Optimal Stabilizing Controller for Boiler Flow Control using Soft Computing Technique

DOI : 10.17577/IJERTV3IS120286

Download Full-Text PDF Cite this Publication

Text Only Version

Optimal Stabilizing Controller for Boiler Flow Control using Soft Computing Technique

D. Aditya M.tech Scholar

Dr. M. Siva Kumar Professor & Head of the Department

Gudlavalleru engineering college Gudlavalleru engineering college

Gudlavalleru,AndhraPradesh, India Gudlavalleru,AndhraPradesh, India

Abstract – PID controllers are widely used in many industrial applications due to their simplicity and robustness. In this paper, control of steam flow parameters of the Boiler using conventional PID controllers such as Zieglers-Nicholas, Modified Zieglers-Nicholas & Tyreus-Luyben methods have been studied. From this study it has been found that the controller designed using conventional PID may not able to satisfy required performance criterion such as IAE,ITAE,ISE.To overcome this difficulty, in this paper a new PID controller is proposed using PSO technique .The proposed PSO-PID strategy determines the controller parameters by optimizing various performance indices such as ITAE, IAE & ISE. The comparative results (Settling time, Maximum overshoot, ITAE, IAE, ISE) shows the efficacy of the proposed method. These controllers are also simulated under different disturbances using MATLAB/Simulink and results are successfully verified.

Keywords-Fuzzy logic controller, PSO-PID, IAE, ITAE, ISE

  1. INTRODUCTION

    The dynamic behavior of industrial plants heavily depends on disturbances and in particular on changes in operating point.

    Fig1: Schematic diagram of boiler

    Fig 2: Basic elements of Boiler

    The main input variables of a chemical plant are fuel, feed water and air. The outputs of the system are electrical power, steam pressure, steam temperature, flue gas as

    Shown in fig1

    In many industrial processes, control of liquid flow or temperature control is required. Boiler flow control system is a very complex system, because of nonlinearities and uncertainties in the system.There are various approaches to the design of the level controllers. The tank dynamics model based proportional integral derivative (PID) controllers have become famous for boiler level control. Conventional control approaches are not convenient to solve the complex issues in this highly nonlinear system. The control action of chemical industries maintaining the controlled variables. In this paper, control of boiler flow via three methods PID, Fuzzy Logic Controller and PSO-PID. PID control is one of the earlier control strategies.PID controller has a simple control structure which is easy to understand but the response of PID controller is not fast. To overcome these problems we use fuzzy logic and PSO-PID Controller. Performance analysis of PID, Fuzzy Logic Controller and PSO-PID has been done by the use of MATLAB and simulink. Comparison of various time domain parameters is done to prove that the PSO-PID has no overshoot, lesser settling time and lesser values for the IAE, ITAE, ISE as compared to PID and fuzzy-logic controller.

  2. MATHEMATICAL MODELING

    The most important aspect of any system is the theoretical analysis, which is a key for the prediction of the system being developed. A boiler of a chemical plant is taken as a case study and the temperature control of the boiler is achieved using conventional PID controller and intelligent fuzzy logic based controller Keeping this in mind the boiler equations were formulated and toolkits like Control, design and Simulation were used in order to study the dependencies of the input variables to the output variables.

    Mass balance equation for the steam in the drum: d/dt (As.Vs) =Xr.q-qs . (1)

    Mass balance equation for the water in the system: d/dt (Aw.Vw) = qfw qs (2)

    Mass balance equation for the steam in the risers: d/dt (As.a.Vr) = P/hc Xr.q (3)

    The circulation flow q is given by the momentum balance: (Aw – As) =k.q2 . (4)

    Set point of temperature = 380 degrees Celsius.

    Where

    a average steam quality in risers (volume ratio) hc evaporation enthalpy of water (J/Kg)

    k friction coefficient in down-commer riser loop q Circulation flow (Kg/s)

    q Fw feed water flow (Kg/s) qs Steam flow (Kg/s)

    As steam density (Kg/m3) Aw water density (Kg/m3) Vr volume of risers (m3)

    Vs volume of steam in drum (m3)

    Vw volume of water in drum down commer and risers (m3)

    P power supplied to water in riser from fuel (W) Xr average steam quality at riser outlet (mass ratio)

    2.1 Representation of system

    The manipulated input output process transfer function G(s) =

    ( )1B+D is calculated with the help of Matlab.

    7 6 0 1

    A = 1 0 0 , B= 0 , C = 0 5 5 0 1 0 0

    D = 0

    N = [0 -0.0000 5.0000 5.0000]

    D = [1 7 6 0]

    Transfer function:

    G(S) = +

    + (+)

  3. PROPORTIONAL INTEGRAL -DERIVATIVE CONTROLLER

    A proportionalintegralderivative controller (PID controller) is a generic control loop feedback mechanism

    (Controller) widely used in industrial control systems a PID is the most commonly used feedback controller. A PID

    Controller calculates an "error" value as the difference between a measured process variable and a desired set point.

    The controller attempts to minimize the error by adjusting the process control inputs. They are used in most automatic process control applications in industry. PID controllers can be used to regulate flow, temperature, pressure, level, and many other industrial process variables. Without automatic controllers, all regulation tasks will have to be done manually. For example: To keep constant the temperature of water discharged from an industrial gas-fired heater, an operator will have to watch a temperature gauge and adjust a fuel gas valve accordingly. If the water temperature becomes too high for some reason, there has to close the gas valve a bit just enough to bring the temperature back to the desired value. If the water becomes too cold, then open the gas valve. The control task done is called feedback control, and frequently changes the firing rate based on feedback that he gets from the process via the temperature gauge. Feedback control can be done manually as described here, but it is commonly done automatically. The valve, process, and temperature gauge forms a control loop. Any change the operator makes to the gas valve affects the temperature which is fed back to the operator, thereby closing the loop.

