Optimal Load Flow Analysis in Interconnected Network Using MATLAB

DOI : 10.17577/IJERTV4IS060086

Download Full-Text PDF Cite this Publication

Text Only Version

Optimal Load Flow Analysis in Interconnected Network Using MATLAB

Ram Kishore Pal (M.Tech Student) Rakesh Singh Lodhi

Electrical & Electronics Engineering Electrical & Electronics Engineering Oriental University Oriental University

Indore, M.P., India Indore, M.P., India

Abstract- Load flow analysis is the basis of power system planning design and operation. The main objective of this paper is to present an optimal load flow method to solve the Interconnected Distribution System… The load flow test case problem has been successfully solved for interconnected distribution systems with different methods like Newton- Raphson, Gauss-Seidel and Fast-Decoupled. The comparison of results for the test case of IEEE 30 bus network clearly shows that the Newton-Raphson method is indeed capable of obtaining optimum solution efficiently for Load flow problems. The power loss has also been reduced on getting the solution and implementation of remedial actions through MATLAB programming.

Keywords- Load flow, Newton-Raphson, Gauss-Seidel, Fast- decoupled method, MATLAB, Interconnected system

  1. INTRODUCTION

    The history of civilization shows a close relationship between the consumption of energy and progress of mankind. The per capita electricity consumption shows a measure of prosperity and progress of any country. Energy consciousness in the people has created an interest in them to tap new sources of energy from time to time.

    Amongst the various forms of energy, electricity has played a very vital role for a devolved country. To fetch the electricity as per the requirement of various categories of users a huge interconnected network is required Therefore a number of studies need to be conducted on the system for its operation control. Power system network is the biggest man made system in the world. This network is very vast and it is very difficult to understand its behavior. For getting values of system parameters, a deep study of this system network is required. A system may be under steady state or transient state. When a power system is in operation, it frequently switches over from one state to another. Therefore the system conditions need to be analyzed under both the conditions for better operation and control.

    Depending upon the type of algebraic equations developed in the study, numerical methods are selected to solve them. The solution of mathematical expressions gives the parametric values which are helpful to decide whether the system is stable or unstable, controllable or uncontrollable.

    The energy is produced at the locations where necessary raw material is available economically and safely i.e. pithead power station. This resulted in evolution of large central energy generating station with elaborate transmission and distribution systems. Due to large energy requirements an interconnected power systems are preferred over isolated power system.

    An interconnected system gives better handling of load and operation is economical as compared to the isolated system with given security and reliability constraints.

  2. LOAD FLOW ANALYSIS

    One of the most common computational procedures used in power system analysis is the load flow calculation.

    Load flow studies determine the voltage, current, active, and reactive power, power factor and power loss in the system. Load flow studies are an excellent tool for system planning. A number of operating stages can be analyzed, including contingency conditions, such as the loss of a generator, a transmission line, a transformer, or a load and also to determine the size and location of capacitors for power factor improvement.

    Following three methods are mostly used for the solution of a Load Flow Problem.

    • Newton-Raphson method (N-R)

    • Fast-decoupled Power Flow method and

    • Gauss-Seidel method (G-S)

  3. LOAD FLOW EQUATION

For the formulation of the active and reactive power entering a bus, we need to define the following quantities. Let

the voltage at the ith bus be denoted by

The study can be covered in to three stages:

Network modeling, Mathematical modeling and Solution

In the network modeling stage, the equipments are

Vi Vi i Vi cosi

Self admittance at bus-i as

  • j sini

    .. (1)

    represented as an equivalent electrical circuit component.

    In mathematical modeling stage, with the help of applicable laws, the network model is converted in to mathematical

    Yii

    Yii

    ii

    Yii

    cosii

  • j sinii

    Gii

  • jBii

    .. (2)

    ij

    ij

    model as algebraic equations in study state and .differential

    Mutual admittance between the buses i and j can be written as

    equations are developed in dynamical studies. Solution of the equations is obtained through Matlab programming.

