Enhancing the Heat Transfer Rate in Conventional Parabolic trough Type Solar Collector by Implementation of Helically Extruded-Cut Type Finned Pipe in CFD
Ommuruga P S Preethivi Raj S
Department of Mechanical Engineering Department of Mechanical Engineering
St. Josephs College of Engineering St Josephs College Of Engineering Chennai, India Chennai, India
Anto Felix Sotvik G S
Department of Chemical Engineering St. Josephs College Engineering Chennai, India
Abstract – The Absorber pipe is the heart of the heat transfer mechanism involved in a parabolic trough collector (PTC). The paper envisages the implementation of helically extruded-cut fin in the absorber pipe of a solar parabolic trough type collector and its influence in increasing the heat transfer coefficient, there by comparing each of the respective properties with the conventional plane pipe and solid finned pipe. A conventional plane pipe model has been used as a base for comparison of the two types of finned pipes and the various heat transfer properties that vary has been systematically presented using CFD. The thermal resistance property has been used as the standard of calculation. The HT domain of a PTC is designed with the fins and their contrasting heat transfer rate, hydrodynamic properties, thermal properties has been found and has been reported.
Keywords: Heat transfer, Parabolic Trough Collector, Finned Pipe, Thermal Resistance, Helical Fins, Extruded-Cut Fins.
-
INTRODUCTION
The suns total energy output is 3.8 × 1020 MW which is equal to 63 MW/m2 of the suns surface. This energy radiates outwards in all directions. Only a tiny fraction, 1.7 × 1014 kW, of the total radiation emitted is intercepted by the earth. Solar energy collectors are special kinds of heat exchangers that transform solar radiation energy to internal energy of the transport medium. The major component of any solar thermal power system using solar radiation is the solar thermal collector. This is a device that absorbs the incoming solar radiation, converts it into heat, and transfers the heat to a fluid (usually air, water, or oil) flowing through the collector. The solar parabolic trough type collector usually has concave reflecting surfaces to intercept and focus the suns beam radiation to a smaller receiving area, thereby increasing the radiation flux. Concentrating collectors are suitable for high-temperature applications. The main challenge in designing these systems is to select the correct operating temperature upto the super saturated temperature of (150oC) above which heat losses from receiver pipe occurs. This is because the efficiency of the heat engine rises as its operating temperature rises, whereas the efficiency of the solar collector reduces as its operating temperature rises. Concentrating solar collectors are used exclusively for higher operating temperature of the heat transfer fluid required. Because the maximum operating temperature for flat-plate collectors is low relative to the desirable input temperature for heat engines, and therefore system efficiencies would be very low [1]
Solar thermal power plants produce electricity by converting the solar radiation into high temperature heat using mirrors and reflectors. The collectors are referred to as the solar-field. This energy is used to heat a working fluid and produce steam. Steam is then used to rotate a turbine or power an engine to drive a generator and produce electricity all solar thermal power plants are based on four basic essential systems which are collector, receiver (absorber), transport, storage and power conversion. Parabolic Trough, Solar towers, Parabolic Dishes and Linear Fresnel Reflectors are the four main technologies that are commercially available today. The parabolic shaped dish tracks the sun, through a two axis movement, onto a thermal receiver mounted at the focal point. The concentrated beam radiation is absorbed into a receiver to heat a fluid or gas to approximately 750°C. This fluid or gas is then used to generate electricity. The estimated output from the solar power plant depends on the design parameters [2]
The parabolic-trough solar concentrators are one of the basic elements of a concentrating solar power plant. This method of concentrated solar collection has the advantage of high efficiency and low cost, and can be used either for thermal energy collection, for generating electricity. Through solar trough collector temperature increase up to 100°C to 400°C or above 400°C [3]. A lot of remarkable simulations and experiments on the efficiency of heat collection of parabolic trough collector have been studied since 1980s. In order to reduce the number of receiver elements needed in the lines, the heat transfer rate from external heat flux to the inner absorber tube should be enhanced. The effect of inserting metal foams in absorber tube on thermal-hydraulic performance increases the Nusselt number about 5-10 times with the increase of friction factor 10-20 times. The thermal losses of the enhanced tubes can be reduced by 2.23%-13.62% compared to that of the smooth tubes [4].
