Life Assessment of Transformer: A Case Study

DOI : 10.17577/IJERTCONV4IS02025

Download Full-Text PDF Cite this Publication

Text Only Version

Life Assessment of Transformer: A Case Study

Parasnatp Pushpanjali Singh Bisht 2 Atesham Azhar Naiyer3

1Assistant Professor & HOD EEE EEE Department, RVS College of Engineering and Technology, Jamshedpur, India

2 Assistant Professor Department, RVS College of Engineering and Technology, Jamshedpur, India

3 Engineer At Power Grid

Abstract-.Power Transformers are the most vital equipment in a sub-station / Receiving station. Failure of a Transformer leads to loss of revenue besides affecting reliability of power supply to consumers. In order to ensure that Power Transformers provide long and trouble-free service, several diagnostic tests are carried out and remedial actions initiated throughout their operational lifetime. For the oil-filled Transformers, more particularly which are in service for more than 15 years, it is advisable that we should also estimate the residual life of the Transformers. Many methods are there which access the life of transformer like Tan & and capacitance measurements for windings, Degree of Polymerisation, Effect of moisture, Furan testing, Dissolved gas Analysis, Partial Discharge measurement, Magnetising current measurement etc. These methods can help the utilities in making optimum use of the Transformers and also taking timely decisions regarding refurbishment / replacement of Transformers, The paper presents the real life case study of assessing life of 315 MVA Power Transformer.

  1. INTRODUCTION

    Power transformer are most vital and costliest equipment of Electrical Power System .In order to ensure reliable and economic power supply it is essential that we should utilize the installed transformer optimally . In order to access the life of transformer various methods like Tan & and Capacitance measurement for windings, Tan & and Capacitance measurement for Bushing, Partial Discharge Measurement , Insulation resistance measurement, Magnetizing current measurement , Ratio test, Dissolved Gas Analysis , Furan testing etc.

    Modes of measurement

    There are three modes of measurement

    1. Ungrounded Specimen test(UST)

    2. Grounded Specimen Test(GST)

    1. Ungrounded Specimen test(UST)

      The Ungrounded Specimen Test (UST) is referred to as the test of an insulation sample that is not grounded. This test configuration automatically provides a guard connection that can be used effectively to measure only one component out of a multi component insulation system. The UST is of great advantage as its guard connection is also ground.

  2. TAN DELTA TEST

    Tan Delta test is a diagnostic test conducted on insulation of cables and winding. It is used to measure the deterioration in winding .It also give an idea of ageing process in the cable and ensure us to predict the remaining life of the cable .It is alternatively known as loss angle test or dissipation factor test Dissipation factor (Tan )

    Fig. 1. Ungrounded Specimen Test(GST)

    1. The Grounded Specimen Test (GST)

      The Grounded Specimen Test (GST) is referred to as the measurement of an insulation sample that has one of its terminals grounded. To conduct a GST test, the measuring circuit of the instrument used must be ungrounded to make the measurement possible. As most pieces of electric power system equipment is grounded, the grounded specimen test must be used if the equipment is to be tested in the installed condition. GST is therefore the most important and most frequently used test. Most up-to-date test equipment also offer a grounded specimen test with guard-GSTg. This connection allows one to measure one component of a multi- component, grounded, insulation system.

      Fig.2 Grounded Specimen test

    2. Capacitance and Tan Measurement for Bushing

      Capacitance and Tan Measurement for Bushing provides an indication of the quality and soundness of insulation in the bushing. Portable capacitance and Tan bridge such as Schering bridge or transformer arm bridge, power supply and standard capacitor is used for measurement of Capacitance and Tan

      Testing Procedure:

      1. Ensure that test specimen is isolated from other equipments

      2. Position the test set at least 6 feet (180 cm) away from test specimen to be tested.

      3. To prevent damage to the test set always the capacitance multiplier dial to the SHORT position , the capacitance measuring dials to the O position.

      4. Keep the UST-GST switch to UST position

      5. Keep interference suppressor switches in off position

      6. Connect the ground terminal of test set to low impedance earth ground

      7. Connect control unit to the high voltage unit using two 5 feet long shielded cables

      8. Connect the low voltage cable with red sheath to be Cx red terminal of the test set .Make sure the connector locks to the receptable.