    Yij

    Yij

    ij

    Yij

    cos

  • j sinij

    G

  • jBij

..(3)

Let the power system contains a total number of n buses. The injected current at bus-i is given as

Ii Yi1V1 Yi 2V2 YinVn

The steps of a computational algorithm are given below:

Step-1: With the load profile known at each bus i.e. PD, QD are known, allocate Pca and Qca to all generating stations.

Step-2: Assembly of bus admittance matrix YBUS with the line and shunt admittance data stored in the computer, YBUS is

n

YikVk

k 1

n

The complex power at bus-i

P jQ V I V Y V

.. (4)

assembled by using the rule for self and mutual admittances. Step-3: Iterative computation of bus voltages (Vij= 2, 3 ., n): to start the iterations a set of initial voltage values is assumed.

Step-4: Computation of slack bus power: substitution of all

i i i i

i ik k

k 1

n

bus voltages computed in step 3 along with Vi yields S*= P- jQ.

Vi cos i j sin i [YikVk cosik j sinik cos k j sin k ]

k 1

n

[YikViVk cos i j sin i cosik j sinik cos k j sin k ]

k 1

Step-5: Computation of line flows and line losses: this is the last step in the load flow analysis wherein the power flows on the various lines of the network are computed. Consider the lines connecting buses i and k.

B Newton-Raphson Method

Note that

(5)

The first method (G-S) is simpler but the second (NR) is

cosi j sin i cosik j sinik cos k j sin k

cosi j sin i cosik k j sinik k

cosik k i j sinik k i

Therefore substituting in (5) we get,

n

i

ik

i

k

ik

k

i

P Y VV cos (6)

reported to have better convergence characteristics and is faster than (G-S) method.

The Newton-Raphson procedure is as follows:

Step1: Choose the initial values of the voltage magnitudes

V(0) of all np load buses and n 1 angles (k) of the voltages of all the buses except the slack bus.

Step-2: Use the estimated V(k) and (k) to calculate a total n

calc

1 number of injected real power P (k) and equal number of

real power mismatch P

.

(k)

k 1

n

Q

Y VV

sin

Step-3: Use the estimated V(k) and (k) to calculate a total np number of injected reactive power Qcalc(k) and equl number

i ik i k

k 1

ik k i

(7)

of reactive power mismatch Q(k).

Step-3: Use the estimated V(k) and (k) to formulate the

This is load flow equation.

Then the total real power injected in bus-i is

Jacobian matrix J(k).

Pi,inj

PGi

  • PLi

(8)

2

P2

Let the injected power calculated by the load flow program

be P

i,calc

. Then the mismatch

Step-4: Solve

n

V2

P

for (k) and

P P P

P P P

(9)

J n

i i,inj

i,calc

Gi Li

i,calc

V2

Q2

Similarly, the mismatch between the reactive power and calculated values is given by

V

Qi

Qi,inj

Qi,calc

QGi

QLi

Qi,calc

(10)

1 n p

p

V1 n

Q1 n

p

The purpose of the load flow is to minimize the above two mismatches. It is to be noted that (6) and (7) are used for the calculation of real and reactive power in (9 to10).

IV TECHNICAL SOLUTION

V(k)V(k).

Step-5: Obtain the updates from

1 0 0

(11)

V k

Because of the nonlinearity and the difficulty involved in the analytical expressions for the above power flow

V k 1 V k 1

V k

(12)

equations, numerical iterative techniques are applied such as:

A Gauss-Seidel Method

The Gauss-Seidel Method is another iterative technique for solving the load flow problem, by successive estimation of the node voltages.

Step-6: Check if all the mismatches are below a small number. Terminate the process if yes. Otherwise go back to step-1 to start the next iteration with the updates given by

(11) and (12).

C. Fast-Decoupled Load Flow method:

Power-flow Programming Steps

Step 1: Input raw data: Input the electrical grid data in the standard data structure and estimate start points of the remaining undefined bus magnitude and phase angle.

Step 2: Data regeneration: Line data and bus data are specified to change along with bus numbers simultaneously. Step 3: Evaluate Ybus: Evaluate bus admittance matrix.