Convection is a process which involves mass movement of fluids. On getting heated, the fluid near the wall moves up due to the effect of buoyancy and this hot fluid is replaced by cold fluid moving towards the wall. There will always be a boundary layer adjacent to the wall, either in the natural convection or forced convection, where the temperature and velocity vary from plate to the free stream. Initially the velocity increase with increasing distance from the surface and reaches a maximum and then decrease to approach zero value. This is because of action of viscosity diminishes rapidly with distance from inner wall of the pipe, while density difference
decreases more slowly. The thermal boundary layer is considered as the stationary fluid film which is responsible for heat conduction and then heat is transported by fluid motion. The used of heat transfer enhancement has become widespread during the last so many years. The need of heat transfer enhancement is to reduce the size and cost of the equipment. This goal can be achieving in two ways active and passive enhancement. The active enhancement is less common because it requires addition of external power (e.g., an electromagnetic field) to cause a desired flow modification. In the passive enhancement, it consists of alteration to the heat transfer surface or incorporation of a device whose presence results in a flow field modification. The most popular enhancement is the fin. Fins are the extended surfaces which are used to enhance the rate of heat transfer dissipation from heated surfaces to working fluid. The application of finned tubes to the design of parabolic trough collectors has some losses as the pressure losses, thermal losses and thermo- mechanical stress and thermal fatigue. The result shows an improvement potential in parabolic trough solar plants efficiency by the application of internal finned tubes [5].
-
THE PROCESS FLOWCHART:
Fig III.1
Plane Pipe
Internally Solid
Finned Pipe
Extruded Cut
Finned Pipe
Inner
Diameter (di)
25 mm
25 mm
25 mm
Outer
Diameter (d0)
30 mm
30 mm
30 mm
Pipe
Thickness (t)
2.5 mm
2.5 mm
2.5 mm
Pipe Length
(L)
2565 mm
2565 mm>
2565 mm
Wetted
Perimeter
39.25mm
43.25mm
43.25mm
Outer Surface
Area (Ao)
0.241× 10-6
0.241× 10-6
0.254× 10-6
Inner Surface Area (Ai)
0.201× 10-6
0.261× 10-6
0.261× 10-6
Fin Profile and Path
–
Helically, internally wounded Rectangle
Helically Extruded-cut Rectangle
Fin Width
(Wf)
–
2 mm
2 mm
Fin Thickness
(tf)
–
1.5 mm
1.5 mm
Fin Length (Lf)
–
3683.22 mm
3683.22 mm
Fin Area (Af)
–
5524.83 mm2
16573 mm2
Fin Volume (V)
–
11049 mm3
8286.75 mm3
Pitch (p)
–
50 mm
50 mm
Number of
Turns (n)
–
51
51
Cross Section
A. Specifications of the receiver pipe:
Fig I
-
DESIGN MODELLING:
The design parameters are calculated from geometric relation of parabolic collector, receiver pipe and internal fin as follows (Kalogirou, 2009; CFD Analysis of a Tube with Different Internal Fin Profile, I. Satyanarayana, 2015, Design support system for PTC, D.E Woldemichael).
-
Specifications of the Parabolic Collector:
Assumptions:
Focal Length (f) = 0.55 m
Rim Angle () = 900 Aperture Length (La) = 2.525 m
Aperture Width:
Wa = 4f tan /2
= 2200 mm
Aperture Area:
Aa = Wa × La
= 5550 mm2
-
Design Rendering:
-
Plane Pipe:
TABLE I
-
Internally Solid Finned Pipe:
-
Extruded Cut Finned Pipe:
Fig III.2 The CAD rendering and the design Drafts.
B. PRE PROCESSING OF THE DOMAIN:
-
Input Parameters:
Plane Pipe
Internally Solid Finned Pipe
Extruded Cut Finned Pipe
Inlet Temperature (K)
300
300
300
Radiation Intensity over Reflector (W/m2)
600
600
600
Reflector Emissivity ()
0.9
0.9
0.9
Velocity Magnitude (m/s)
0.01
0.01
0.01
Heat transfer fluid
Water
Water
Water
Pipe Material
Aluminium
Aluminium
Aluminium
Reflector Material
Aluminized Mirror
Aluminized Mirror
Aluminized Mirror
Thermal
Conductivity (W/mK)
200
200
200
Heat Transfer Rate of Air hair, (W/m2K)
50
50
50
Viscous Model
K-epsilon
K-epsilon
K-epsilon
Table II
The Radiation conditions were assumed to be same as that occurs at the Black Rock Desert Mojave, CA.
