Fault Ride Through Analysis Of Wind Farm In Low Voltage Distribution System
Manju Aggarwal, S. K. Gupta, Madhusudan Singh
Apeejay Stya University, Sohna, Haryana, India, DCRUST, Murthal, Haryana, India Delhi Technological University, Delhi, India
Abstract
In this paper, a wind farm comprising of squirrel cage induction generators (SCIG) is described and impact of different types of faults, balanced and unbalanced, at different locations in low voltage distribution system has been analyzed. A distribution Static Compensator (DSTATCOM) is being used for Fault Ride through (FRT) analysis of wind farm in low voltage distribution system. The role of a DSTATCOM is to enhance the capability of wind farm as required by grid code for grid below100kV.
-
Introduction
Today, modern energy industry faces a growing awareness regarding the impact of conventional power generation on the environment. Issues such as limited fossil fuel reserves, climate change due to CO2 emissions, brings to attention alternative technologies [1-2] to generate electricity in a more sustainable manner. Wind power is the worlds rapid growing source of energy. The penetration of wind power in the electrical grids increases steadily in many European countries, with highest percentage found in Denmark (28%). Increasing penetration of wind turbines into grid system has led system operator to develop new grid codes. Grid code describes the connection condition of wind turbines to grid. The grid codes are mainly related to fault ride through (FRT) capability, power quality issues, grid stability, and reactive power control of wind turbines. Connection requirements of wind power generating units have been explained in [3-7]. Six Grid Codes are selected for the analysis of a generic Grid Code. Among the chosen Grid Codes is Denmark due to the high penetration of wind power. Ireland, EON
[8] (a German transmission system Operator (TSO)),Scotland and the UK. The Grid Code of Germany is chosen due to the important wind power market and due to detailed technical descriptions in the Grid Code of EON. The squirrel cage induction generators (SCIG) which typically employ a conventional induction machine, is simpler in design and do not incorporate power electronics and thus do not have issues related to harmonic injection into the system. However, the wind turbines drain large amount of reactive power from the grid which causes low voltage. Reactive power capacity of SCIG [9-14] can be controlled by using shunt capacitors during steady state operation. However, reactive power injection capability decreases during fault conditions therefore, these devices require some additional power electronic compensation devices to fulfil FRT capability. Among other devices DSTATCOM is best suited for such applications as DSTATCOMs are faster, smaller and have better performances at reduced voltages.
This paper explains the analysis of different types of faults i.e. unbalanced and balanced, at different location in low voltage distribution system. The role of DSTATCOM [15-20] is to enhance the FRT capability of wind farm as required by grid code. The fault ride through (FRT) capability, which is one of the most demanding requirement that have been included in the grid codes and shown in Fig.1.The wind turbine should remain stable and connected during the fault while voltage at the PCC drop to 15% of the nominal value
i.e. drops of 85% for the part of 150 msec. Only when the grid voltage falls below the curve, the turbine is allowed to disconnect from the grid.
V(pu)
100%
95%
60%
-
System modelling
-
Model equations of wind turbine
A wind farm consists of several wind generators connected to the grid system through a single bus. Equivalent model of wind farm [21-22] can be built by combining all wind turbines into single equivalent turbine. By Betz theory, power extracted from air through wind turbine is given by
30%
15%
0 150 3000
(2)
(3)
Whereis the power absorbed, is the mechanical output power of the turbine is the performance coefficient of the turbine, is the ratio of
Fault occured
Time(ms)
the rotor blade tip speed to wind is the air density (Kg/ m3) is the blade pitch angle in
Fig. 1. Fault Ride Through (FRT) capability
-
-
-
System Configuration
The proposed system consists of 11kV, 450kVA, 50Hz low voltage distribution system along with a wind energy conversion system (WECS) connected directly to the grid and DSTATCOM as shown in Fig.2. The distribution system consists of a11kV/415V transformer and a feeder. Voltage at the point of common coupling (PCC) is 415V. Wind farm comprising of three 7.5kW Squirrel Cage Induction Generators (SCIG) driven by fixed speed wind turbines. A DSTATCOM supplies the lagging or leading current to manage the constant terminal voltage at PCC during fault conditions.
Wind Farm
radian, R is turbine radius in meters, is the wind speed in m/s. The equation for is given by
(4)
With (5)
Power coefficient is the function of tip speed ratio and blade pitch angle. In order to achieve , optimal value of tip speed ratio and blade pitch angle is required and therefore giving the
Pgrid,Qgrid
Zs
Qig
ig1
ig2
maximum power output at all available wind speed. Optimal value of can be achieved at one optimal
AC 11kV/415 V
Feeder
Pig
ig3
value of tip speed ratio i.e. . So it is required to
11kV,450kVA
.