Step 4: Evaluate power mismatch: Evaluate Pi and Qi respectively from real power mismatch equation (9) and (10). Step 5: Evaluate Jacobian elements.

Step 6: Evaluate increments. Evaluate increments of bus voltage magnitude V and increments of bus angle degree

Bus Status

S.

No.

Data

N-R

G-S

Fast Decoupled

1

Iteration

4

83

15

2

Error

1.2e-005

0.000951

0.0009195

3

Total Load Bus active

power in MW

283.400

283.400

283.400

4

Total Load Bus Reactive power in

MVAr

126.200

126.200

126.200

5

Total Generation Bus active

power in MW

300.998

300.727

300.998

6

Total Generation Bus Reactive

power in MVAr

125.144

125.098

125.145

Line Losses

1

Total MW

Line Losses

17.599

17.573

17.598

2

Total MVAr

Line losses

22.244

22.139

22.245

by power flow matrix with Gauss Elimination method. Step 7: Update variables. Update new bus voltage magnitude and new bus phase angle by using equations as follows. And then returns to Step5 with new values to replace the precious values.

TABLE-1

IEEE-30 Bus Data comparison of different load flow methods

V(k+1)=Vk+Vk (13)

(k+1)= (k)+(k) (14)

Step 8: Examine reactive power of each PV Bus.

Step 9: Termination conditions. The process is continued until the residuals P(k) and Q(k) are less than tolerance accuracy as follows.

Max|P(k) |< Max|Q(k)|<

Note the are the small positive constant, such as 0.001, 0.00001, and the smaller numbers are pretty more accurate. Step 10: Evaluate power of the swing bus and each PV bus: Evaluate reactive power of each PV bus and evaluate active power and reactive power of the swing bus eq.

Step 11: Reconfigure bus numbers: Return each bus number to the original bus number in the bus data matrix and the line data matrix.

Step 12: Evaluate line flow and loss: Evaluate real and reactive power ows in transmission lines and transformers, as well as equipment losses.

  1. OPTIMAL POWER FLOW PROBLEMS-SOLUTION TECHNIQUES:

    1. Problem I (IEEE 30 bus system)

      One case is to make use of it to gives the optimal solution of load flow techniques on the IEEE- 30 bus test system. The case study is evaluating various analytical methods and computer program for the solution by Gauss-seidel, Newton- Raphson and Fast Decouple load flow method. Bus 1 is taken as a slack bus with its voltage adjusted to 1.060 pu. The data for the voltage controlled buses are given in Appendix-I and II.

    2. Test Results

      Load flow analysis is carried out in IEEE 30 bus test system. Output Voltage magnitude and Voltage Angle Load Bus active and reactive power, generation bus active and reactive bus and line losses values from N-R, G-S and FDLF.

      The rate of convergence of the GS method is slow as compare to other two methods. In GS method no of iteration are in increases trend in proportion to the no of buses in network whereas in NR and FDLF method no of iteration are lower side despite increase of no of buses in network.

      The chief advantage in GS method is the easy programming and most efficient utilization of core memory. In FDLF, storage requirements are around 60% to that of the NR method, but slightly more than the GS method. The programming of NR method is complex and it has the disadvantage of requiring a large computer memory. But Because of high accuracy and lowest no of iterations, the NR method is preferable for load flow and stability studies. The method can be extended for transformer tap-changing operations, variable constraints on bus voltage, optimal real and reactive power scheduling. The GS method is useful only for smaller bus system. NR method is reliable small and large system also. The FDLF method is comparatively more reliable than GS method and of course the NR method is most reliable for any system whether small or larger one.

  2. CONTROL TECHNIQES

    1. Load sharing

      In the given data, the active load on bus no.-5 is 94.2 MW and line losses is 17.599 MW/22.244MVAr as shown in table 1.Corrective step:-

      From the highly loaded bus no 5, the 10% load is shared by bus no 7 with the modified loading condition of bus no 5 as 84.8MW and on bus no 7 as 32.2MW.