-
Meshing of CFD Domain:
Fig IV.1 The PTC Domain
Fig IV.2 Concentric Pipe Domain
-
GOVERNING EQUATIONS
There are Three Equations Used for Flow Analysis they are:
-
Continuity Equation:
-
Momentum Equation:
-
Energy Equation:
-
Plane Pipe:
-
-
-
-
ANALYSIS AND RESULTS.
-
Helically Extruded-cut finned Pipe:
The results of the analysis of the collector tubes of
type:
The results of the analysis of the collector tubes of Plane
extruded-cut type:
-
Post processed results of the domain:
A.1. Post processed results of the domain:
Fig VI.1 Temperature Contour
Fig VI.4 Temperature Contour
Wall heat transfer coefficient contour:
Outlet Temperature (K)
Plane Pipe
321
Internally Solid Finned Pipe
337
Extruded Cut Finned Pipe
346
-
-
Corresponding Plots
-
Plane Pipe:
Table III
Fig VI. 2. Temperature contour of the PTC domain
-
Internally Solid Finned Pipe:
The results of the analysis of the collector tubes of Internally solid finned type:
B.1 Post processed results of the domain:
Fig VI.3 Temperature Contour
Fig VI.5 Surface heat transfer Coefficient
Fig VI.6 Surface Nusselt Number
-
-
Internally Solid Finned Pipe:
Fig VI.7 Surface Heat Transfer Coefficient
Fig VI.8 Surface Nusselt Number
-
Helically Extruded-cut finned Pipe:
-
Fig VI.9 Surface heat transfer Coefficient
Fig VI.10 Surface Nusselt Number
Fig VI.11 (Surface Heat Transfer Coefficient VS Concentric Pipe Length of Three Types of Pipe)
From the above plot (Fig VI.11) the mean surface heat transfer coefficient between concentric pipes are:
Mean Heat Transfer Coefficient, hin (W/m2K) |
|
Plane Pipe |
52.5 |
Internally Solid Finned Pipe |
92.83 |
Extruded Cut Finned Pipe |
113.3 |
Table IV
So the (Table IV) shows the mean heat transfer coefficient of the Extruded Cut Finned Pipe is higher than the Plane Pipe and Internal Solid Finned Pipe due to higher outer surface area of the Extruded Cut Finned Pipe results in lower the convection and radiation resistance and also lower the volume of the Extruded Cut Fin comparing to Solid Fin will lower the conduction resistance through receiver pipe.
-
THERMAL RESISTANCE:
Thermal Resistance is a property of heat transfer and the measurement of amount of resistance an object offers to the heat flow. Thermal Resistance of a medium depends on the geometry and the thermal properties of the medium.
Conduction Resistance can be reduced by:
-
Reducing the thickness of the material and increasing the surface area of the material. So in Helically Extruded-Cut Fin the thickness of the material is reduced and the surface area of the material is increased, while comparing with Helical Solid Fin.
Convection and Radiation Resistance can be reduced by:
-
Increasing the surface area of the material. So the overall outer surface area of the Helically Extruded-Cut Finned Pipe is maximum than the Helical Solid Finned Pipe and Plane Pipe.
Convection Resistance:
Rconv outer = [1/ 2L] × [1/ha×ro]
= 0.08277 K/W
Rconv inner= 1/[hin×Ai]
-
-
RESISTANCE CALCULATIONS
-
Plane Pipe:
Radiation Resistance:
= 0.0498 K/W
Conduction Resistance:
Rcond = [1/2KL] × ln [ro / ri]
= 5.659 × 10-5 K/W
Convection Resistance:
Rconv outer = [1/ 2L] × [1/ha×ro]
= 0.08277 K/W
Rconv inner = [1/2L] × [1/hin×ri]
= 0.0945 K/W
Radiation Resistance:
Rrad pipe = [1-]/ [A0×]
= 0.461 K/W
Surface Area of Reflector (Aref) = 5.77 m2
Rrad reflector = [1-]/ [Aref×]
= 0.019 K/W
Roverall rad = .019 + 0.461
= 0.48 K/W
Overall Resistance of Plane Pipe:
Roverall= 1 / [ [Roverall rad + Rconv outer ]/[Roverall rad×Rconv outer]] + Rcond
+ Rconv inner
= 0.1651 K/W
-
Internally Solid finned Pipe:
Rrad pipe = [1-]/ [A0×]
= 0.461 K/W
Surface Area of Reflector (Aref) = 5.77 m2
Rrad reflector = [1-]/ [Aref×]
= 0.019 K/W
Roverall rad = 0.019 + 0.461
= 0.48 K/W
