Energy Audit of a Boiler- A Case Study Thermal Power Plant, Unit-Iii Parli (V) Maharastra

DOI : 10.17577/IJERTV2IS60659

Download Full-Text PDF Cite this Publication

Text Only Version

Energy Audit of a Boiler- A Case Study Thermal Power Plant, Unit-Iii Parli (V) Maharastra

Mr. M. G. Poddar. Mrs. A. C. Birajdar Asst.Prof. Instrumentation Engg. Dept . Asst.Prof. Instrumentation Engg. Dept.

M.B.E.S. College of Engg, Ambajogai. M.B.E.S. College of Engg, Ambajogai. Maharastra. Maharastra.

Abstract

The world over, energy resources are getting scarcer and increasingly exorbitant with time. In India bridging the ever-widening gap between energy demand and supply by increasing supply is an expensive option. The share of energy costs in total production costs can, therefore improve profit levels in all the industries. This reduction can be achieved by improving the efficiency of industrial operations and equipments. Energy audit plays an important role in identifying energy conservation opportunities in the industrial sector, while they do not provide the final answer to the problem, they do help to identify potential for energy conservation and induces the companies to concentrate their efforts in this area in a focused manner.

Hence, there is a growing interest in understanding the energy audit study Therefore, in this project, the present study of Energy Audit mainly focused at identifying practical, sustainable and economically viable energy cost saving opportunities in boiler of Unit- III of the Parli Thermal Power Station. The study shows that there is significant energy cost saving opportunities, and recommendations have been made to realize this potential.

  1. Introduction [1][2][3].

    Energy may be defined as the capacity for vigorous activity. Energy is present in nature in various forms. Mankind uses the various forms energy for different purposes consist of lighting, heating, cooking, running machinery, transportation and for other applications. It is the crucial resource for all nation building activities, which keep the countrys wheels of progress moving at an

    accelerated pace. Without energy the activities of mankind will come to a standstill and the life on the earth become impossible.

    Energy conservation is a wise and efficient use of energy in order to ensure that for a given amount of energy maximum activities, productive work and profitability is achieved.

    The availability of commercial sources of energy such as oil, coal and gas within our country are rapidly dwindling and the supply of them has to be supplemented by import. Based on the present consumption, the commercial resource will last for oil 17 years; gas 59 years; and coal 300 years (30 years for high grade coal).

    Keeping above considerations in view, it is high time to focus our attention towards energy conservation. Conserving energy is a national need wherein every individual at whatever level can participate and help. By energy conservation, we can save 10 to 30% of energy and cost through simple action.

    In the case of industries, such as power plants the energy conservation is must. In this study our attention is focused on Energy auditing. Energy audit serves to identify all the energy streams into a facility quantify energy use according to discrete function.

    Energy audit is a vital link in the entire energy management chain. The energy manager in proposing course of action and evaluating their consequences required a detailed information base from which to work. The information base is produced by energy audit a vital element in the overall energy management program.

    The overall program includes other managerial and operational activities and

    responsibilities. However, the audit process is the most important part of the program and is essential to the programs implementation.

    The term audit signifies an analysis of the input and output parameters to evaluate discrepancies if any. Energy audit also aims at identifying, evaluating and analyzing various forms of energy input and output. But the scope of energy audit does not end here. With the help of this information, potential areas of energy conservation are identified so as to review the specific energy input both in terms of cost as well as absolute quantity. Energy audit also throws pointers where further action may be required for improving the performance of the equipment / process. It is therefore lays the foundation for development of better process. In an energy audit study of system interaction effect opens the potential for improvement in other areas such as quality, working conditions, environmental effects etc. Thus, energy audit is not merely an audit but is more of a total system improvement technique.

    In this project, the study is mainly targeted at identifying, sustainable and economically viable energy cost saving opportunities in boiler section of Unit-III of Parli Thermal Power Station, Parli-Vaijanath. The study shows that, there is a significant cost saving opportunities and recommendations have been made to realize this potential.

  2. Relevance of Energy Audit [4][5][6] [7] [8][9][10][11].

    The energy audit serves to identify all of the energy streams into a facility and to quantify energy use according to discrete function.

