Cost-Benefit Analysis and Emission Reduction of Lighting Retrofits in an Academic Institution

DOI : 10.17577/IJERTCONV5IS05033

Download Full-Text PDF Cite this Publication

Text Only Version

Cost-Benefit Analysis and Emission Reduction of Lighting Retrofits in an Academic Institution

Kuldeep Singh

Electrical Engineering Department, Assistant Professor at Baba Banda Singh Bahadur

Engineering College, Fatehgarh Sahib, India

Simarpreet Singh

Electrical Engineering Department, Assistant Professor at Baba Banda Singh Bahadur

Engineering College, Fatehgarh Sahib, India

Abstract – This study projects electricity savings, cost benefit analysis and emission reduction of lighting retrofits in an academic institution. The cost-benefit is determined as a function of energy savings due to retrofit of more efficient lighting system. The energy savings were calculated based on 25, 50, 75 and 100% of potential retrofits of inefficient lighting in the academic institution. The data used was collected by conducting a survey and by recording the actual load and operating hours of the existing inefficient lighting system at different places in the institution. The study found that, this strategy save a significant amount of energy and money. The study also shows that there is a good potential for reducing carbon emissions by retrofitting the inefficient lighting with efficient lighting.

  1. INTRODUCTION

    There has been growing concern about energy consumption and its environmental implications for the last decade. A lot of energy efficient measures are being taken day by day to save energy. Lighting system in any building consumes a substantial part of total electricity consumption. Electric lighting accounts for about 25% of total building energy used by Ghisi and Tinker, 2005. A lighting retrofit means to replace inefficient lighting with the efficient one. Electricity savings over time is significant enough to not only pay for the new lighting, but also produce return on investment. This can be done by either reducing the input wattage or reducing the hours of operation of the lighting to reduce energy consumption. A lot of studies on retrofitting inefficient lighting by reducing input wattage are conducted as presented by Stefano, 2000; Lee, 2000; Guan et al.,1997. This study is also proposed to reduce consumption of electricity by retrofitting of conventional electromagnetic ballasts used with T8 fluorescent tube lights with more efficient electronic ballasts in an academic institution. The electronic ballast can replace electromagnetic ballast without any modification. Fluorescent tube light uses an arc of electricity to create light. This current must be applied in very precise ways to the gases within the tube–normal household electrical current is too erratic and powerful for the fluorescent tube. So the fixture requires a control device known as the ballast, which limits the current and meters it out in cycles that the tube light needs to keep lit.In all fluorescent lighting systems, the ballast provides the proper voltage to start the lamp and then regulates the electric current flowing through the lamp to stabilize output. There are two types of ballasts, the conventional electromagnetic ballasts and the newer electronic ballasts. Electronic ballasts increase lamp-ballast efficacy, leading to increased energy

    efficiency and lower operating costs. Electronic ballasts are more efficient than magnetic ballasts in converting input power to the proper lamp power, and their operating of fluorescent lamps at higher frequencies reduces end losses, resulting in an overall lamp-ballast system efficacy increase of 15% to 20% as presented by Eley et al., 1993.

    One of largest advantages of electronic ballast is the enormous energy savings it provides. This is achieved in two ways. The first is its amazingly low internal core loss, quite unlike old fashioned magnetic ballasts. And second is increased light output due to the excitation of the lamp phosphors with high frequency.The life of FTL with magnetic ballasts is only 5000 burning hours whereas the life with electronic ballast increases up to 20000 burning hours given by Cris Gribbin,2006. This study attempts to calculate potential electricity savings, emission reduction and cost benefit analysis of lighting retrofit and to make a small effort in curbing the global warming.

  2. COLLECTED DATA

    Sant Longowal Institute of Engineering and Technology is located in Longowal, district Sangrur, Punjab, India. The data used for this study is collected from the institution buildings and comprises of number of fixtures, operating hours per year and wattage of Fluorescent Tube Lights. The building blocks selected for the study are 10 hostels and 5 Instructional blocks, Administration Block, Health Centre, Student Activity Centre and Estate Office. Location details and number of fixtures are provided in Table 1-3. Generally, in SLIET one semester holds for 16 weeks and classes are conducted for 5 days a week excluding Saturdays and Sundays. So number of days of working for instructional blocks is calculated as 160 and operating hours is taken as 6 hours/day. For office buildings the number of days of operation is calculated as 220. This can be calculated as there are 365 days in a year and offices are occupied for 5 days in week so number of days remaining excluding Saturdays and Sundays are 261 and further 20 days are deducted due to holidays and further 20/21 days are taken as reserve for leaves by the individual office occupants. For hostels the number of days of operation is taken as 250 as normally a student resides in the hostel for 8 months (approx.) per year and hours of operation taken is 10 hours per day. The data is collected by conducting survey at all these locations. The uncertainty, sensitivity analyses, life cycle cost and payback period of lighting system can be found by McMahon et al., 2000.