      9. Connect the external interlock cable to the interlock terminal of the test set

      10. Connect the high voltage cable with black sheath to the high voltage terminal of high voltage unit.

      11. For 3-ph auto-transformer, short together all 400KV, 220 KV and Neutral bushing

        Measurement of C1 Capacitance and Tan delta:

        1. Connect the crocodile clip of the HV cable to the top terminal of the shorted HV/IV bushing. Unscrew the test tap cover , insert a pin in the hole of the central test tap stud by pressing the surrounding contact plug in case of 245 KV OIP bushing and remove he earth strip from the flange by unscrewing the crew.

        2. Connect the LV cable to the test tap of the bushing under the test to the capacitance and tan kit through a screened cable and earth the flange body. Repeat

        the test for all body by changing only LV lead connection of the kit to the test tap of bushing which is to be tested.

        Measurement of C2 capacitance and Tan Delta

        HV lead to be connected to the test tap of the bushing under test ad LV of the kit to be connected to the ground. HV of the bushing is to be connected to the guard terminal of the test kit.

        Recording of test result

        Make of Capacitance and tan kit –

        ETEL AUTOMATIC TAN DELTA TEST KIT

        Ambient Temp 26C

        Bushing

        Capacitance

        PREVIOUS VALUES

        PRESENT VALUES

        2 KV

        10 KV

        2KV

        10KV

        400 KV BUSHINGS

        R ph

        469.85

        pF

        469.73pF

        469.61pF

        469.60 pF

        Y ph

        462.53pF

        462.55pF

        462.51pF

        462.50pF

        B ph

        465.45pF

        469.23pF

        465.36pF

        469.61pF

        220 KV BUSHINGS

        R ph

        382.5 pF

        382.12pF

        382.45pF

        382.43pF

        Y ph

        417.48

        pF

        417.58 pF

        417.66 pF

        417.78 pF

        B ph

        380.68

        pF

        380.69pF

        380.94pF

        380.94pF

        52 KV

        bushing

        Rph

        207.58

        pF

        207.74pF

        207.22pF

        207.23pF

        Yph

        190.22

        pF

        190.53pF

        190.34pF

        190.34pF

        Bph

        207.65

        pF

        207.54pF

        207.24pF

        207.24pF

        Tan Delta

        PREVIOUS VALUES

        PRESENT VALUES

        2KV

        10 KV

        2KV

        10KV

        400 KV BUSHINGS

        Rph

        .0033

        .0033

        .0034

        .0034

        Y ph

        .0032

        .0032

        .0034

        .0034

        B ph

        .0033

        .0032

        .0034

        .0032

        220 KV bushing

        R ph

        .0037

        .0035

        .0037

        .0037

        Y ph

        .0060

        .0055

        .0062

        .0058

        B ph

        .0036

        .0035

        .0037

        .0037

        52 KV Bushing

        R ph

        .0044

        .0045

        .0047

        .0047

        B ph

        .0036

        .0034

        .0035

        .0035

        Y ph

        .0046

        .0045

        .0047

        .0047

        Comments

        The tan delta value has not exceeded the acceptable limit of 0.7%

        The main capavitance (C1) variation of the bushing i.e, the capacitance between high voltage terminal and test tap is within + 10% -5%

        Rate of rise of tan delta is not more than .001 year Hence bushings are healthy

    3. Capacitance and Tan Measurement for Winding

      The purpose of Capacitance and Tan Measurement for winding is to carried out to a certain the general condition of the ground and inter winding insulation of transformer

      Testing Procedure

      1. Measurement should be made between each inter winding combination with all other winding grounded to the tank or ground he entire windings guarded.

      2. For two winding Transformer , measurement should be made between each winding and ground with remaining winding grounded

      3. For three winding Transformer , measurement should be made between each winding and ground with one remaining winding guarded and second remaining winding grounded.