Overall Resistance of Plane Pipe:
Roverall= 1 / [[Roverall rad + Rconv outer]/ [Roverall rad×Rconv outer]]
+ Rcond1 + Rconv inner + Rcond2
= 0.1222 K/W
-
Helically Extruded-cut finned Pipe:
Fig VIII.2 CS of Extruded-Cut Fin
Length of tube with helically extruded-cut (Lc) = 2.496 m
Conduction Resistance:
-
Resistance through the pipe with helically extruded-cut: Rcond1 = [1/2KLc] × ln [ro / ri]
= 5.8152 ×10-5 K/W
Conduction Resistance:
Fig VII.1
-
Resistance through the Helically Extruded-cut fin:
-
Rcond2 = /[×f]
= 0.001415 K/W
Convectional Resistance:
Rconv outer = 1/[ha×Ao]
= 0.0787 K/W
-
Resistance through pipe:
Rcond1 = [1/2KL] × ln [ro / ri]
= 5.659 × 10-5 K/W
-
Resistance through helical inner solid fin:
Rcond2 = /[×f]
= 0.00181 K/W
Rconv inner = 1/[hin×Ai]
= 0.04163 K/W
Radiation Resistance:
Rrad pipe = [1-]/ [A0×]
= 0.4362 K/W
Surface Area of Reflector (Aref) = 5.77 m2
Rrad reflector = [1-]/ [Aref×]
= 0.019 K/W
Roverall rad = 0.019 + 0.4362
= 0.4552 K/W
Overall Resistance of Plane Pipe:
Roverall= 1 / [ [Roverall rad + Rconv outer ]/[Roverall rad×Rconv outer]] + Rcond
+ Rconv inner
THERMAL RESISTANCE (K/W)
= 0.1093 K/W
0
5.659E-08
0.00181
0.001415
Solid Fin Pipe
Cut Fin Pipe
and increases the kinetic energy and the velocity of the working fluid that flows through it. So future holds a key for PTC technology in the application of extruded-cut type finned collector tubes.
IX REFERNCES
-
Solar energy engineering : processes and systems / Soteris Kalogirou.
1st ed. ISBN 978-0-12-374501-9
-
Performance of solar power plants / Dr.B D Sharma.
0.18
0.16
0.14
0.0701
0.12
0.1
0.0701
0.08 0.0666
0.06
0.0945
0.04
0.0507
0.04163
0.02
-
New Trends in Designing Parabolic trough Solar Concentrators and Heat Storage Concrete Systems in Solar Power Plants /Valentina A. Salomoni, Carmelo E. Majorana, Giuseppe M. Giannuzzi, Adio Miliozzi and Daniele Nicolini.
-
Numerical study on heat transfer enhancement in a receiver tube of parabolic trough solar collector with dimples, protrusions and helical fins / Z. Huanga, G.L. Yua, Z.Y. Lia*, W.Q. Taoa.
-
CFD analysis of a tube with different internal fin profiles / Dr.I. Satyanarayana, Ava Mallesh, P.Chandrashekar.
-
Maximising the heat transfer through fins using cfd as a tool /Sanjay Kumar Sharma and Vikas Sharma
-
Design support system for PTC , D.E Woldemichael ISSN 1812-5654
-
Calculation of finned tube pressure drop and heat transfer using fully three-dimensional CFD methods. / Christopher J. Matice, P.E., Brian Gao,Stress Engineering Services, Inc.
-
Heat Transfer A practical Approach , II edition ,Yunus A. Cengel.
-
The Science portal ,Wikipedia.com , Wikimedia Inc.
Convection Resistance on inner wall surface of pipe (K/W)
Conv+Rad Resistance on outer wall surface of pipe (K/W)
Plane Pipe
Conduction Resistance (K/W)
TABLE VII.1 Comparison of thermal resistance for three concentric pipe types
III CONCLUSION
Thus the Thermal performance of all the three types of collector tubes of the PTC were analyzed and it has been arrived that implementation of the extruded cut finned type collector tube shows minimum thermal resistance and maximum overall heat transfer coefficient .This is attributed due to the geometrical exposure of the high heat transfer area of the extruded-cut finned type collector tube to the radiation from the trough which considerably gets heated more than the other types. This increase directly affects the Nusselt number which is the index of thermal conductivity and the convective efficiency happening in real-time. As far as the hydro- dynamical aspect of heat transfer is considered, in the extruded-cut type finned tube it is similar to the internally solid finned tubes as both of the tubes causes turbulence dissipation