Harmonic Compensation of Controlled & Uncontrolled Loads by using Sahf

DOI : 10.17577/IJERTV5IS100196

Download Full-Text PDF Cite this Publication

  • Open Access
  • Total Downloads : 164
  • Authors : Smt. Smita Singhai, Prof. Umesh Yadav, Prof. Versha Singh, Prof. Dr. S. Gupta
  • Paper ID : IJERTV5IS100196
  • Volume & Issue : Volume 05, Issue 10 (October 2016)
  • DOI : http://dx.doi.org/10.17577/IJERTV5IS100196
  • Published (First Online): 17-10-2016
  • ISSN (Online) : 2278-0181
  • Publisher Name : IJERT
  • License: Creative Commons License This work is licensed under a Creative Commons Attribution 4.0 International License

Text Only Version

Harmonic Compensation of Controlled & Uncontrolled Loads by using Sahf

Smt. Smita Singhai1, Prof. Umesh Yadav2, Prof. Versha Singp, Prof. S. Gupta4 Department of Electrical Engineering, National Institute of Technology,

Raipur (C.G.)(INDIA)

AbstractIn this paper ,three phase shunt active harmonic filter is used for harmonic compensation of controlled & uncontrolled loads by using phase locked loop techniques with new synchronized pulse generator. The circuit model consists of a standard shunt SAHF with IGBT inverter used for harmonic elimination of controlled & uncontrolled loads. PLL is used for generating a sinusoidal output & Synchronized pulse generator is used for giving firing pulse to controlled converter used as one of a Non-Linear load. The SAHF uses a PLL with adaptive filter to generate a reference sinusoidal source current which is in-phase with load current and has the same RMS gain as the load current. Hysteresis switching is used for Current control. In Hysteresis switching method, a hysteresis band is formed & within the band, the shunt line current tracks the reference current In this way Hysteresis Switching is used for producing the reference signal for the IGBT inverter & also the synchronized pulse generator is used for generating firing pulse for 3-phase controlled rectifier used as one of non-linear load.

KeywordsShunt Active harmonic filter (SAHF), IGBT inverter, Series Inductor, Phase locked loop (PLL), Hysteresis Switching (HS), Point of common coupling (PCC), Synchronized pulse generator.

  1. INTRODUCTION

    Many industrial & Domestic load posses non-linear behavior, examples are Controlled and Uncontrolled rectifiers, welding transformer, switched mode power supply (SMPS), arc furnaces, various motor drive applications etc. All these Nonlinear loads cause distortion in voltage and current waveforms due to presence of various orders of Harmonics reactive power and resonance problems, higher transformer and line losses, over-voltages, over-heating, Electro Magnetic Interference (EMI) problems, and other Power Quality Issues. All these undesirable effects result in reducing system stability [1] -[3]. Traditionally various types of Passive filters alone have been used to eliminate the harmonics due to their lower cost and higher efficiency. However, these filters have multiple drawbacks including fixed compensation affecting sometimes the voltage regulation at the PCC at fundamental frequency. Therefore, Active Harmonic Filters (AHF) or Active Power Line conditioners(APLC) are recently used for solving these power quality problems in many Industrial applications . The classification of AHF is Shunt Active harmonic filter, Series Active Harmonic filter, combination of both or with passive

    & active filters together called Hybrid Active harmonic filter[4]. The Shunt AHF is suitable for current based & reactive power compensation. The Series AHF is suitable to suppress voltage harmonics, voltage flicker & to decrease voltage unbalance. The combination is called Unified Power Quality Conditioner which is the best solution for Active filtering[6]. All these type of AHF has ability to compensate all the harmonics and reactive power and after compensation keeps the system balanced irrespective of the load; i.e., nonlinear and or balanced and unbalanced [5][7-11].

    In this paper, we proposes SAHF of which most significant part is PLL & HS used to estimate the reference current and control the dc-bus capacitor voltage of the inverter. A PLL is feedback system that fixes relation between output phase and input phase that are synchronized or locked, thats why the name called Phase Locked Loop. The hysteresis switching current control technique has been the most suitable technique for all the applications of VSI in SAHF , the used active power Filters in this paper. The present hysteresis band current controller having property of unconditioned stability, high speed response, and good accuracy [12-14].The proposed shunt active harmonic filter is validated and investigated for two nonlinear loads in which one is controlled load & another one is uncontrolled load. The used one of controlled non-linear load getting a firing pulse from Synchronized 6-pulse generator.

  2. PROPOSED CONTROL STRATEGIES

    Proposed methodology uses PLL & HS controlled shunt AHF to reduce the harmonic and unbalance problems from the combination of controlled & uncontrolled non-linear loads. The shunt AHF with IGBT inverter & HS is installed at the Point of Common Coupling (PCC). The three-phase shunt active harmonic filter is a three phase current controlled voltage-source inverter (VSI) with a mid-point earthed, split capacitor in the dc bus.