      4. Finally measurement should be made between all windings connected together and the grounded tank

      5. Removal of jumpers from bushing for capacitance and tan measurement windings

      6. Rest all procedure is same of Capacitance and Tan Measurement for bushing

    Recording of test result

    Make of Capacitance and tan kit

    ETEL AUTOMATIC TAN DELTA TEST KIT

    Weather : Clear, Oil Temp: 35 C

    Comments

    1. The tan delta value has not exceeded the acceptable limit of 0.7%

    2. The main capacitance (C1) variation of the winding is within + 10% -5%

    3. Rate of rise of tan delta is not more than .001 year

    4. Hence bushings are healthy

  3. MAGNETIZING CURRENT TEST Magnetising current test is performed to locate defect in

    magnetic core structure, shifting of windings, failure in turn

    to turn insulation or problem in tap changers. These conditions change the effective reluctance of magnetic circuit thus effecting the current required to establish flux in the core.

    Testing Procedure

    1. The test comprises a simple measurement of single phase current in one side of the transformer usually the low voltage side

    2. 3 phase transformers are tested by applying 3 phase ac supply HV terminals Keep the tap position in the lowest position

    3. Measured the voltage applied on each phase and current in each phase of HV terminal

    4. After completion of the above steps keep the tap position in normal position and repeat the above steps

    5. After completion of the above steps keep the tap position in Highest position and repeat the above steps

    6. keep the tap position in Highest position and Keep LV and HV terminal open

    7. Measure the phase to phase voltage between the IV terminal and current on each IV terminal

    8. Record the test result

    Recording Of Test Result

    TEST VOLTAGE

    2KV

    TEST MODES

    PREVIOUS VALUE

    PRESENT VALUE

    CAPACITANCE

    TAN

    CAPACITANCE

    TAN

    HV-LV in

    UST mode

    16985 pF

    .0022

    16998pF

    .0023

    HV-Ground in GST mode

    27501pF

    .0024

    27513pF

    .0026

    LV-Tank in GST mode

    24323pF

    .0020

    2432pF

    .0023

    TEST VOLTAGE

    10 KV

    TEST MODES

    PREVIOUS VALUE

    PRESENT VALUE

    CAPACITANCE

    TAN

    CAPACITANCE

    TAN

    HV-LV in

    UST mode

    16999pF

    .0022

    17011pF

    .0024

    HV-Ground in GST mode

    27500pF

    .0025

    27511pF

    .0027

    LV-Tank in GST mode

    24366pF

    .0022

    24370pF

    .0024

    TEST VOLTAGE

    2KV

    TEST MODES

    PREVIOUS VALUE

    PRESENT VALUE

    CAPACITANCE

    TAN

    CAPACITANCE

    TAN

    HV-LV in

    UST mode

    16985 pF

    .0022

    16998pF

    .0023

    HV-Ground in GST mode

    27501pF

    .0024

    27513pF

    .0026

    LV-Tank in GST mode

    24323pF

    .0020

    2432pF

    .0023

    TEST VOLTAGE

    10 KV

    TEST MODES

    PREVIOUS VALUE

    PRESENT VALUE

    CAPACITANCE

    TAN

    CAPACITANCE

    TAN

    HV-LV in

    UST mode

    16999pF

    .0022

    17011pF

    .0024

    HV-Ground in GST mode

    27500pF

    .0025

    27511pF

    .0027

    LV-Tank in GST mode

    24366pF

    .0022

    24370pF

    .0024

    Apply 3 Phase ac supply on HV terminal and Keep IV and LV open

    R-Y

    Tap position

    Voltage Applied

    Current Measured

    Between

    (Volts)

    In

    (mA)

    Lowest

    406

    R phase

    17

    Y-B

    391

    Y phase

    16

    B-R

    413

    B phase

    16

    Normal

    R-Y

    404

    R phase

    18

    Y-B

    390

    Y phase

    20

    B-R

    410

    B phase

    20

    Highest

    R-Y

    403

    R phase

    23

    Y-B

    390

    Y phase

    23

    B-R

    410

    B phase

    22

    Apply 3 phase ac supply on IV terminal and keep HV and LV terminal open

    Tap position

    Voltage Applied

    Current Measured

    Between

    (Volts)

    In

    (mA)