Control Scheme
Vdc
Qstat
Va,Vb,Vc
istat
load
load
PL,QL
iL
control tip speed ratio according to wind speed which is known as maximum power point tracking. Active pitch control is used mainly for high wind speed. In the present analysis pitch angle is zero which is a valid assumption for low to medium wind speed. In this analysis the system maximum value of power
coefficient is 0.48 .
Fig. 2. Basic Structure of Test System
-
DSTATCOM Control algorithm
Basic working principle of DSTATCOM is described by the following equations. The instantaneous value of current are written using Kirchoffs current laws as
(6)
(7)
Where are the grid current, load current, compensator current and wind farm current current supplied by each wind generator
Compensating currents provided by DSTATCOM to make utility voltage purely sinusoidal are given as
(8)
The main current needs to be sinusoidal for ideal compensation; irrespective of the nature of the load based on the generation of source currents components.
(11)
The in phase component of reference currents are derived using in phase unit vector template as
(12)
(13)
(14)
Whereis the output of PI controller regulating dc bus voltage of DSTATCOM. Quadrature components of reference current are obtained as follows
(15)
(16)
(17)
Quadrature component of reference source
Vdc* Vdc
ua,ub,uc
ida
idb idc
c
c
isab *
Switches S1-S8
PI
controller
Id
PI
controller
Id
Hystersis current controller
/tr> Hystersis current controller
current) is calculated by
(18)
Va
PLL
Unit
Vb
Vc
Vtref
Vt
Vector Template
Quadrature Template
PI
controller
Iq
PI
controller
Iq
Wa,Wb,Wc iqa iqb
iqc
To VSC
(19)
(20)
Where is obtained by by comparing it with the reference voltage i.e. maximum value of desired A.C voltage (Vtref) at PCC. PI controller processes the
Fig. 3. Control scheme of DSTATCOM
Control scheme of DSTATCOM is shown in Fig.3. Reference source currents are the sum of direct and quadrature axis currents. Direct axis currents (idabc) are derived by first calculating unit vector template from a phase locked loop (PLL) by generating angle as
(9)
(10)
voltage error. The amplitude of reactive current to be produced by the STATCOM is decided by the output of the PI controller in AC voltage control loop. In inner current loop hysteresis current controller is used, where source currents are compared with reference current derived from outer loop. This enables the source current controlling to be sinusoidal. This method is simple, robust and favorable as compared with other methods.
-
Simulation results and discussion
Fault ride through analysis of wind farm with and without static compensator is analyzed for various types of faults, at different location in low voltage distribution system. The proposed scheme is modeled and simulated in MATLAB/simulink. The r.m.s value of voltage at point of common coupling (Vpcc), rms voltages of each phase (Vabc), rotor speed (w), and reactive power of wind generators (Qig) are presented with and without controller. Positive values of active / reactive power of wind generator and DSTATCOM imply that these powers flow towards PCC.
-
Analysis of low voltage distribution system with Line to line fault near grid without/with controller
In order to analyze the behavior of the 11kV, 450kVA, and 50Hz low voltage distribution system following unbalanced fault, a line to line fault has been simulated near grid. Line to line fault is applied at t = 1.0s and clearance time is 150ms. Fig.4 presents the voltage at the point of common coupling (Vpcc), rms voltages of each phase (Vabc), speed of rotor (w), reactive powers absorbed by the generators (Qig) and Fig.5 presents reactive power injected by DSTATCOM and dc link voltage (Vdc) in addition to waveforms of Fig.3.
Fig. 4. R.m.s.voltage at the point of common coupling(Vpcc), rms oltages of each phase at pcc(Vabc), speed (w ), reactive power absorbed by wind farm(Qig), without DSTATCOM
It has been observed from that DSTATCOM helps in reducing the voltage dip and time to clear fault by supplying reactive power during fault. Frequency increases to 1.2pu without controller but with DSTATCOM it is within range i.e. 1.05pu. The values of voltage at point of common coupling and time to clear the fault for different types of fault at different location has been given in Table1.
Fig. 5. R.m.s.voltage at the point of common coupling(Vpcc), rms voltage aof each phase at pcc, speed (w ), reactive power absorbed by wind farm(Qig), reactive power injected by DSTATCOM(Qstat),dc link voltage(Vdc)
-
Analysis of low voltage distribution system with three phase fault near grid without/with controller
To analyze the behavior of the system with balanced fault, three phase fault has been simulated near grid. Fig.6 shows that the voltage at the point of common coupling drops below 0.15pu during fault occurrence which leads to disconnection of wind turbine from the grid as depicted in Fig1. DSTATCOM helps to avoid such situation by supplying reactive power as observed from Fig.7 hence, contributing to FRT enhancement
Fig. 6. R.m.s.voltage at the point of common coupling(Vpcc), rms voltage aof each phase at pcc, speed (w ), reactive power absorbed by wind farm(Qig), without DSTATCOM
Fig. 7. R.m.s.voltage at the point of common coupling(Vpcc), rms voltage aof each phase at pcc, speed (w ), reactive power absorbed by wind farm(Qig), reactive power injected by DSTATCOM(Qstat),dc link voltage(Vdc)
-
Analysis of low voltage distribution system with Line to line fault at pcc without controller
Now, the system is analyzed with same type of faults
i.e. balanced and unbalanced. However, the location is weakest point i.e. point of common coupling because at this point where the wind turbine is connected to low voltage distribution system and from this point the wind
turbine takes its reactive power and sends its generated power to the grid.