    Figure2 .6-Pulse Synchronizing Generator

    Figure1.Proposed Active Power Filter Configuration

    It consists of two Non-linear loads in which one is Uncontrolled & another one is Controlled load. Both are phase-shifted by 30 degrees. For obtaining 30 degree phase shift in between two loads, the Controlled load is connected in Delta-Delta form and Uncontrolled load in Delta-Star form. The Delta-star connected uncontrolled rectifier is connected with Delta-Delta form Controlled load by a transition switch initially closed having transition time 5/60 sec to change the load output. The Active harmonic filter uses a PLL & HS to generate harmonic free output current which is in-phase and has the same RMS gain as the reference current. The current error in between the load current and the reference current is generated by the IGBT Bridge Inverter through hysteresis switching. The Proposed Control strategies uses two loads in which one is controlled & another one is uncontrolled loads. The controlled load gets firing pulse from Synchronized 6-pulse generator circuit.

  3. SYNCHRONISED 6-PULSE GENERATOR, PHASE LOCKED LOOP (PLL) & HYSTERESIS

    SWITCHING (HS)

    1. Synchronized 6-Pulse Generator:

      The Synchronized 6-Pulse Generator block can be used to give firing pulse to fire each of the six thyristors of six-pulse converter. The input of the Generator having five inputs. Input 1 is the alpha firing signal in Degree. Input (2 to 4) are the phase to phase synchronizing voltages. Synchronizing voltages should be in phase with three phase voltages at converter AC terminal. AB, BC , CA are the line voltages. Input 5 allows us to Block the operation of Generator. The pulses are disabled when applied signal is greater than zero. The output of the block is a vector of six pulses which are individually synchronized on the six thyristor voltages. The pulses are generated by synchronized 6- pulse generator by an alpha degrees after increasing zero crossings of the thyristor commutation voltages.

      The figures below display the synchronization of the six pulses generated by pulse Generator for firing angle of 0 degree. The pulses are generated exactly at the zero crossings of the three line-to-line synchronization voltages AB, BC and CA.

      Figure3 .6-Pulse Synchronizing Generator for alpha=0°

      The Synchronized 6-Pulse Generator block can be designed to work in double-pulsing mode. In this mode two pulses are sent to each thyristor of 6-pulse Generator, when the alpha angle is reached, first pulse is given, second pulse is given after 60 degrees later. The figures below shows the synchronization of the six pulses for an alpha 30 degrees and with double-pulsing mode. The pulses are generated 30 degrees after the zero crossings of the input supply voltage (line-to-line).

      Figure4 .6-Pulse Synchronizing Generator fr alpha=30°

    2. PLL Introduction:

      Various methods of synchronization techniques are presents todays. They are m a i n l y classified as open- loop and closed- loop techniques. Open-loop technique directly estimates the phase angle of the input voltage and input current signals. In closed-loop methods, the estimation of the phase is adaptively updated through a loop mechanism having self locking tendency. PLL is Negative feedback control system where output frequency ( fout) tracks with the input frequency ( fin) and rising edges of input clock approaches align to rising edges of output clock.

      Mathematical equation of frequency synthesizer-

      () sin(2()) [phase locked loop]

      () = sin(2())

      When phase-Locked,

      = fout =N fin

    3. Proposed PLL:

      Proposed methodology of PLL for estimation of reference current is shown in figure 5. In proposed scheme of PLL the load current, input frequency and terminal voltage are the inputs. Firstly, the distorted three phase supply voltages are sensed and given to the proposed PLL which generates sine terms. The supply voltage is multiplied with a suitable gain of values K=1N before being given as an input to the PLL.

      Figure 5. Simulation Model of Shunt Power Active Filter with Phase Locked Loop (PLL & & Hysteresis Switching (HS)

      Here the load current is Il , the load voltage is Vt, the Output signal of the adaptive detecting circuit is and the fundamental reference frequency is f which is in phase with ac source voltage. The input sinusoidal reference signal which is the fundamental component of the system voltage has the same frequency and phase with the desired fundamental components of load current and load voltage, accordingly, the dc component of the integrator output will tune until they are equal in magnitude. From the sampled load current and load voltage, the corresponding fundamental real components of the voltage and current are extracted.

      = sin() [0 + (1/)0sin()

      = 0 sin() 1 sin()

      Where

      1 = (1 ) sin()

      = sin() [0 + (1 ) sin())

      = 0 sin() 1 sin()

      Where

      = ( 1 ) sin()

      1

      And

      IL= IP+IQ+IH VL= VP+VQ+VH

      Where fundamental active component load current is IP , fundamental reactive component of load current is IQ , harmonic components in load current is IH, fundamental active component of load voltage is VP , fundamental reactive component of load voltage is VQ, and the harmonic components in load voltage is VH. Proportional coefficient is K1 and the dc component of the integrator output is K0.