    Normal

    R-Y

    409

    R phase

    92

    Y-B

    399

    Y phase

    90

    B-R

    417

    B phase

    94

    Comments

    The set of readings for current measurement in each of tap position is found to be equal . It indicated healthy winding

  4. MOISTURE MEASUREMENT

    Moisture on the transformer affects dielectric strength and ageing of insulation and sometimes result in sudden failure due to bubble evolution on increased loading. Moisture in insulation being measured indirectly by measuring moisture content in oil. As water concentration in oil is highly temperature dependant , moisture in oil not a reliable indicator of dryness of cellulose.. New transformers should have less than 0.5% of moisture in paper by weight. Maximum amount of water in the transformer is present in the paper. When the oil temperature increases, more water is dissolved in the oil. Thus water content in the oil together with the temperature can give an estimate of water present in the paper.

    Moisture in paper

    Classification

    <0.5

    New Transformer

    0.5-1.5

    Dry insulation

    1.5-2.5

    Medium wet insulation

    2.5-4

    Wet insulation

    >4

    Very wet insulation

    A. Moisture measurement through domino

    DOMINO test is used to determine the moisture content of the oil in Transformers and reactors. The sensor is made of Thin polymer film which measure capacitance.

    T he capacitances changes proportional to the change in saturation of water in oil.

    DOMINO Principle

    Relative saturation RS= Wc * 100/S(%) Wc = Concentration of water in oil

    S= Solubility of water in oil that can be held at a given temperature

    Solubility of water in oil at given temperature, Log S= – 1567/K+ 7.0895

  5. FURAN ANALYSIS

    The mechanical properties of insulating paper can be established by direct measurement of its tensile strength or degree of polymerization (DP). These properties are used to evaluate the end of reliable life of paper insulation. It is generally suggested that DP values of 150-250 represent the lower limits for end-of-life criteria for paper insulation; for values below 150, the paper is without mechanical strength. Direct measurement of these properties is not practical for in- service transformers Analysis of paper insulation for its DP value requires removal of a few strips of paper from suspect sites. This procedure can conveniently be carried out during transformer repairs. The results of these tests will be a deciding factor in rebuilding or scrapping a transformer. Note: Since it is usually not practical (and often dangerous to the transformer) to obtain a paper sample from a de- energised, in service transformer an alternative method has been found. When a cellulose molecule de-polymerises

    (breaks into smaller lengths or ring structures), a chemical compound known as a furan is formed.

    By measuring the quantity and types of furans present in a transformer oil sample, the paper insulation overall DP can be inferred with a high degree of confidence. The types and concentration of furans in an oil sample can also indicate abnormal stress in a transformer, whether intense, short duration overheating or prolonged, general overheating. Furan analysis can be used to confirm Dissolved Gas Analysis where carbon monoxide present indicates problems with solid insulation.

    Furan derivatives

    2- Furaldehyde 2 FAL

    Furfuryl alchol 2 FOL

    2-Acetylfuran 2 ACF

    5-Methyl -2-Furaldehyde 5MEF 5-Hydroxymethyl-2-Furaldehyde 5HMF

    1. Furaldehyde is the most abundant of furan derivatives but the other four are occasionally found in large concentration to indicate significant paper degradation

      Approximate Relation Between DP And Total Furans

      2 FAL(ppm)

      DP= (1.5-

      log(2FAL))/.0035

      2FAL

      ppm

      DP=1850/(2FAL+2.3)

      0.1

      714

      0.1

      770

      0.5

      514

      0.5

      660

      1

      428

      1

      560

      2

      342

      2

      430

      3

      292

      3

      349

      4

      256

      4

      293

      5

      228

      5

      253

      1. Life Assessment of equipment by Furan Analysis Life of the equipment is generally the life of solid insulation itself, the remaining can be predicted from DP value

    % Life (remaining) = 100 * (DP-200)/(1200-200)

    We say % age life ,it is rather the % age reliability of the equipment to understand short circuit forces, overloading etc

  6. DISSOLVED GAS ANALYSIS

    DGA is probably the most powerful tool or detecting fault in electrical equipment in service. Thermal and electrical distributions in the operating transformer are two

    Sl. No.