Fig. 8. R.m.s.voltage at the point of common coupling(Vpcc), rms voltage aof each phase at pcc, speed (w ), reactive power absorbed by wind farm(Qig), without DSTATCOM
Fig. 9. R.m.s.voltage at the point of common coupling(Vpcc), rms voltage aof each phase at pcc, speed (w ), reactive power absorbed by wind farm(Qig), reactive power injected by DSTATCOM(Qstat),dc link voltage(Vdc)
Line to line fault is applied between phase a and phase
b. The contribution of DSTATCOM is very little in case of a fault as the voltage drop in fault condition is major, hence reactive power injection is limited. Instead, DSTATCOM plays a vital role in post fault clearance scenario when it injects reactive power as per its rated capacity to help recover the voltage faster and hence improving the system stability
-
Analysis of low voltage distribution system with three phase fault at pcc without controller
For the three phase balanced fault at pcc, the DSTATCOM do not have the ability to let the wind turbine ride through this type of fault because voltage on its terminal will be zero. After the fault clearance DSTATCOM helps in reducing the time to clear the fault.
Fig. 10. R.m.s.voltage at the point of common coupling(Vpcc), rms voltage aof each phase at pcc, speed (w ), reactive power absorbed by wind farm(Qig), without DSTATCOM
Fig. 11. R.m.s.voltage at the point of common coupling(Vpcc), rms voltage aof each phase at pcc, speed (w ), reactive power absorbed by wind farm(Qig),a active power injected by DSTATCOM(Qstat),dc link voltage(Vdc)
TABLE 1. rms voltages at pcc and time to clear fault for different types of fault at different location
Location of fault
Type of fault
Vpcc t=1s t=1.15
Time to clear fault
Near Grid
Three phase
fault
Without controller
0
0.24s
With controller
0.2pu
0.1s
Near Grid
L-L
Fault
Without controller
0.22pu
0.15s
With controller
0.54pu
0.02s
At point of common coupling
Three phase
fault
Without controller
0
0.25s
With controller
0
0.11s
At point of common coupling
L-L
Fault
Without controller
0.22pu 0.32pu
0.15s
0.05s
With controller
0.32pu
0.05s
TABLE 2. rm voltages at pcc and time to cear fault for different types of fault at different location
Location of fault
Rms voltage of each phase
Without controller
With controller
Near grid
Va
0.19pu
0.62pu
Vb
0.44pu
0.74pu
Vc
0.45pu
0.93pu
At pcc
Va
0.22pu
0.32pu
Vb
0.22pu
0.33pu
Vc
0.45pu
0.63pu
-
-
Conclusion
-
This paper analyzes the impact of different types of faults at different location, in low voltage distribution system with and without DSTATCOM. Results shows that DSTATCOM helps in providing voltage support following voltage dips that arise from external short- circuits occurrence. DSTATCOM is considered as an effective means of enhancing the FRT capability of wind farm.
-
Appendix
The parameters of 11kV, 450kVA, and 50 Hz low voltage distribution system are given below:
SCC=450kVA, X/R =7
Feeder parameters: R= 0.2 , L=4.4mH
Following are the parameters of 7.5kW, 415V, 50Hz, 4- pole Y – connected induction machine:
Rr =0.03pu, Rs = 0.035pu, Xlr = Xls= 0.062pu, J = 0.1384 kg-m2
DSTATCOM Parameters:
Lf = 5mH, Rf = 0.01, Vdc=700volts and Cdc = 8000uF
Parameters of AC voltage regulator Kiq = 0.008, Kpq = 0.5
Parameters of DC voltage regulator Kid = 10, Kpd = 0.6
Wind turbine Characteristics: Three turbines of rating 7.5kW Cp=0.48, µ = 8.1
c1 = 0.5176, c2 = 116, c3 = 0.4, c4 = 5, c5 = 21 and c6
= 0.006
-
References
EKANAYAKE,J. B.,and STRBAC, G., Trends in wind power technology and grid code requirements,proc.International Conference on Industrial and Information Systems, no. pp.129-134,
Aug.2007
[4]. EL-HELW, H. M., TENNAKOON, and S. B.,Evaluation of the suitability of a fixed speed wind turbine for large scale wind farms considering the new UK grid code, Renewable Energy 33 (2008) 1-12.