      = 0sin()

      = + + 0 sin()

      = +

      = 0sin()

    4. Introduction of Hysteresis Switching:

    A dynamic hysteresis band PWM controller uses current control which is implemented through feedback modulation. A hysteresis band is formed, within which reference current is marked, the shunt line current tracks the reference current. The reference currents calculated by the controller is compared by the measured values of compensation currents. In this way, the command signals for the inverter semiconductor switches can be produced by comparing them.

    Figure 6. Hysteresis band PWM control

    D) Proposed Control Scheme:

    Figure 5 shows IGBT Inverter block diagram with PLL and HS which is implemented in simulink. Here, the two currents in which one is sensitive load currents Iload & the measured load currents Imeas, are fed in to adaptive controller. The fundamental sinusoidal signals are obtained through the PLL using adaptive filters which is explained in figure 5. Let the load current Il, and the current of active filter be the input to the shunt firing unit. The gate signal obtained from this unit is the input to the IGBT. The gate signal Ig is obtained by means of using hysteresis current controlling technique. For detecting the current to be compensated, reference current should be obtained. The root mean square (RMS) value of load current is used for improving the PLL value. Root mean square value (RMS) of load active current can be obtained by-

    ( ) 2

    ( ) 2

    1

    ( = ()

    Figure 6 shows the principle of the dynamic hysteresis

    current controller technique for current control. Within the

    For the hysteresis controller the calc

    ulated value of currents

    Hysteresis band, If the shunt line current exceeds the maximum current limit of the hysteresis band, the upper half switch of the inverter arm is turned off and the lower half switch is turned on. The result of that is, the current starts to decay. Within the hysteresis band if the current crosses the minimum current limit of the hysteresis band, the lower switch of the inverter arm is turned off and the upper switch is turned on. The result is that, the current gets back into the hysteresis band. In this way the shunt line current is forced to track the reference current within the hysteresis band.

    is given along with the sensed three phases load current.

  4. SIMULATION RESULTS

    Simulation Model is carried out on a Matlab /Simulink software R2013a. Figure 6 represents the simulation model of harmonic compensation of controlled & uncontrolled loads with SAHF. Figure 7 represents the Simulink model of controlled & uncontrolled loads without SAHF. Harmonics which are generated by non-linear loads is removed by PLL based Shunt Active Power Filter. Given model considers the harmonics due to non-linear (controlled & uncontrolled) loads and the disturbance presents in supply system also taken into consideration. Figure 8.1 represents the input current wave shape is non-sinusoidal which represents unbalanced supply. For given model, the Simulation time is

    0.08 seconds. Figure 8.2 shows the 3 phase injected current waveform by ASHF at the point of common coupling. Figure

    8.3 shows 3-phase load current waveform which is a combination of Controlled (delta-delta) & Uncontrolled (delta-star) loads. Table 1 shows simulation parameters.

    Table I System Parameters

    SYSTEM

    PARAMETERS

    VALUE

    SOURCE

    VOLTAGE

    Vs

    4160*3*2 V

    FREQUENCY

    f

    50 Hz

    INDUCTANCE

    Ls

    1×10-5 H

    LOAD 1

    CONTROLLED RECTIFIER (DELTA-DELTA)

    THYRISTOR ON- RESISTANCE

    1X10-3 OHMS

    SNUBBER RESISTANCE

    1X103 OHMS

    SNUBBER CAPACITANCE

    1X10-6 F

    LOAD 2

    DIODE RECTIFIER (DELTA-STAR)

    RESISTANCE

    1X10-3 OHMS

    SNUBBER RESISTANCE

    1X103 OHMS

    SNUBBER CAPACITANCE

    1X10-6 F

    SAHF

    SHUNT ACTIVE HARMONIC FILTER

    LAF

    1X10-3 OHMS

    MAX.CURRENT

    4000A

    FREQUENCY

    50HZ

    DC BUS CAPACITANCE

    5X10-4 F

    VOLTAGE

    440 V

    SYNCHRONISING 6-PULSE GENERATOR

    DOUBLE PULSING MODE

    FREQUENCY

    50 Hz

    PULSE WIDTH

    10 degree

    THREE PHASE BREAKER

    (CLOSED)

    TRANSITION TIME

    5/60 Sec

    Figure 6. Simulink Model of Harmonic Compensationof Controlled & Uncontrolled Loads with SAHF