      Now the results simulation process is obtained by way of reduced line losses to the extent of 17.536MW/21.976 MVAr as show in table2

      TABLE-2

      IEEE-30 Bus Data comparison after 10% load sharing from bus no 5 to 7

      Bus Status

      S.

      No.

      Data

      N-R

      G-S

      Fast

      Decoupled

      1

      Iteration

      4

      83

      15

      2

      Error

      7.75e-007

      0.0009625

      0.0009271

      3

      Total Load Bus

      active power in MW

      283.400

      283.400

      283.400

      4

      Total Load Bus Reactive power

      in MVAr

      126.200

      126.200

      126.200

      5

      Total

      Generation Bus

      active power in MW

      300.936

      300.661

      300.936

      6

      Total Generation Bus

      Reactive power in MVAr

      124.876

      124.829

      125.877

      Line Losses

      1

      Total MW Line

      Losses

      17.536

      17.510

      17.536

      2

      Total MVAr

      Line losses

      21.976

      21.869

      21.977

    2. Control by VAR generators

      The control the voltage profiles of an interconnected system using positive VAR power injects the load buses. Load flow solution gives the voltage levels at the load buses. In bus no 30 voltage is less as compare to other buses voltages, it is indicate of the fact that the reactive power flow capacity of the transmission lines for specifies voltage limits cannot meet the reactive load demand. This situation can be remedied by installing VAR generators at the load bus no 30. After the positive VAR inject.

      Reduction in line losses by injecting 10% MVAr power in the system:-

      In the given data, PU voltage magnitude is less than the rated to the extend of 0.995 and the line losses are to the extend of 17.599MW/22.244MVAr as shown in table 1.

      Corrective step:-

      From the given data table 1, bus no 30 is identifies as the weak bus in terms of the rated voltage and therefore additional 10% reactive power 1.0MVAr is injected in bus no 30.

      Now the results are obtained through simulation process by way of reduced line losses to the extent of 17.578 MW/22.1415MVAr as shown in table 3.

      TABLE-3

      IEEE-30 Bus Data comparison after 10% MVAr power injected at bus no 30

      Bus Status

      S.

      No.

      Data

      N-R

      G-S

      Fast

      Decoupled

      1

      Iteration

      4

      83

      15

      2

      Error

      7.69e-007

      0.0009300

      0.0009720

      3

      Total Load Bus

      active power in MW

      283.400

      283.400

      283.400

      4

      Total Load Bus

      Reactive power in MVAr

      126.200

      126.200

      126.200

      5

      Total Generation Bus active power in

      MW

      300.978

      300.693

      300.962

      6

      Total Generation Bus Reactive power

      in MVAr

      124.040

      114.650

      124.041

      Line Losses

      1

      Total MW Line Losses

      17.578

      17.536

      17.578

      2

      Total MVAr

      Line losses

      21.141

      21.69

      22.141

    3. Changing the tap position of the transformer

    In the given data, the transformer tap position feeding bus no 4 is 0.932 as shown in table 1. And the line losses are to the extent of 17.599MW/22.244MVAr.

    Corrective step:-The transformer tap position is put on 1 instead of 0.932 and the results are obtained through the simulation process by way of reduced line losses to the extent of 17.542MW/22.625MVAr as shown in table-4.

    TABLE-4

    Bus Status

    S.

    No.

    Data

    N-R

    G-S

    Fast

    Decoupled

    1

    Iteration

    4

    83

    15

    2

    Error

    0.0004082

    0.0009567

    0.0009871

    3

    Total Load Bus

    active power in MW

    283.400

    283.400

    283.400

    4

    Total Load Bus

    Reactive power in MVAr

    126.200

    126.200

    126.200

    5

    Total Generation

    Bus active power in MW

    300.939

    300.686

    300.928

    6

    Total Generation

    Bus Reactive

    power in MVAr

    125.482

    125.476

    125.547

    Line Losses

    1

    Total MW

    Line Losses

    17.542

    17.531

    17.528

    2

    Total MVAr

    Line losses

    22.625

    22.517

    22.644

    IEEE-30 Bus Data comparison after changing the tap position 0.932 to 1.0 at bus no 4.