    Code

    Kind of fault

    Grouping of fault

    X

    Y

    Z

    1

    0

    0

    0

    No fault

    F1

    2

    0

    1

    0

    Partial discharge with low intensity discharge

    F2

    3

    1

    1

    0

    Partial discharge with high intensity discharge

    F3

    4

    1

    or 2

    0

    1

    or 2

    Partial discharge with low intensity discharge

    F2

    5

    1

    0

    2

    Partial discharge with high intensity discharge

    F3

    6

    0

    0

    1

    Thermal fault with temperature less than 150°C

    F4

    7

    0

    2

    0

    Thermal fault with temperature between 150° C to 300° C

    F5

    8

    0

    2

    1

    Thermal fault with temperature between 300 °C to 700° C

    F6

    9

    0

    2

    2

    Thermal fault with temperature greater than 700°C

    F7

    Sl. No.

    Code

    Kind of fault

    Grouping of fault

    X

    Y

    Z

    1

    0

    0

    0

    No fault

    F1

    2

    0

    1

    0

    Partial discharge with low intensity discharge

    F2

    3

    1

    1

    0

    Partial discharge with high intensity discharge

    F3

    4

    1

    or 2

    0

    1

    or 2

    Partial discharge with low intensity discharge

    F2

    5

    1

    0

    2

    Partial discharge with high intensity discharge

    F3

    6

    0

    0

    1

    Thermal fault with temperature less than 150°C

    F4

    7

    0

    2

    0

    Thermal fault with temperature between 150° C to 300° C

    F5

    8

    0

    2

    1

    Thermal fault with temperature between 300 °C to 700° C

    F6

    9

    0

    2

    2

    Thermal fault with temperature greater than 700°C

    F7

    most important causes of dissolved gases in oil. The gases produced from thermal decomposition of oil and solid insulation are because of losses in conductors due to loading. Also decomposition occurs in oil and solid insulation is due to occurrence of arc. In case of electrical disturbances the gases are formed principally by ionic bombardment. The gases are generated mainly because of cellulose and oil insulation deterioration. In the normal operation of the transformer, gases such as Hydrogen (H2), Methane (CH4), Ethylene (C2H4), Acetylene (C2H2), and Ethane (C2H6) and so on are released

    1. Doernenburg ratio method

      This method utilizes the gas concentration from ratio of CH4/H2, C2H2/CH4, C2H4/C2H6, C2H2/C2H4.

      M

      N

      O

      P

      CH4/H2

      C2H2/C2H4

      C2H6/C2H2

      C2H2/CH4

      Suggested Fault Diagnosis

      >0.1

      <0.75

      >0.4

      <0.3

      Thermal Decomposition

      <0.1

      <0.001

      >0.75

      <0.4

      >0.3

      Corona (Low Intensity PD)

      <0.1

      <0.75

      >0.4

      <0.3

      Arcing(High Intensity PD)

    2. Rogers ratio method

    According to the IEC standards, the extended Rogers method is used to produce a three digit code. The code is determined based on the three gas ratios of C2H2/C2H4, CH4/H2, and C2H4/C2H6

    Gas ratio

    Value

    Code

    X= C2H2/C2H4

    X<0.1

    0

    0.1<X<3

    1

    X>3

    2

    Y= CH4/H2

    Y<0.1

    1

    0.1<Y<1

    0

    Y>1

    2

    Z=C2H4/C2H6

    Z<1

    0

    1<Z<3

    1

    Z>3

    2

    ROGER'S RATIO

    Fault Gases(IEC STANDARD)

    RATIO

    CODES

    S.

    No.