    Table.1.Input data for fixtures in Teaching Blocks

    Location

    No. of fixtures

    Electrical and

    Instrumentation

    800

    Computer Science

    300

    Mech. and Workshops

    1500

    Food and chemical

    600

    Applied sciences

    500

    Total

    3700

    Table.2.Input data for fixtures in Hostels

    Items

    Details

    No. of Hostels

    10

    Fixtures in Hostel

    200

    Total

    2000

    Table.3.Input data for fixtures in Offices

    Items

    Details

    Administration Block

    300

    Health Centre

    20

    Estate Office

    30

    Student Activity

    Centre

    100

    Total

    450

    ABBREVIATIONS USED

    AS annual savings (Rupees) BS bill savings (Rupees) CC capital costs (Rupees)

    CERs certified emission reductions (tCO2) d discount rate

    DO days of operation in a year

    E electronic ballast lighting system EC energy consumption (kWHr)

    ECE energy consumption with electronic ballast (kWHr)

    ECM energy consumption with electromagnetic ballast (kWHr)

    EF emission factor

    ES energy savings (kWHr) GRC gross return on capital (%) LL lamp life (burning hours)

    M electromagnetic ballast lighting system n number of years

    NF number of fixtures NPV net present value NRC net return on capital OH operating hours

    PC power consumption (kWHr) PE price of electricity (Rs/kWHr)

    PF1 power factor with lighting system M PF2 power factor with lighting system E R number of replacements

    TS total savings (Rupees)

  3. METHODOLOGY

    A survey is necessary to determine the potential of retrofit lighting, the operating hours of fluorescent tube lights with electromagnetic ballasts and load taken by one fixture. The data obtained from the survey presented in Tables 4-6 was used to calculate projected electricity savings, emission reductions and cost-benefit analysis of lighting retrofits.

    Table.4.Load calculations with electromagnetic ballast for Table 1

    Items

    Details

    Electrical load per fixture

    45 W

    Operating Hours per day

    6

    No. of days per year

    160

    Total fixtures taken

    3700

    Total electrical load

    166.5 kW

    Total units consumed/year (kWHr)

    159840

    Table.5.Load calculations with electromagnetic ballast for Table 2

    Items

    Details

    Electrical load per fixture

    45 W

    Operating Hours per day

    10

    No. of days per year

    250

    Total fixtures taken

    2000

    Total electrical load

    90 kW

    Total energy

    consumed/year (kWHr)

    225000

    Table.6.Load calculations with electromagnetic ballast for Table 3

    Items

    Details

    Electrical load per fixture

    45 W

    Operating Hours per days

    6

    No. of days per year

    220

    Total number of fixtures

    450

    Total electrical load

    20.25

    Total units consumed/year (kWHr)

    26730

      1. Number of Retrofits

        Number of retrofits is determined by conducting a survey and it was found that in SLIET there is a practice of using 1X36 W, T8 fluorescent tube light fixture with electromagnetic ballast. So total numbers of fixtures were counted and there is a potential of 6150 lighting retrofits.

      2. Energy Consumption

        Energy consumed by the existing system is calculated by the multiplication of total number of retrofits in each block, power consumption, number of days of operation per year and operating hours of the lighting per day. This can be represented by the following equation. All the calculations are done in according to Mahlia et al., 2004.

        EC NF PC OH DO .. (1)

      3. Energy Savings

        Energy savings from retrofitting is the difference between energy consumption of inefficient and efficient lighting. This is given in table 7. This can be calculated using the following equation:

        ES EC M EC E

        (2)

        Table.7.Predicted electricity consumption and savings

        Location

        ECM(kWHr/year)

        ECE(kWHr/year)

        Potential of electricity savings (kWHr/year)

        25% retrofits

        50% retrofits

        75% retrofits

        100% retrofits

        Teaching Blocks

        159840

        127872

        7992

        15984

        23976

        31968

        Offices

        26730

        21384

        1336.5

        2673

        4009.5

        5346

        Hostel

        225000

        180000

        11250

        22500

        33750

        45000

        Total

        411570

        329256

        20578.5

        41157

        61735.5

        82314

      4. Emission reduction

        The environmental impact from retrofitting is potential reduction of greenhouse gases which pollutes the environment or other element that caused negative impact on the environment. Carbon emissions can be reduced to some extent by retrofitting the inefficient lighting along with savings in energy. The potential CERs that can be generated from these measures are calculated by taking emission factor of 0.7240 kg of CO2/kWHr given by the CO2 Baseline Database for the Indian Power Sector, 2007. The emission reduction is a function of energy savings. The CERs are calculated by the following equation:

        ES EF

        BS ES PE (6)

        Items

        Details

        Total electricity savings per

        year (kWHr)

