Modeling and fault analysis of wind turbine with a Permanent Magnet Synchronous Generator using PSCAD

DOI : 10.17577/IJERTV3IS040379

Download Full-Text PDF Cite this Publication

Text Only Version

Modeling and fault analysis of wind turbine with a Permanent Magnet Synchronous Generator using PSCAD

Swagat Dash, Prof (Dr.)Bibhuti Bhusan Pati Department of Electrical Engineering, VSSUT, Burla Department of Electrical Engineering, VSSUT, Burla

Abstract- The aim of this work is to analyze a typical configuration of a Wind Turbine Generator System (WTGS) equipped with a Distribution Grid. Now a days, doubly fed induction generators are being widely used on WTGS, although synchronous generators are being extensively utilized too. There are different types of synchronous generators, but the multi-pole Permanent Magnet Synchronous Generator (PMSG) is chosen in order to obtain its model. It offers better performance due to higher efficiency and less maintenance since it does not have rotor current and can be used without a gearbox, which also implies a reduction of the weight of the nacelle and a reduction of costs. Apart from the generator, the analyzed WTGS consists of another three parts: wind speed, wind turbine and drive train. These elements have been modeled and the equations that explain their behaviour have been introduced. What is more, the whole WTGS has been implemented in PSCAD.

Index TermsPSCAD/EMTDC, PMSG, Distribution Grid Fault analysis

  1. INTRODUCTION

    The utilization of wind energy has a very long tradition. Some historians suggest that wind turbines (windmills) were known over 3000 years ago [1]. Until the early twentieth century wind power was used to provide mechanical power to pump water or to grind grain.

    The first wind turbines appeared at the beginning of the last century and technology was improved step by step from the early 1970s. By the end of the 1990s, wind energy has reemerged as one of the most important sustainable energy resources, partly because of the increasing price of the oil, security concerns of nuclear power and its environmental issues. Moreover, as wind energy is abundant and it has an inexhaustible potential, it is one of the best technologies today to provide a sustainable electrical energy supply to the world development.

    Actually, during the last decade of the twentieth century, World wide wind capacity doubled approximately every three years. Currently, five countries (Germany, USA, Denmark, India and Spain) concentrate more than 83% of world wide Wind energy capacity in their countries [2]. Studies have shown that by the end of2003, the total installed capacity of the wind turbines reached 39.234 GW and will exceed 110 GW by the year of 2012[3].

    The need for increased power production from the wind and economic reasons, when the rated power of today's wind turbines is still relatively small (2MW units are now typical), makes it necessary to group wind turbines into so-called wind farms.

    Wind farms are built on land, but in recent years there has been (and will probably be in the future) a strong trend towards locating them offshore. The lack of suitable wind turbine sites on land (it is particularly the case of densely populated countries) and the highest wind speeds located near the sea (and consequently higher energy can be extracted from the wind) are the two main reasons for locating wind farms offshore. Horns Rev in Denmark [4] is an example of a current Off shore wind farm, which is capable of producing 160 MW.

    Both induction and synchronous generators can be used for wind turbine systems [5]. Mainly, three types of induction generators are used in wind power conversion systems: cage rotor, wound rotor with slip control and doubly fed induction rotors. The last one is the most utilized in wind speed generation because it provides a wide range of speed variation. However, the variable-speed directly-driven multi-pole permanent magnet synchronous generator (PMSG) wind architecture is chosen for this purpose and it is going to be modeled: it offers better performance due to higher efficiency and less maintenance because it does not have rotor current. What is more, PMSG can be used without a gearbox, which implies a reduction of the weight of the nacelle and reduction of costs.

    This paper makes the choice to define a wind turbine connected to a permanent Magnet Synchronous Generator with 100 pole pairs. The connection to the grid is then performed through a full AC/DC/AC converter and a step up transformer. The main advantage of this strategy is to allow to remove the gear box in the wind turbine.