    Energy audit can be considered as the first step towards understanding how energy is being used in a given facility. It indicates the ways in which different forms of energy are being used and quantifies energy use according to discrete functions. Energy audit does not provide the final answer to the problem. They identify where the potential for improvement lies and, therefore where energy management efforts must be concentrated.

    1. Methodology

      It is true that there is no clear-cut methodology, which can be tailor-made for conducting energy audit. Historically energy audit are broadly classified in to two types:

      Preliminary Energy Audit A preliminary energy audit study typically involves two or three days. In preliminary energy audit, the entire audit exercise can be divided into three steps:

      Step-1: Identifies the quantity and cost of various energy forms used in the plant.

      Step-2: Identifies energy consumption at the department/process level.

      Step-3: relates energy input to production, thereby highlighting energy wastage in major equipment/ processes.

      The typical output from preliminary audit assignments is:

      Set of recommendations for immediate low- cost action, and Identification of major areas/ projects, which require a more time in depth analysis.

      Detailed Energy Audit The detailed audit goes beyond quantitative estimates of costs and savings. It includes engineering recommendations and well-defined projects, and lists priorities. Approximately 95% of all energy is accounted during the detailed audit.

      The detailed energy audit which must always be conducted after a preliminary energy audit, is an instrumental survey followed by detailed plant energy analysis. Sophisticated instrumentation, including flow meters, pyrometers, flue gas analyzer and infrared scanners are used to enable the energy auditor to compute energy efficiencies and balances during typical equipment operation. The actual tests performed and the instruments required depend on the type of facility under study and objectives, scope and level of funding of the energy management program. Thus, an energy audit can take as little as one-man week or as much as several man years in a sophisticated plant.

  3. Factors affecting the operating efficiency of boiler [12] [13].

    1. Quality of coal

      In the situation we are, there is practically no or very little control of quality of fuel in general and coal i particular for our power station management. They get coal of wider variations in specification, from the designed ones. The effects due to variations are highlighted below.

      Inherent moisture With each percentage increase in moisture the loss may increase by 25 to 30 KJ/kg of fuel.

      Hydrogen The increase in wet stack losses is directly proportional to increase in hydrogen content.

      Ash The increase in ash content will lead to higher auxiliary power consumption, increase in unburnt carbon content and loss of sensible heat, increase in soot blowing frequency etc.

      Hardness More milling power and increase in unburnt carbon.

      Volatile Low volatile coals are slower burning, if the values fall below certain limits it may create problem. The fineness has also to increase; adjustments in primary air are also required.

      The Indian coals for power generation are of poor quality. High ash content and low volatile matter characterize these. Air for combustion optimization:

      The importance of correct air supplies can hardly be over emphasized. It is convenient to consider these aspects under the following heads.

    2. Total air quality

      With the reduction in total air indicated by percentage increase in carbon dioxide, the stack losses would reduce and air temperature will fall at air heater outlet. The fan power (ID and FD) will decrease, but the unburnt material will increase and also after a certain point unburnt gas may appear leading to increase in loss. The variation in coal characteristics has not much effect on optimum percentage of carbon dioxide, but the variation in load do have effect, primarily because the mixing of the fuel and air is not good. The optimum values of carbon dioxide would be lower at lower loads.

      Primary Air The primary air acts as carrier of pulverized fuel from the mills and helps to burn the volatile matter. Both the quantity and temperature of PA have significance in mill operation. The temperature required depends upon the wetness of the coal and the hot air may have to be tempered with cold air to control the temperature. The velocity of primary air passing through the mills, which is of course directly related to its volume, will affect not only the materials rejected fuel. At high velocity large size particles would be lifted and may appear a unburnt carbon in ash, while at low velocity PA may fall back to mill or if carried may separate out in PA pipes, leading to fire hazards. The frequency of soot blowing is also affected by PA variations.

      Secondary Air Variations affect the C and A loss and if reduced to very low values will also lead to unburnt gas loss, as CO will be formed. The optimum wind box pressure is formed by carrying out a series of tests to determine the combustible loss at various wind box pressure.