    Figure 7. Simulink Model of Controlled & Uncontrolled Loads without SAHF

    Figure 8.1 3 phase Source Current Waveform Figure 8.2 3 phase injected current waveform

    Figure 8.3 3 phase Load current waveform Figure8.4 FFT waveform of Non-Linear loads with SAHF (THD 0.57%) with fundamental freq 50 Hz

  5. FFT Analysis

    The Fast Fourier Transform (FFT) is used to measures the order of harmonics with the fundamental frequency at 50 Hz of the source current and also considers THD (total harmonic distortion) presents in selected signal. The FFT analysis of the system with and without the use of Shunt Active Filter is shown in Figure 8.4 & 8.5. The figure 6 shows the Non- linear loads directly connected with supply system that means without the use of Active Filter. In that case supply current having a THD of about 21.22% which is shown in figure 8.5. When Active Filter is used, the THD is reduced up to about 0.57% which is shown in figure 8.4.

    Figure 8.5 FFT waveform of Non-Linear loads without SAHF (THD 21.22%) with fundamental freq 50 Hz

  6. CONCLUSION

    This project proposes the implementation of a three-phase shunt active harmonic filter with phase locked loop having a combination of controlled & uncontrolled loads. Simulation result shows, this system provides unity power factor operation of non-linear loads with harmonic current sources, harmonic voltage sources, reactive, and unbalanced components which reduces the harmonics from 21.22% to 0.57%.

  7. REFERENCES

  1. M. El-Habrouk, M.K. Darwish and P. Mehta, Active Power Filter: A Review, IEEE Proc. Electr.Power.Appl, pp. 403-413,

    Sept 2000

  2. B. Singh, K. Al-Haddad and A. Chandra, A Review of Active Filter for Power Quality Improvements, IEEE Trans. on Industrial Electronics, pp. 960-971, Feb 1999

  3. Fang Zheng Peng, Harmonic Sources and Filtering Approaches, IEEE Industry Applications Magazine, pp. 18- 25, July 2001

  4. Fang Zheng Peng, Application issues of Active Power Filters, IEEE Industry Applications Magazine, pp. 21-30, Sept 1998

  5. H.L. Jou, Performance Comparison of the Three-phase Active-power-filter Algorithms, IEE Proc. Gener. Trans.

    Distrib., pp. 646-652, Nov 1995

  6. Adil M. Al-Zamil and D.A Torrey, A Passive Series, Active Shunt Filter for High Power Applications, IEEE Trans. on Power Electronics, pp. 101-109, January 2001

  7. S. Rahmani, Ab. Hamadi, Student Member IEEE, and K. Al- Haddad, Fellow IEEE A New Combination of Shunt Hybrid Power Filter and Thyristor Controlled Reactor for Harmonics and Reactive Power Compensation 2009 IEEE Electrical Power & Energy Conference.

  8. Hirofumi Akagi, Fellow, IEEE, and Ryota Kondo, A Transformerless Hybrid Active Filter Using a Three-Level Pulsewidth Modulation (PWM) Converter for a Medium- Voltage Motor Drive IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 25, NO. 6, JUNE 2010

  9. ZHENG Jiakun, MENG Chao, LI Po, HONG Yongqiang, The Study of Transformerless Shunt Hybrid Active Power Filter Compensation for Unbalanced Load 2012 IEEE 7th International Power Electronics and Motion Control Conference – ECCE Asia

    June 2-5, 2012, Harbin, China.

  10. Ab. Hamadi, S. Rahmani, Member IEEE, and K. Al-Haddad, Fellow member IEEE A Novel Hybrid Series Active Filter for Power, pp 1100-1104 , 2005

  11. R. D. Patidarl, Student Member, IEEE and S. P. Singh, A Fast Acting 1/z Controller for Shunt Active Filter Operation for Harmonics and Reactive Power Compensation 2008 IEEE Region 10 Colloquium and the Third International Conference on Industrial and Information Systems, Kharagpur, INDIA December 8 -10, 2008.

  12. M.asadi, A.Jalilian, H.F.Farahani, Compensation of unbalanced non linear load and neutral current using stationary reference frame in shunt active filters , 2010 IEEE.

  13. JenoPaul P, Ruban Deva Prakash T, Jacob Raglend Electrical & Electronics Engineering Nooral Islam University, Tamilnadu, Adaptive PLL controller based shunt Active Filter for power quality improvement in Matrix converter International Journal of Applied Engineering Reseach,DINDIGUL Vol 1,No 4, 2011.

  14. Varsha Prasad, Dr Chirag Sharma, Department of E&CE, Nitte Meenakshi Institute of Technology, Yelahanka, Bangalore-560 064, India A Review of Phase Locked Loop International Journal of Emerging Technology and Advanced Engineering , Volume 2, Issue 6, June 2012.