    X

    Y

    Z

    X

    Y

    Z

    Kinds of Faults

    1

    0

    0.561

    0.774

    0

    0

    0

    No Result

    2

    0.02

    2.842

    3.312

    0

    2

    2

    Thermal fault with temp

    >700°C

    3

    0.02

    1.286

    3.556

    0

    2

    2

    Thermal fault with temp

    >700°C

    4

    0.04

    1.928

    4.324

    0

    2

    2

    Thermal fault with temp

    >700°C

    5

    0.002

    2.156

    4.677

    0

    2

    2

    Thermal fault with temp

    >700°C

    6

    0.018

    1.365

    6.480

    0

    2

    2

    Thermal fault with temp

    >700°C

    7

    0.038

    1.389

    6.262

    0

    2

    2

    Thermal fault with temp

    >700°C

    8

    0.034

    1.098

    5.002

    0

    2

    2

    Thermal fault with temp

    >700°C

    9

    0

    2.270

    1.912

    0

    2

    1

    Thermal fault with temp bet. 300°C &

    700°C

    ROGER'S RATIO

    Fault Gases(IEC STANDARD)

    RATIO

    CODES

    S.

    No.

    X

    Y

    Z

    X

    Y

    Z

    Kinds of Faults

    1

    0

    0.561

    0.774

    0

    0

    0

    No Result

    2

    0.02

    2.842

    3.312

    0

    2

    2

    Thermal fault with temp

    >700°C

    3

    0.02

    1.286

    3.556

    0

    2

    2

    Thermal fault with temp

    >700°C

    4

    0.04

    1.928

    4.324

    0

    2

    2

    Thermal fault with temp

    >700°C

    5

    0.002

    2.156

    4.677

    0

    2

    2

    Thermal fault with temp

    >700°C

    6

    0.018

    1.365

    6.480

    0

    2

    2

    Thermal fault with temp

    >700°C

    7

    0.038

    1.389

    6.262

    0

    2

    2

    Thermal fault with temp

    >700°C

    /td>

    8

    0.034

    1.098

    5.002

    0

    2

    2

    Thermal fault with temp

    >700°C

    9

    0

    2.270

    1.912

    0

    2

    1

    Thermal fault with temp bet. 300°C &

    700°C

    B. Case Study

    DGA result of TATA STEEL, Jamshedpur (Tata Nagar). Equipment: 15/18.75 MVA

    Make BHEL

    Rated Voltage: 420/220/33 KV

    Rated current: 434/526.6/837.03 Ampere

    FAULTY GASES

    Sl.

    No.

    H2

    CH4

    C2H6

    C2H4

    C2H2

    CO

    CO2

    1

    21

    11.5

    65.3

    50.6

    0

    327

    5892

    2

    178

    506

    176

    583

    11.7

    151

    1844

    3

    502

    646

    194

    690

    14

    175

    2267

    4

    695

    1340

    629

    2720

    2.5

    335

    5655

    5

    684

    1475

    635

    2970

    5.5

    377

    6413

    6

    26

    35.8

    34.5

    224

    3.94

    105

    1096

    7

    408

    567

    354

    2217

    83.6

    74

    1912

    8

    397

    436

    354

    1771

    60.5

    70

    1867

    9

    21

    47.9

    37.7

    72

    0

    154

    1714

    ROGER'S RATIO

    Fault Gases(IEC STANDARD)

    RATIO

    CODES

    S.

    No.

    X

    Y

    Z

    X

    Y

    Z

    Kinds of Faults

    1

    0

    0.561

    0.774

    0

    0

    0

    No Result

    2

    0.02

    2.842

    3.312

    0

    2

    2

    Thermal fault with temp

    >700°C

    3

    0.02

    1.286

    3.556

    0

    2

    2

    Thermal fault with temp

    >700°C

    4

    0.04

    1.928

    4.324

    0

    2

    2

    Thermal fault with temp

    >700°C

    5

    0.002

    2.156

    4.677

    0

    2

    2

    Thermal fault with temp

    >700°C

    6

    0.018

    1.365

    6.480

    0

    2

    2

    Thermal fault with temp

    >700°C

    7

    0.038

    1.389

    6.262

    0

    2

    2

    Thermal fault with temp

    >700°C

    8

    0.034

    1.098

    5.002

    0

    2

    2

    Thermal fault with temp

    >700°C

    9

    0

    2.270

    1.912

    0

    2

    1

    Thermal fault with temp bet. 300°C &

    700°C

    FAULTY GASES

    Sl.

    No.