    From Bus

    To Bus

    R (pu)

    X (pu)

    B/2

    (pu)

    X'mer Tap

    1

    2

    0.0192

    0.0575

    0.0264

    1

    1

    3

    0.0452

    0.1652

    0.0204

    1

    2

    4

    0.057

    0.1737

    0.0184

    1

    3

    4

    0.0132

    0.0379

    0.0042

    1

    2

    5

    0.0472

    0.1983

    0.0209

    1

    2

    6

    0.0581

    0.1763

    0.0187

    1

    4

    6

    0.0119

    0.0414

    0.0045

    1

    5

    7

    0.046

    0.116

    0.0102

    1

    6

    7

    0.0267

    0.082

    0.0085

    1

    6

    8

    0.012

    0.042

    0.0045

    1

    6

    9

    0

    0.208

    0

    0.978

    6

    10

    0

    0.556

    0

    0.969

    9

    11

    0

    0.208

    0

    1

    9

    10

    0

    0.11

    0

    1

    4

    12

    0

    0.256

    0

    0.932

    12

    13

    0

    0.14

    0

    1

    12

    14

    0.1231

    0.2559

    0

    1

    12

    15

    0.0662

    0.1304

    0

    1

    12

    16

    0.0945

    0.1987

    0

    1

    14

    15

    0.221

    0.1997

    0

    1

    16

    17

    0.0824

    0.1923

    0

    1

    15

    18

    0.1073

    0.2185

    0

    1

    18

    19

    0.0639

    0.1292

    0

    1

    19

    20

    0.034

    0.068

    0

    1

    10

    20

    0.0936

    0.209

    0

    1

    10

    17

    0.0324

    0.0845

    0

    1

    10

    21

    0.0348

    0.0749

    0

    1

    10

    22

    0.0727

    0.1499

    0

    1

    21

    23

    0.0116

    0.0236

    0

    1

    15

    23

    0.1

    0.202

    0

    1

    22

    24

    0.115

    0.179

    0

    1

    23

    24

    0.132

    0.27

    0

    1

    24

    25

    0.1885

    0.3292

    0

    1

    25

    26

    0.2544

    0.38

    0

    1

    25

    27

    0.1093

    0.2087

    0

    1

    28

    27

    0

    0.396

    0

    0.968

    27

    29

    0.2198

    0.4153

    0

    1

    27

    30

    0.3202

    0.6027

    0

    1

    29

    30

    0.2399

    0.4533

    0

    1

    8

    28

    0.0636

    0.2

    0.0214

    1

    6

    28

    0.0169

    0.0599

    0.065

    1

  3. CONCLUSION

The load flow case problem has been successfully solved for interconnected systems with different load flow methods and obtained results have been compared for all the three methods like Newton-Raphson, Gauss-Seidel and Fast- Decouple.

The Newton-Raphson, Gauss-Seidel and Fast-Decoupled load flow method were successfully designed and implemented to solve the Load flow problem. The comparison of results for the test case of IEEE 30 bus network clearly shows that the Newton-Raphson method is indeed capable of obtaining optimum solution efficiently for Load flow problems.After getting the solution,. the line losses have also been reduced by taking the remedial actions like reactive power injection, changing the transformer tap position and shifting of load and after formulation of the programmed results obtained through running on mat lab software as shown in table 2and4. This indicates the significance of the Newton Raphson method to solve load flow problems interconnected power system network.

REFERENCES

  1. IEEE Standard – 141 (1993) on IEEE Recommended Practice for Electric Power Distribution for Industrial Plants

  2. IEEE Standard – 399 (1997) on IEEE Recommended Practice for Industrial and Commercial Power System Analysis

  3. Gross C. A. and Melipoulos. S.P., Per-Unit scaling in Electric Power Systems, IEEE transactions on Power Systems, Vol. 7, No. 2, May 1992.