      The control over temperature of SA is also important, as it has a bearing on heat loss. For example, if the temperature at SA outlet is 5 C lower than the air heater outlet temperature, then the loss of heat is the equivalent of about 0.2%. Thus SA piping should have good lagging.

      Excess air This is the quantity of air required over the theoretical to ensure complete combustion. Due to the stratification of gases or other physical constraints, it is not possible to have all the oxygen molecules to come into the contact with fuel particles at right time to take part in combustion process. It is therefore operational necessity. It is imperative to regulate air supply in such a way that an optimum value is achieved, as too low a value would mean formation of CO and consequently increase in unburnt losses and higher values would tend to increase stack losses. The better mixing of PA reduces amount of excess air, which in modern boiler is in the range of 20% to 25%. The inference about the excess air can be had from oxygen or carbon dioxide indicators. The excess air can be calculated with the following formula.

      Leakage air The increase of air into the gas

      ExcessAir O2 % 100

      21 O2 %

      circuits dilutes the components of flue gases. It increases the burden on ID fans and electrostatic precipitators, as this air has not taken part in the combustion process. The errors are more significant with respect to oxygen, a 5% dilution causes an error of 19.5%. This aspect has to be taken into account when oxygen indicators are installed at the air heater outlet of gases, as there wrong inferences are likely to be drawn. The leakage of air can be calculated by using the following equation.

      % Leakage 8.2 (O2 after APH) 4.25 (O2 before APH)

      21.0 8.2 (O2 after APH)

  4. Typical losses in boiler [9].

    1. Dry flue gas loss

      This loss is arising due to heat discharged to atmosphere through the flue gases. The burning of carbon and sulphur are the main components giving rise to dry flue gases. There is not much the operator can do, expecting to control the

      temperature after air heater, keeping in view the formation of dew point temperature. Seigert formula, based upon % of carbon dioxide in flue gives the losses

      % Loss = K (T t) / (% CO2)

      Where K is 0.68 for anthracite and 0.63 for bituminous coal.

      T = Temperature at air heater gas outlet in C & t= Temperature of air at FD fan inlet in C.

    2. Wet flue gas loss

      These arise due to moisture and hydrogen in fuel. The nature and extent of losses are as follows.

      1. Moisture in fuel loss.

        The moisture that enters the combustion chamber as part of the fuel causes the heat loss because it must be heated from its initial temperature to boiling temperature then evaporated and finally superheated to leave the boiler at the same temperature as the final gases.

        Heat loss due to moisture can be calculated by the following equation.

        % Loss = M/100[1.88(T-25) + 2442 + 4.2(25 t)]

        KJ / Kg fuel

        Where M = % moisture / Kg of fuel.

        Combustion of hydrogen Hydrogen combines with oxygen in the boiler furnace producing water, it is thus necessary to evaporate water that results in loss of the boiler efficiency.

        % Loss = 9H / 100 [1.88(T-25) +2442 + 4.2(25 t)] KJ / Kg

        fuel

      2. Moisture in combustion air loss.

        Sensible heat carried away by ash The loss which is due to sensible heat in ashes, grit and dust is due to the their leaving the boiler at a relatively high

        temperature. It is entirely separate loss from that which is due to the refuse containing combustible matter.

        The amount of heat carried away by grit / dust is about 125 KJ /Kg with 10% ash in coal. Indian coals may have dust / grit as high as 40%. Thus heat loss on this account is about 500 KJ / kg.

        Radiation and unaccounted losses The radiation loss depends upon the boiler casing insulation. In modern PF fired boiler, high insulation coupled with water-cooled furnaces, the radiation losses are kept low. The losses can be reduced by taking air at FD fan inlet, as circulated through boiler columns. The % radiation loss varies with the size of unit for comparable qualities of lagging, as proportional surface area per MW decreases with increase in unit size. The unaccounted losses include heat in ash / grit, evaporation from water filled hoppers exposed to direct radiant heat from the furnace.

        Boiler loss = 100 total losses.

        Excess air

        Excess air supplied can be calculated by the below equation

        Air heater leakage Air heater leakage can be

        % Excess air supplied O2 % X100

        (21- O2 %)

        determined by following formula based on gas inlet

        and outlet analysis.