[5]. Sharad W. Mohod, and Mohan V. Aware, A Statcom Control Scheme for Grid Connected Wind Energy System for Power Quality Improvement, IEEE Transaction on System Journal, Vol. 4, No. 3, pp. 346- 352, Sept. 2010 [6]. Arulampalam, M. Barnes, N. Jenkins, and J. B. Ekanayake, Power quality and stability improvement of a wind farm using STATCOM supported with hybrid battery energy storage, IEE Proc. Generation, Transmission and Distribution, vol. 153, no. 6, pp.701- 710, Nov. 2006 [7]. M. Tsili and S. Papathanassiou, A review of grid code technologyrequirements for wind turbine, Proc. IET Renew. power gen., vol. 3,
pp. 308332, 2009
[8]. I. Erlich, W. Winter, and A. Dittrich, Advanced grid requirements for the integration of wind turbines into the German transmission system, in Power Engineering Society General Meeting, 2006. IEEE, 18-22 June 2006,p. 7pp.
[9]. S. M. Alghuwainem, R. A. Hammouda, and A.-R. M. Al-Farhan, Transient analysis of a wind-driven induction generator, in Proc. Canadian Conf. Electrical Computer Engineering, vol. 2, 2001, pp. 1316. [10]. D.J. Trudnowski, A. Gentile, M. Khan and E.M. Petritz, Fixed-Speed Wind-Generator and Wind-Park Modeling for Transient Stability Studies, IEEE Trans.Power Syst., Vol. 19, No. 4,November, 2004
[11]. L. M. Fernandez, J. R. Saenz, and F. Jurado, Dynamic models of wind farms with fixed speed wind turbines, Renewable Energy, vol. 31, pp.1203 -1230, 2006. [12]. Y. Uctug and M. Demirekler, Modeling, Analysis and Control of a Wind-Turbine Driven Self-Excited Induction generator, IEE Proceedings Generation, Transmission and Distribution, Vol. 135, No. 4, July 1988. [13]. L.Holdsworth, X.G.Wu, J.B.Ekanayak and Jenkins,Comparison of Fixed-speed and doubly-fed Induction Generator Wind Turbines during Power System Disturbances, IEE proceedings C- Gener.Transm., Distrib. vol.150, no.3, pp.343-352, july2003
[14]. L. Holdsworth, X. G. Wu, J. B. Ekanayake, and N. Jenkins, Comparison of fixed speed and doubly-fed induction wind turbines during power system disturbances, Proc. Inst. Elect. Eng., Commun., vol.150, no. 3, pp. 343352, May 2003
[15]. Gaztañaga, I. Etxeberria-Otadui, D. Ocnasu, and S. Bacha, Real-time analysis of the transient response improvement of fixed-speed wind farms by using a reduced-scale STATCOM prototype, IEEE Trans Power Syst., vol. 22, no. 2, pp. 658666, May 2007. [16]. M. Molinas, J. A. Suul, and T. Undeland, Wind farms with increased transient stability margin provided by a STATCOM, in Proc. Int Power Electron. Motion Contr. Conf. (IPEMC06), Shanghai, China, Aug. 16, 2006, vol. 1, pp. 6369. [17]. M. Molinas, J. Kondoh, J. A. Suul, and T. Undeland, Reactive support for wind and wave farms with a STATCOM for integration into the power system, in Proc. Renewable Energy Conf., Makuhari, Japan,Oct. 913, 2006, pp. 16651668. [18]. G. Chicco, M. Molinas, T. Undeland, and G. Viglietti, Improvement of the transient stability margin in wind systems with a STATCOM, in Proc. VI World Energy Syst. Conf., Torino, Italy, Jul. 12, 2006, pp. 371 376. [19]. W. Xueguang, A. Atputharajah, Z. Changjiang, andN. Jenkins, Application of a static reactive power
compensator (STATCOM) and a dynamic braking resistor (DBR) for the stability enhancement of a large wind farm, Wind Eng., vol. 27, no. 2,2003
[20]. Alex Q. Huang, Mesut E. Baran, Subhashish Bhattacharya, Wanye Litzenberger, Loren Anderson, Anders L.Johnson and Abdel-Aty Edris, STATCOM Impact Study on the Integration of a Large Wind Farm into Weak Loop Power System, IEEE Transaction on Energy Conversion,Vol.23, No. 1, pp. 226-233, March 2008. [21]. L. M. Fernandez, J. R. Saenz, and F. Jurado, Dynamic models of wind farms with fixed speed wind turbines, Renewable Energy, vol. 31, pp.1203 -1230, 2006. [22]. Z. Saad-Sauoud and N. Jenkins, Simple wind farm dynamic model, IEE Proc. Generation, Transmission, and Distribution, vol. 142, no. 5, pp. 545-548, Sept.1995.