  4. Jian Yang, Anderson M. D., PowerGraf : An Educational Software Package for Power Systems Analysis and Design, IEEE Power Systems, Vol. 13, No. 4, November 1998

  5. Joong-Rin Shin, Wook-Hwa Lee, Dong-Hae Im, A Windows based Interactive and Graphic Package For the Education and Training of Power System Analysis and Operation, IEEE Power Systems, Vol. 14, No. 4, November 1999.

  6. Marizan Sulaiman, Zainuddin Mat Isa, A GUI based Per-Unit Representation of Power System with Symmetrical Components : An E-Learning Approach, Student Conference on Research and Development Proceedings, Malaysia, pp. 257-261, 2003

  7. Ming-Tong Tsay, Shun-Yu Chan, A Personal Computer Graphical Environment for Industrial Distribution System Education, Design and Analysis, IEEE Power Systems, Vol. 15, No. 2, May 2000.

  8. A Sekar, Bhaskar Mahyavanshi, Power System Simulation Software for Use in Cyberspace, report from Tennessee Technical University, Cookeville, USA, pp. 230-233, 2005.

  9. Nagrath I. J. & Kothari D. P., Modern Power System Analysis, Tata McGraw Hill, 1989.

  10. Stevenson & Grainger, Power System Analysis, Tata McGraw Hill, 1994.

  11. Kusik G.L., Computer-Aided Power System Analysis, Tata McGraw Hill, 1992.

  12. H. Saadat, Power System Analysis, Tata McGraw Hill, 1999.

  13. Chapman S. J., MATLAB programming for Engineers, Thomson, 2002.

  14. Amos Gilat, MATLAB : An Introduction with Applications, John Wiley & Sons, 2003.

  15. IS : 3842(Part-I)-1967, Application Guide for Electrical Relays for

    A.C. Systems. Part-I Overcurrent Relays for Feeders and Transformers.

  16. Jackson Prajapati, Virendra Patel, Hemal Patel, Load Flow, Short Circuit and stability Analysis Using Matlab, ICGCCEE.2014.6922365, 14665786/IEEE, P.g.1 5.

Appendix-I

30 Bus system Line Data

Appendix-II

30 Bus System Bus Data

B

us

Ty

pe

V

the

ta

P

g

Qg

Pi

Ql

Qmin

Qmax

1

1

1.06

0

0

0

0

0

0

0

2

2

1.04

3

0

4

0

50

21.

7

12.7

-40

50

3

3

1

0

0

0

2.4

1.2

0

0

4

3

1.06

0

0

0

7.6

1.6

0

0

5

2

1.01

0

0

37

94.

2

19

-40

40

6

3

1

0

0

0

0

0

0

0

7

3

1

0

0

0

22.

8

10.9

0

0

8

2

1.01

0

0

37.

3

30

30

-10

40

9

3

1

0

0

0

0

0

0

0

/td>

10

3

1

0

0

19

5.8

2

0

0

11

2

1.08

2

0

0

16.

2

0

0

-6

24

12

3

1

0

0

0

11.

2

7.5

0

0

13

2

1.07

1

0

0

10.

6

0

0

-6

24

14

3

1

0

0

0

6.2

1.6

0

0

15

3

1

0

0

0

8.2

2.5

0

0

16

3

1

0

0

0

3.5

1.8

0

0

17

3

1

0

0

0

9

5.8

0

0

18

3

1

0

0

0

3.2

0.9

0

0

19

3

1

0

0

0

9.5

3.4

0

0

20

3

1

0

0

0

2.2

0.7

0

0

21

3

1

0

0

0

17.

5

11.2

0

0

22

3

1

0

0

0

0

0

0

0

23

3

1

0

0

0

3.2

1.6

0

0

24

3

1

0

0

4.3

8.7

6.7

0

0

25

3

1

0

0

0

0

0

0

0

26

3

1

0

0

0

3.5

2.3

0

0

27

3

1

0

0

0

0

0

0

0

28

3

1

0

0

0

0

0

0

0

29

3

1

0

0

0

2.4

0.9

0

0

30

3

1

0

0

0

10.

6

1.9

0

0