  2. SYSTEM DESCRIPTION

    The system analyzed is a variable speed wind turbine based on a multi-pole PMSG. Due to the low generator speed, the rotor shaft is coupled directly to the generator, which means that no gearbox is needed. The generator is connected to the grid via an AC/DC/AC converter, which consists of an uncontrolled diode rectifier, an internal DC-Link modeled as a capacitor and a PWM voltage-source inverter.

    ng= 1.Therefore w = wg. The power coefficient Cp reaches a maximum value equal to Cp= 0.593, which means that the power extracted from the wind is always less than 59.3% (Betz's limit), because various aerodynamic losses depend on the rotor construction (number and shape of blades, weight, stiffness, etc.). This is the well known low efficiency to produce electricity from the wind. The turbine subsystem model is depicted in Fig.II.

    A transformer is located between the inverter and the Point Of Common Connection(PCC) in order to raise the voltage by avoiding losses in the transport of the current. The layout of the electrical part is depicted in Fig. I.

    1.0

    Te Tm

    Ef If

    S

    e1r

    w Tm

    W

    Wind Source

    Mean

    Vw Vw

    W

    Wind Turbine

    MOD 2 Type Tm P

    Be

    0 ta

    W * N N/D

    Beta

    Wm Wind Turbine Governor

    Fig.I. Electrical Scheme of a wind turbine equipped with

    direct-driven

    314.16

    100 D

    MOD 2 Type

    Pg

  3. SUBSYTEM MODELS

    1. Wind Turbine Model

      The kinetic energy of the air through the rotor blades is: Ec = ½ mWs2 (1)

      The theoretical power we can obtain from a wind turbine

      is:

      Pth = ½ S Ws3 (2)

      with = air density (1.22 kg/m3)

      Fig.II. Wind turbine Subsystem build in PSCAD

    2. Distribution Grid

      P+jQ

      A distribution grid is a radial grid managed as an open loop. The power always flows in the same direction. The grid study is modeled as Fig.III.

      node1

      0.0001 [ohm]

      S = rotor surface (m2 )

      #1 #2 A V

      node1

      A

      0.016 [H] 1.0 [ohm] V

      Ws= Wind speed (m/s)

      In practice, the power is smaller because the wind speed behind the hub is not Zero . This efficiency is characterized by the Betz coefficient (given by Bernouillis equations), also called the Power Coefficient Cp:

      P+jQ

      Node2

      Node2

      P+jQ

      A Node3

      0.016 [H] 1.0 [ohm] V

      P+jQ

      Cp= P

      real/Pth

      (3)

      Fig.III. Distribution Grid

      Cp = ½ (1-a2) (1+a)

      a = Wind speed behind the rotor / wind speed in front of the rotor

      The amount of aerodynamic torque (w) in (N-m) is given by the ratio between the power extracted from the wind (Pth) , in W, and the turbine rotor speed (w), in rad/s, as follows

    3. AC/DC/AC: Power and Frequency Conversion

    The speed of the wind source being variable, a converter stage AC-DC-AC must be implemented in order to connect the output of the synchronous generator (variable frequency and voltage) to the grid, where a constant frequency and a constant voltage is needed. In the following parts, the power

    p>

    =

    (4)

    conversion stage will be described and parameterized. It is composed of a :

    o A diode rectifier

    It should be noted that the mechanical torque transmitted to the generator (wg) is the same as the aerodynamic torque,since there is no gearbox. It implies that the gear box ratio is

    • A dc bus with a storage capacitance voltage

    • A six pulse bridge thyristor inverter

    The output voltage of a generator is proportional to its speed. The speed of the generator not being controlled, the DC bus must be protected from over-voltage. With a secure margin of 10%.

    To secure the bus, it is possible to block the rectifier in case of over-voltage. This is done with the Single Input Level Comparator. The Dc bus model used in system depicted in Fig.IV

    Idc1

    1.2M

    1.0M

    0.8M

    y

    0.6M

    0.4M

    0.2M

    Main : Graphs

    T_elect_gene Tm

    e1r

    Com. Bus

    6 Pulse Bridge

    AM GM

    AO 0

    KB

      1. [ohm]

        Cap_BRK

        V_Dcbus

        2.3 [F]

        V_Dcbus

        RMS

        RMS

        Idc1 V_Dcbus

        0.0

        0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0

        Fig.V simulation of WTGS in PSCAD

        B.Distribution grid

        S

        Start

        Sequence

        S Open Breaker

        Cap_BRK

        S Wait Until

        7.5 [s]

        S Close Breaker

        Cap_BRK

        Fig.IV. Dc Bus

  4. SIMULATION RESULTS

    1. Turbine Generator

      The PMSG has been considered as a system which makes possible to produce electricity from the mechanical energy obtained from the wind. The dynamic model of the PMSG is derived from the two phase synchronous reference frame, which the q-axis is 90°ahead of the d- axis with respect to the direction of rotation.