        82314

        Price of one electricity unit

        (Rs)

        5

        Total electricity bill savings

        (Rs)

        411570

        Cost of one Electronic Ballast

        (Rs)

        200

        Cost of one 36 W TFL 3250

        lumens (Rs)

        65

        Replacement and labor charges per fixture (Rs)

        45

        Total replacement charges

        (Rs)

        310

        Total investment for replacing 6150 ballasts (Rs)

        1906500

        Simple payback period

        (years)

        4.6

        Table.8.Bill savings and simple payback period for 100% retrofit

        CERs

        1000

        . (3)

      5. Gross return on capital

        Gross return on capital is a function of total savings from the project and capital costs required for the implementation of the project. It expresses the annual return from the project as a percentage of capital cost. This can be calculated from the following equation:

        GRC ( TS ) 100

        CC

        250000

        200000

        168750

        112500

        56250

        225000

        25% Retrofits

        50% Retrofits

        75% Retrofits

        100% Retrofits

        Bill Savings (Rs./year)

        .. (4)

      6. Net return on capital

        Net return on capital is also a function of total savings from the project and capital cost required for the implementation of the project. It is expressed with the help of following equation:

        NRC (TS CC ) 100

        150000

        Rs.

        100000

        50000

        0

        79920

        39960

        119880

        159840

        6682.5

        13365

        20047.5

        26730

        CC

      7. Bill savings

        .. (5)

        Hostels Teaching Blocks Offices

        Fig.1. Annual Bill Savings due to lighting retrofit

      8. Replacements

    The bill savings of lighting retrofit is a function of energy savings and the average price of electricity. The potential bill savings by lighting retrofit is shown in Table 8 and is calculated by the following equation:

    The replacement of the fixture is a function of rated life of the lamp and actual operating hours of the lamp. The burning hours of FTL with electromagnetic ballast is

    OH DO

    5000 hours whereas with electronic ballast the life increases up to 20000 hours. So, number of replacements will decrease and running cost will also decrease with suggested replacements. The details of number of replacements and running costs are shown in Table 9. Number of replacements can be calculated with the help of following equation:

    R LL NF

    .. (7)

    Table.9.Comparison of running cost of system M and E

    Items

    Details

    M

    E

    Annual electricity costs (Rs)

    21222000

    1527840

    Lamp life (Burning hours)

    5000

    20000

    Total replacements per year

    1829.2

    457.3

    Replacement cost per FTL

    32

    65

    Total replacement cost/year (Rs)

    58534.4

    29724.5

    Total running cost per year (Rs)

    2116384

    1676005

    Table.10. Predicted emission reduction (tCO2)

    Retrofits

    Tons of Carbon

    Dioxide/year

    25%

    14.89

    50%

    29.79

    75%

    44.69

    100%

    59.59

      1. Distribution losses

        In an electrical system distribution losses are of great importance towards energy loss estimations. One factor which influences distribution losses is power factor of electrical system. A lot of emphasis is given to improve the power factor of the system to reduce distribution losses. The power factor of electromagnetic ballast is 0.5 only whereas power factor of electronic ballast is as high as 0.95. Reduction in the distribution loss % in kWh when tail end power factor is raised from PF1 to a new power factor PF2 will be as given by Mahlia et al., 2004., as give below

        PF

        2

        1 1 100

        It shows that electricity savings of 82314 KWh annually can be achieved by replacing electromagnetic ballasts with energy efficient electronic ballasts in the institution. Table 8 shows the potential bill savings of Rs 411570 per year and the pay-back period is only 4.6 years which is a short term pay- back period as it is less than 5 years. The power factor of the electromagnetic ballasts is only 0.5 whereas the power factor of electronic ballast is 0.95. With retrofitting of electromagnetic ballast by electronic ballasts the power factor of the system will increase which has additional advantage of reduction in distribution losses as if the overall power factor of the system is increased from 0.5 to 0.95 then distribution losses will reduce by 72% which will help the power generating company. Due to reduction of overall load the conductor heating will reduce and thus heat losses will also be lower. As a result, maintenance charges will reduce. With the installation of 36 W T8 energy efficient lamps with 3250 lumens there will be 33% increase in the luminance as compared to the existing lamp of 2450 lumens. Based on potential energy savings per year, the emission reduction can be calculated using Eq. (3). The result is tabulated in Table

        10. The predicted annual emission reductions from teaching blocks and hostels is 59.59 tCO with 100% retrofits. The

        PF 2

        2

        … (8)

        emission reductions with 25, 50 and 75% retrofits are also

        shown in the Table 10. Net present values with 25%, 50%,

      2. Net present value

        Net present value depends on the discount rate. This is calculated for 8%, 9% and 10% discount rate for 10 years. This can be calculated from the following equation:

        AS [(1 d )n 1]

        NPV [d (1 d )n ] . (9)

        75% and 100% retrofits are also calculated with 8%, 9% and 10% discount rates separately for hostels, offices and teaching blocks which are presented by Figs. 2-5. Figures shows that for 25% retrofits the values are almost same with all the discount rates but with 100% retrofits there is a considerable difference in the values with different discount rates.