        The moisture in air exists in vapor form and thus takes heat

        % Leakage

        (Downstream O2 % – UpstreamO2 %) X100

        on account of rise of temperature from ambient to that at outlet of air heater. The loss is about 0.2% and is generally ignored.

        Gross wet flue gas loss = a + b + c

        Loss due to unburnt carbon in ash This is due to the unburnt carbon left in the fly ash or grit.The unburnt carbon depends on the quality of grinding and the distribution of different components of total air. Coarser the grinding and air supply below optimum, higher the loss. It may also be noted that over grinding increases power consumption in milling system and additional excess air, results in stack losses.

        % Loss = CA X 33820 / 100 KJ / Kg fuel

        Where C = % of carbon in ash. A = Kg ash / Kg fuel.

        (21.0 DownstreamO2 %)

  5. Efficiency evaluation of FD, PA and ID fans.

    The following observations have been made to calculate efficiency of FD, PA and ID fans.

    Total static pressure in terms of mm WC. Airflow rate in m3 /s.

    Actual power consumption in KW.

    By using above parameters, the theoretical efficiency of fans can be calculated from the below formula.

    WQh

    P The

    g KW 1000

    Where, P The = Theoretical power in KW.

    W = Weight density of air in N / m3

    hg = Total static pressure in meter of air column.

    The efficiency of fan can be calculated by the following formula.

    Table 2. Parameters of FD fan at 185 KW load

    fan

    Theoretical Power

    Parameters

    FD A

    FD B

    Inlet guide vane position

    20%

    15%

    Air flow rate m3/S

    47.52

    39.2

    Air flow rate T/h

    200

    165

    Total static pressure mmWC

    35

    27.4

    Actual power KW

    126

    108

    Parameters

    FD A

    FD B

    Inlet guide vane position

    20%

    15%

    Air flow rate m3/S

    47.52

    39.2

    Air flow rate T/h

    200

    165

    Total static pressure mmWC

    35

    27.4

    Actual power KW

    126

    108

    Actual Power X Efficiency of motor

    Efficiency of motor is taken as 0.9.

  6. Observation and Calculation.

    The various readings are considered in the table 1,2,3,4,5 and 7. Calculated results are in the table 6,8 and 9.

    Description

    Units

    Values at 185 MW

    Values at 180 MW

    Steam Flow

    T/h

    560

    545

    Steam pressure

    Kg/cm2

    136

    136

    Steam temp.

    0C

    535

    535

    Feed water temp. at ECO I/L

    0C

    242

    239

    Feed water temp. at ECO O/L

    0C

    299

    295

    PA temp. after AH A/B

    0C

    255

    255

    SA temp. AH A/B

    0C

    305

    305

    FG temp. AH I/L

    0C

    -/330

    -/330

    FG temp. AH O/L

    0C

    165/165

    162/158

    O2 temp. AH I/L

    %

    4/3

    3.2/3.0

    O2 temp. AH O/L

    %

    9.0

    8.6

    Furnace pressure

    mmWC

    -10

    -10

    Excess Air at AH I/L

    %

    20%

    17.3%

    Description

    Units

    Values at 185 MW

    Values at 180 MW

    Steam Flow

    T/h

    560

    545

    Steam pressure

    Kg/cm2

    136

    136

    Steam temp.