      Table.I. shows the parameter of turbine- generator that has been considered

      Table.I.Computation Parameter

      Parameter

      Symbol

      Values & Unit

      No.of pole pair

      P

      100

      Rated speed

      m

      3.1416 rad/sec

      Rated power

      Sn

      3 MVA

      Rated Voltage

      E

      0.69Kv

      d-axis reactance

      Xd

      0.4p.u

      Rated current

      In

      1450A

      Fig.V. shows simulation result of turbine-generator model

      A distribution grid is a radial grid connected with the turbine-generator system through AC-DC-AC converter. The power always flows in the same direction.Fig.VI. shows simulation result of Distribution Grid

      Main : Graphs

      9.0

      8.0

      7.0

      6.0

      5.0

      4.0

      3.0

      2.0

      1.0

      0.0

      Psource

      P1

      P2

      P3

      P

      0.00 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00

      1. Active Power of Grid at Various Node

        Main : Graphs

        8.0

        7.0

        6.0

        5.0

        4.0

        3.0

        2.0

        1.0

        0.0

        Qsource

        Q1

        Q2

        Q3

        y

        0.00 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00

        Pm

        Qgene

        Pgene

        I3

        I2

        I1

      2. Reactive Power of Grid at Various Node

        Main : Graphs

        Main : Graphs

        4.00

        3.50

        3.00

        2.50

        2.00

        1.50

        1.00

        0.50

        0.00

        -0.50

        0.60

        0.50

        0.40

        0.30

        0.20

        0.10

        0.00

        y

        I

        5.0 10.0 15.0 20.0 25.0 30.0 35.0

        0.00 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00

        Main : Graphs

        1.20

        Vsource

        E1

        E2

        E3

        1.00

        0.80

        0.60

        0.40

        0.20

        0.00

        0.0

        0

        0.25

        0.50

        0.75

        1.00

        1.25

        1.50

        1.75

        2.00

        0.70

        0.60

        0.50

        y

        0.40

        y

        0.30

        0.20

        0.10

        Analog Graph

        Ifault w ithout DG Ifault

        0.00

        0.0 2.5 5.0 7.5 10.0 12.5 15.0 17.5 20.0

        Fig.VI. Simulation of Distribution Grid in PSCAD At t=2s,We have the following values:

        Node1

        Node2

        Node3

        P(MW)

        8.9

        2.41

        0.78

        Q(MVAR)

        7.0

        1.80

        0.55

        V(pu)

        1.0

        0.91

        0.90

        I(KA)

        0.52

        0.15

        0.05

        C. Fault Analysis

        The connection of a distributed generator to a radial distribution system leads to situations not normally supported by the network in case of faults. The distributin network is a radial network and the protections are based on the current measurement.

        This simulation consists of connecting the distributed generator at one node and the fault component at another node. Then, the current and the active power are measured in order to determine the protection level necessary and compared to the values measured without the wind turbine generator.

        This simulation comprises of two cases. In the First case, fault is connected at Node 3 and distributed generator is connected at Node 1.the simulation is formed in both mode.i. e with and without DG and the results are compared.

        CASE 1 Fault at Node 3

        First perform a simulation with distribution grid alone and add the grid to the distribution generator .Fig.VII. shows simulation result and comparison between the two mode.

        Analog Graph

        1. Fault current at Node 3

          Main : Graphs

          3.50

          3.00

          2.50

          2.00

          1.50

          1.00

          0.50

          0.00

          firing angle

          y

          0.0 2.5 5.0 7.5 10.0 12.5 15.0 17.5 20.0

        2. Thyristor firing angle

          Main : Graphs

          2.00

          1.75

          1.50

          1.25

          1.00

          0.75

          0.50

          0.25

          0.00

          -0.25

          Pgrid

          Qgrid

          pow er

          0.0 2.5 5.0 7.5 10.0 12.5 15.0 17.5 20.0

        3. Real and Reactive power of grid

    Fig.VIII. Simulation Results of Fault occurred at Node 3 Table.III. shows the comparison of fault analysis of two mode.