    H2

    CH4

    C2H6

    C2H4

    C2H2

    CO

    CO2

    1

    21

    11.5

    65.3

    50.6

    0

    327

    5892

    2

    178

    506

    176

    583

    11.7

    151

    1844

    3

    502

    646

    194

    690

    14

    175

    2267

    4

    695

    1340

    629

    2720

    2.5

    335

    5655

    5

    684

    1475

    635

    2970

    5.5

    377

    6413

    6

    26

    35.8

    34.5

    224

    3.94

    105

    1096

    7

    408

    567

    354

    2217

    83.6

    74

    1912

    8

    397

    436

    354

    1771

    60.5

    70

    1867

    9

    21

    47.9

    37.7

    72

    0

    154

    1714

    ROGER'S RATIO

    Fault Gases(IEC STANDARD)

    RATIO

    CODES

    S.

    No.

    X

    Y

    Z

    X

    Y

    Z

    Kinds of Faults

    1

    0

    0.561

    0.774

    0

    0

    0

    No Result

    2

    0.02

    2.842

    3.312

    0

    2

    2

    Thermal fault with temp

    >700°C

    3

    0.02

    1.286

    3.556

    0

    2

    2

    Thermal fault with temp

    >700°C

    4

    0.04

    1.928

    4.324

    0

    2

    2

    Thermal fault with temp

    >700°C

    5

    0.002

    2.156

    4.677

    0

    2

    2

    Thermal fault with temp

    >700°C

    6

    0.018

    1.365

    6.480

    0

    2

    2

    Thermal fault with temp

    >700°C

    7

    0.038

    1.389

    6.262

    0

    2

    2

    Thermal fault with temp

    >700°C

    8

    0.034

    1.098

    5.002

    0

    2

    2

    Thermal fault with temp

    >700°C

    9

    0

    2.270

    1.912

    0

    2

    1

    Thermal fault with temp bet. 300°C &

    700°C

  7. CONCLUSION

In this paper the analysis of life assessment of transformer is done so that due to failure of transformer there should not be any type of fault occur in electrical systems. Various methods are explain in the paper like Tan & and capacitance measurements for windings, Degree of Polymerisation, Effect of moisture, Furan testing, Dissolved gas Analysis, Partial Discharge measurement, Magnetising current measurement along with their cases studies and results

REFRENCES

  1. Bhalla ,Deepika., Kumar Bansal, Raj. and Gupta, Hari Om(2008). Transformer Incipent fault diagnosis based on DGA using fuzzy logic Internal Journal 2008.

  2. IEEE Std C57.104-199, 1992, "IEEE Guide for the Interpretation of Gases Generated in Oil Immersed Transformers". IEEE Press, New York

  3. Rogers R. R., 1978, "IEEE and IEC code to interpret incipient faults in transformers using gas in oil analysis ", IEEE transaction electrical Insulation., ,Vo.13,No.5, 349-354

  4. DiGiorgio, J.B. (2005) Dissolved Gas Analysis of Mineral Oil Insulating Fluids. DGA Expert System A Leader in Quality, Value and Experience 1, 1-17

  5. Dornerburg, E. and Strittmatter, W, Monitoring oil cooling transformers by gas analysis, Brown Boveri Review, vol61, May 1974, pp. 238-247.

  6. Duval, M., 1989, "Disssolved gas analysis, It can save your transformer", IEEE Electrical Insulation Man., Vo.5, No.6, 22-27.

  7. Gradnik, K. M., Physical-Chemical Oil Tests, Monitoring and Diagnostic of Oil-filled Transformers. Proceedings of 14th International Conference on Dielectric Liquids, Austria, July 2002

  8. Haupert ,T. J., Jakob, F., and Hubacher, E. J., 1989, "Application of a new technique for the interpretation of dissolved gas analysis data" 1lth Annual Technical Conference of the International Electrical Testing Association, 43-51.

  9. Herbert G. Erdman (ed.), Electrical insulating oils, ASTM International, 1988 ISBN 0-8031-1179-7, p.108.

  10. Hooshmand R., Banejad M., 2006 "Application of Fuzzy Logic in Fault Diagnosis in Transformers using Dissolved Gas based on Different Standards", World Academy of Science, Engineering and Technology,No.17.

Leave a Reply