    0C

    535

    535

    Feed water temp. at ECO I/L

    0C

    242

    239

    Feed water temp. at ECO O/L

    0C

    299

    295

    PA temp. after AH A/B

    0C

    255

    255

    SA temp. AH A/B

    0C

    305

    305

    FG temp. AH I/L

    0C

    -/330

    -/330

    FG temp. AH O/L

    0C

    165/165

    162/158

    O2 temp. AH I/L

    %

    4/3

    3.2/3.0

    O2 temp. AH O/L

    %

    9.0

    8.6

    Furnace pressure

    mmWC

    -10

    -10

    Excess Air at AH I/L

    %

    20%

    17.3%

    Table 1. Operating Parameters of boiler-III

    Table 3. Parameters of PA fans at 185 KW load

    Parameters

    PA A

    PA B

    Inlet guide vane position

    90%

    90%

    Air flow rate m3/s

    57.6

    58.4

    Air flow rate T/h

    243

    245

    Total static pressure mm WC

    910

    860

    Actual power KW

    1080

    1170

    Table 4. Parameters of ID fan at 185 KW load with parallel operating Condition

    Parameters

    ID – A

    ID B

    ID C

    Damper Position

    100%

    open

    100%

    open

    100%

    open

    Inlet guide vane position

    100%

    open

    100%

    open

    80%

    open

    Air flow rate m3/s

    208

    108.7

    86.96

    Air flow rate T/h

    615

    321

    257

    Total static pressure mm WC

    290

    207

    204

    Actual power KW

    1138

    6636

    806

    Table 5. Coal and ash analysis

    Parameter

    Values at 185 MW

    Values at 180 MW

    Calorific value of fuel

    16027.018

    KJ/Kg

    16027.018

    KJ/Kg

    Fixed carbon

    32.63%

    32.63%

    Volatile matter

    21.27%

    21.27%

    Ash in coal

    38.57%

    38.57%

    Total PA Fan

    2250

    1006.88

    49.84

    ID Fan-A

    1138

    591.72

    57.77

    ID Fan-B

    636

    220.72

    38.56

    ID Fan-C

    806

    174.00

    23.98

    Total ID Fan

    2580

    946.44

    40.13

    Moisture

    7.53%

    7.53%

    Carbon in slag ash

    2.81%

    /td>

    2.81%

    Carbon in fly ash

    0.55%

    0.55%

    CO2 at AH O/L

    11.5%

    11.5%

    Temp. of flue gas at FD fan intake (t)

    400C

    400C

    Temp. of flue gas at AH O/L (T)

    1650C

    1600C

    Moisture

    7.53%

    7.53%

    Carbon in slag ash

    2.81%

    2.81%

    Carbon in fly ash

    0.55%

    0.55%

    CO2 at AH O/L

    11.5%

    11.5%

    Temp. of flue gas at FD fan intake (t)

    400C

    400C

    Temp. of flue gas at AH O/L (T)

    1650C

    1600C

    Table 6. Evaluation of losses at different load condition

    Particulars

    Values at 560 T/h

    Values at 545 T/h

    Dry flue gas loss

    6.84

    6.57

    Wet flue gas loss

    8.44

    8.40

    Loss due to unburnt carbon in ash

    0.8154

    0.8154

    Sensible heat carried by gas

    3.00

    3.00

    Radiation & unaccounted loss

    1.22

    1.22

    Total loss

    20.31

    20.01

    Boiler efficiency

    76.69

    79.96

    Table 7. Performance evaluation of Air Pre-heater

    Particulars

    Units

    Design

    Operation

    PA temp. after APH

    C

    335

    245

    SA temp. after APH

    C

    329

    300

    FG temp. before APH

    C

    363

    320/300

    FG temp. after APH

    C

    144

    165/165

    O2 in FG before APH

    4.3/3.6

    Parameter.

    Actual power consumed. (Kw)

    Theoretical power required. (Kw)

    Efficiency. (%)

    FD Fan-A

    126

    16.31

    14.38

    FD Fan-B

    108

    10.53

    10.84

    Total FD Fan

    234

    26.84

    12.61

    PA Fan-A

    1080

    514.19

    52.90

    PA Fan-B

    1170

    492.69

    46.78

    Parameter.

    Actual power consumed. (Kw)

    Theoretical power required. (Kw)

    Efficiency. (%)

    FD Fan-A

    126

    16.31

    14.38

    FD Fan-B

    108

    10.53

    10.84

    Total FD Fan

    234

    26.84

    12.61

    PA Fan-A

    1080

    514.19

    52.90

    PA Fan-B

    1170

    492.69

    46.78

    Table 8. Efficiency evaluation of boiler 3

    Table 9. Summary of Energy saving potential

    Sr. No

    Proposal

    Annual coal savings

    Annu al energ y saving s in Lakh Units

    Annual cost savings in Rs.Lakh

    Boiler and auxiliaries

    1.

