu, An Experimental study on ferrocement box-beams under flexural loading, International Journal of Emerging Technology and Advanced Engineering, ISSN 2250-2459, Volume 2, Issue 9, September 2012.

  4. Rao.T.C, Rao.T.D.G & Rao.B.P.R, Flexural Behaviour of Thin- webbed Ferrocement Channel Sections, International Journal of Applied Engineering Research, Vol.7, No.7 (2012), pp.707-716.

  5. Falah M. Wegian and Falah A. Almottiri, Experimental Studies on Reinforced Hollow- Block Concrete Sections, Jordan Journal of Civil Engineering, Volume 1, No. 4, 2007.

  6. A. Kumar; Ferrocement Box sections-viable option for Floors and Roof of Multi-storied Buildings, Asian Journal of Civil Engineering (Building and Housing), Vol. 6, No. 6, 2005, pp. [7] Giulio Ranzo & M J N Priestley, Seismic performance of large reinforced concrete circular hollow columns, 12WCEE, 2000.

  7. Bureau of Indian Standards: IS-875, part 1 (1987), Dead Loads on Buildings and Structures, New Delhi, India.

  8. Bureau of Indian Standards: IS-875, part 2 (1987), Live Loads on Buildings and Structures, New Delhi, India.

  9. Bureau of Indian Standards: IS-1893, part 1 (2002), Criteria for Earthquake Resistant Design of Structures: Part 1 General provis

Leave a Reply