    Table.III. Result of fault analysis

    1.20

    1.10

    1.00

    0.90

    0.80

    I

    0.70

    0.60

    0.50

    0.40

    0.30

    0.20

    Ia1 w ithout DG Ia1 w ith DG

    Default node 3

    Peak without using

    DG

    Peak values with

    DG node1

    I1(KA)

    1.04

    1.00

    Ifault(KA)

    0.68

    0.68

    The peak values at Node 1 is lower with DG than without DG.

    CASE 2 Fault at Node 2

    13.00 13.50 14.00 14.50 15.00 15.50 16.00 16.50 17.00

        1. Simulation result current at Node 1

    In this case the fault is connected at Node 2 and distribution grid is connected at Node 3. Fig.IX. show the results of fault accured at Node 2

    0.090

    0.080

    0.070

    0.060

    y

    0.050

    0.040

    0.030

    0.020

    0.010

    D_grid,D_GRID3 : Graphs

    Ia3w ithout DG I3

  5. CONCLUSION

The modeling of a wind turbine with a Permanent magnet synchronous generator has been treated. The model has been implemented in PSCAD in order to validate it.

The permanent magnet synchronous generator has been connected with distribution grid through ac-dc-ac converter. More ever fault analysis has been done on distribution grid with and without DG.

13.00 13.50 14.00 14.50 15.00 15.50 16.00 16.50 17.00 17.50 18.00 18.50 19.00

  1. Current at Node 3 for Fault occurred at Node 2

    D_grid,D_GRID3 : Graphs

    P3 w ithout DG P3

    2.00

    1.50

    1.00

    0.50

    y

    0.00

    -0.50

    -1.00

    -1.50

    0.0 2.5 5.0 7.5 10.0 12.5 15.0 17.5 20.0

  2. Variation of Power at Node 3

    Ifault

    REFERENCES

    [1] Z. Lubosny. Wind Turbine Operation in Electric Power Systems.Berlin: Springer, 2003.

    [2] T. Ackermann. Wind Power in Power Systems. New York: John Wiley Sons, 2005.

    [3] The American Wind Energy Association (2004, March). Global wind power growth continues to strengthen [Online]. Available: http://www.ewea.org.

    [4] Horns Rev Off shore Wind Farm Technical Report (2007). Available: http://www.homsrev.dk

    [5] J. G. Slootweg,S. W. H. de Haan, H.Polinder and W. L. Kling."General Model for Representing Variable Speed Wind Turbines in Power System Dynamics Simulations". IEEE Transactions on Power Systems, vol. 18,no.1,2003

    [6] A Rolna , A Luna and G Vazquez,Modelling of variable speed wind turbine with a Permanent magnet Synchrnous Generator, IEEE International Symposium on Industrial Electronics (ISlE 2009) Seoul Olympic Parktel, Seoul, Korea July 5-8, 2009.

    D_grid : Graphs

    [7] PSCAD, Tool for power system simulation, Wind Turbine and Grid Connection modeling, Technical paper, CEDRAT, France, January2002.

    [8] PSCAD/EMTDC Users Manual: Ver.4.2, Manitoba HVDC Research Centre, 2005.

    y

    .

    1.60

    1.40

    1.20

    1.00

    0.80

    0.60

    0.40

    0.20

    0.00

    0.0 2.5 5.0 7.5 10.0 12.5 15.0 17.5 20.0

  3. fault current at Node 2

Fig.IX. Simulation of case 2 in PSCAD Simulation result of case 2 is shown in Table.IV.

Table.IV.Results of Fault Analysis

Default Node2-

DG node3

Peak values

without DG

Peak Values with

DG at node3

I3(KA)

0.02

-0.08

Ifault(KA)

1.43

1.43

During a fault, the current at I3 flows in the other direction with DG (the active power is negative). If there is a power protection at this point, this protection will see a negative active power and thus, it will never act! The distributed generator fault current will never be stopped.

The peak value at I3 is greater with DG. This could cause a serious problem if the new and larger I3 exceeds the circuit breaker maximum interrupting rating. In this case the circuit breaker must be changed.

Leave a Reply