    Efficiency of boiler improvement

    10162

    132.10

    2.

    Saving potential in PA fan by arresting air leakages in the rotary Pre- heater

    28.43

    41.22

    3.

    Stopping one of the ID fan by providing gates and rectifying inlet guide vane of fan C

    27.25

    39.52

  7. Recommendations [14][15] [16].

    Decrease Oxygen % in the flue gas at AH inlet.

    Rectify the coal burner tilting to decrease the higher surface temperature to avoid the radiation loss.

    Rectifying seals and cleaning the heat transfer fins would result in reduction in flue gas temperatures and loading on ID fans.

    Arresting leakage of primary air in to flue gas path in AH would reduce the loading of PA fan.

    Wind box damper has to be rectified to meet the required balance air from FD fans.

  8. Result & Conclusion.

    The efficiency boiler is 79.69% at 85% BMRC against the guaranteed value of 86.20% at 100% BMRC.

    The major reasons for having lower efficiency are poor quality of coal and air leakages.

    Efficiency of the boiler is increased by 0.27% by reducing air leakage about 6% in air heater.

    The efficiencies of PA, FD and ID fans are 49.84%, 12.6% and 40.11% respectively at 100% MRC.

    Excess air leakage of about 31% in to the system at AH outlet against designed value of 5-to15%.

    The annual cost saving in auxiliary power consumption of (PA+FD) and ID fans can be reduced to Rs. 41.22 and 39.52 Lakhs respectively.

    The total cost saving of auxiliary power consumption of all the fans put together is Rs. 80.74 Lakhs.

    Increasing the boiler efficiency by 1%, we can save an annual cost of Rs. 132.10 Lakhs.

  9. References.

  1. S.C.Arora and S. Domkundwar A Course in Power Plant Engineering. Dhanphat Rai & Co. (P) Ltd. Educational & Technical Publication. pp 40.1-40.9.

  2. Ronald A Zeitz Energy Efficiency Handbook Council of Industrial Boiler Owners (CIBO) Burke. pp 19-21, 35-42 available at www.cibo.org

  3. Schneider Electric SPA et al, Standard energy audit procedure Green@Hospital 2012

  4. Vipul Shah A paper on Energy Audit. pp 1-21.

  5. Amitkumar Tyagi Hand book of energy Audits and Management.Teri Publisher . pp 16-28.

  6. M. Lei, Energy-saving manuals for power generation. Beijing: China Electric Power, 2005, pp. 13.

  7. V S Verma Power on Demand by 2012, available at available at www.teriin.org

  8. Christopher B Milan A Guide book for performing walk- through Energy Audits of Industrial Facilities Bonneville PowerAdministration, pp 17-21, 37-39 available at www.bpa.gov

  9. Diane Pemberton, A paper on Energy Auditing using predictive Engineering Techniques InfraMation 2003, available at www.infraredtrading.com

  10. www.iea.org

  11. Electrical & Mechanical Services Department , Guidelines on Energy Audit The Government of the Hong Kong Special Administrative Region 2007

  12. Haryana Power Generation Corporation Ltd., Bid Document, Energy Audit Test Of 2X250 MW Unit No. 7 & 8 Panipat Thermal Power Station, Panipat NIT No. Ch-12/E-139 D/ Vol-VII Dated: 23.11.2011

  13. G.Narayana Rao, Optimization of Thermal Power Plant Workshop 01-05 July 2002 Engineering Staff College of India Campus Hyderabad.

  14. V. Stankevicius, J.Karbauskaite, R. Bliudzius A paper on Energy Audits and Real implementation Effect of Energy

    Saving Measures in schools, available at www.asi.ttassflaboratorija.html

  15. George Kanavakis, Harris Andreosatos. Audit II Country Report Bugaria, Final Report 20.11.2002, pp 8-11,available at www.motiva.fi/fi/english/attachment

  16. Ali Hasanbeigi, Lynn Price, Industrial Energy Audit Guidebook: Guidelines for Conducting an Energy Audit in Industrial FacilitiesErnest Orlando Lawrnce Berkeley National Laboratory October 2010