        Net Present Value for Hostels

    1. RESULTS AND DISCUSSIONS

    To calculate energy consumption and potential energy savings by retrofit, it is necessary to have daily average operating hour of lighting in the institution. Based on survey data collected in different locations in the institute the energy consumption and potential energy savings can be calculated. For this study, the calculation is done for 25, 50, 75 and 100% of retrofits. The calculation result is tabulated in Table 7.

    1600000

    1400000

    1200000

    1000000

    Rs.

    800000

    600000

    400000

    200000

    0

    8% Discount Rate 9% Discount Rate

    10% Discount Rate

    25 50 75 100

    Retrofits

    Fig. 2 Net present value for Hostels

    1200000

    1000000

    800000

    Rs.

    600000

    400000

    200000

    0

    Net Present Value for Teaching Blocks

    8% Discount Rate

    9% Discount Rate

    10% Discount Rate

    400

    350

    300

    250

    %

    200

    150

    100

    50

    0

    362.9

    262.9

    2.8

    Return on Capital

    7.2

    139.4

    39.4

    5.2

    191.6

    91.6

    8

    7

    6

    5

    4

    3

    2

    1

    0 Years

    Gross Return On Capital (%)

    Net Return On Capital (%)

    Simple Pay back (years)

    25 50 75 100

    Retrofits (%)

    Fig. 3 Net present value for teaching blocks

    Hostels Teaching Blocks Offices

    Fig. 6 Return on capital and simple payback period

    200000

    180000

    160000

    140000

    Rs.

    120000

    100000

    80000

    60000

    40000

    20000

    0

    1600000

    1400000

    1200000

    1000000

    Rs.

    800000

    600000

    400000

    200000

    0

    Net Present Values for Offices

    8% Discount Rate

    9% Discount Rate

    10% Discount Rate

    25 50 75 100

    Retrofits (%)

    Fig. 4 Net preent value for offices

    NPV at 8% Discount Rate

    25% Retrofit

    50% Retrofit

    75% Retrofit

    100% Retrofit

    Hostels Teachng Blocks Offices

    Fig. 5 NPV at 8% discount rate

  4. CONCLUSION

The calculation results show that lighting retrofits have significant impact on the institution electricity consumption. The recommendations based on findings can be considered for implementation in hostels and offices as considerable amount of energy can be saved and the cost benefit analysis shows that these two areas have high return rate. Furthermore, it will result in reduction in emission from power consumed by the institution. It can be concluded that the institution should encourage use of energy efficient lighting instead of inefficient lighting in the institution. A lot of energy can be saved and emission reductions can be achieved if such kinds of measures are adopted by other institutes also, which have hostel facilities.

REFERENCES

  1. Ghisi E, Tinker JA. An ideal window area concept for energy efficientintegration of daylight and artificial light in buildings. Build Environ 2005; 40(1):5161.

  2. Stefano J.D., Energy efficiency and the environment: the for energy efficient lighting to save energy and reduce carbon dioxide emissions at Melbourne University, Australia, Energy The International Journal 25 (2000) 823-839.

  3. Lee A.H.W., Verification of electrical energy savings for lighting retrofits using short- and long-term monitoring, Energy Conservation and Management 41 (2000) 1999-2008.

  4. Guan F.M. et al.,1997, Energy efficient lighting in China, Energy Policy 25 (1997) 77-83..

  5. Eley, C. et al., 1993, Advanced Lighting Guidelines: Final

    Gross return on capital and net return on capital are calculated and presented by Fig. 6. It is found that the gross return on investment by retrofitting the lighting in hostels and offices is high which is 362.9 and 191.6 respectively, whereas by retrofitting the lights in teaching blocks the return is not so attractive and is 13.4. Similar is the trend for net return on capital value.

    Report. Prepared for the U.S. Department of Energy, California Energy Commission, and Electric Power Research Institute, 1993.

  6. Cris Gribbin, National Light Product Information Program, Lighting Answers: T8 Fluorescent life, Volume 9, Issue 1, PP7, June 2006.

  7. McMahon J. et al., 2000, Uncertainty and Sensitive Analysis of Ballast Life-cycle Cost and Payback Period, Lawrence Berkely Laboratory, University of California, Berkeley, 2000.

  8. Mahlia T.M.I., et al., 2004, Cost-benefit analysis and emission reduction of lighting retrofits in residential sector, August 2004.

  9. The CO2 Baseline Database for the Indian Power Sector, Ministry of Power, Central Electricity Authority (CEA), Version 2, 2007.