    PID controller has three control modes. They are proportional, integral, derivative and each of the three modes reacts differently to the error. The amount of response produced by each control mode is adjustable by changing the controllers tuning settings. The proportional control mode is in most cases the main driving force in a controller. It changes the controller output in proportion to the error. If the error gets bigger, the control action gets bigger. This makes a lot of sense, since more control action is needed to correct large errors. The adjustable setting for proportional control is called the Controller Gain (Kc). A higher controller gain will increase the amount of proportional control action for a given error. If the controller gain is set too

    high the control loop will begin oscillating and become unstable. If the controller gain is set too low, it will not respond adequately to disturbances or set point changes. The use of proportional control alone has a large drawback offset. Suppose increase the flow out of the tank, the tank level will begin to decrease due to the imbalance between inflow and out flow. While th tank level decreases, the error increases and our proportional controller increase the controller output proportional to this error. Consequently, the valve controlling the flow into the tank opens wider and more water flows into the tank.

    As the level continues to decrease, the valve continues to open until it gets to a point where the inflow again matches the outflow. At this point the tank level (and error) will remain constant. Because the error remains constant our P-controller will keep its output constant and the control valve will hold its position. The system now remains at balance, but the tank level remains below its set point. This residual sustained error is called Offset. The effect of a sudden decrease in fuel gas pressure to the process heater described and the response of a p-only controller. The decrease in fuel-gas pressure reduces the firing rate and the heater outlet temperature decreases. This creates and error to which the controller responds. However, a new balance-point between control action and error is found and the temperature offset is not eliminated by the proportional controller. The need for manual reset as described above led to the development of automatic reset or the Integral Control Mode, as we know it today. As long as there is an error present (process variable not at set point), the integral control mode will continuously increment or decrement the controllers output to reduce the error. Given enough time, integral action will drive the controller output far enough to reduce the error to zero. If the error is large, the integral mode will increment/decrement the controller output fast, if the error is small, the changes will be slower. For a given error, the speed of the integral action is set by the controllers integral time setting (TI). A large value of TI (long integral time) results in a slow integral action, and a small value of TI (short integral time) results in a fast integral action . If the integral time is set too long, the controller will be sluggish, if it is set too short, the control loop will oscillate and become unstable. The integral mode continues to increment the controllers output to bring the

    heater outlet temperature back to its set point. The derivative control mode produces an output based on the rate of change of the error .Derivative mode is sometimes called Rate. The derivative mode produces more control action if the error changes at a faster rate. If there is no change in the error, the derivative action is zero. PID control provides more control action sooner than what is possible with P or PI control. This reduces the effect of a disturbance, and shortens the time it takes for the level to return to its set point.

    3.1 PID CONTROLLER AND TUNING

    Fig 3: Block diagram of classical control structure

    A feedback control system measures the output variable and sends the control signal to the controller. The controller

    compares the value of the output signal with a reference value and gives the control signal to the final control element via the actuator .The characteristic equation obtained as below

    S3 + 7S2 + 6 + 5Kp S + 5Kp = 0 . (1)

    Applying Routh – Hauritz criteria in eq (1) we get Kp = 1.68, = 3.7947 and T = 1.6549.

    The equation of ideal PID controller is

    t

    u t = Kc( e t + 1 e t dt + Td de t )

    3.3 Design Of Pid-Controller

    Ti dt

    0

    u s = Kc( 1 + 1 + TdS )

    TiS

    A PID controller is tuned according to a table based on the

    process response test.

    3.2 Tuning Methods (Closed-Loop Methods):

    • Zieglers-Nicholas method:

      Step 1: Reduce the integrator and derivative gains to 0.

      Step 2: Increase Kp from 0 to some critical value Kp=Kc at which sustained oscillations occur

      Step 3: Note the value Kc and the corresponding period of sustained oscillation, Tc

      Step 4: Evaluate control parameters as prescribed by Ziegler and Nichols

      According to Zeigler-Nichols frequency response (Closed

      loop method) tuning criteria Kp = 0.6Kcu, Ti = 0.5T, Td = 0.125T

      For the PID controller in the heat exchanger, the values of tuning parameters obtained are Kp = 1.008, Ti = 0.8274, Td = 0.2068 and P = 1.008, I = 2.0303 , D = 0.3474.

    • Modified Zieglers-Nicholas method:

      For some control loops the measure of oscillation, provide by ¼ decay ratio and the corresponding large overshoots for set-point changes are undesirable therefore more conservative methods are often preferable such as modified Z-N settings

      According to Modified Zeigler-Nichols frequency response tuning criteria Kp = 0.33Kcu, Ti = 0.5T, Td = 0.33T

      For the PID controller in the heat exchanger, the values of tuning parameters obtained are Kp = 0.5544, Ti = 0.8274, Td = 0.5516 and P = 0.5544, I = 2.0304, D = 0.9266.

    • Tyreus-luyben method:

      Step 1-3: Same as steps 1 to 3 of Ziegler-Nichols method above Step 4: Evaluate control parameters as prescribed by Tyreus and Luyben

      Fig 4: Simulink representation of feedback control

      Fig 5: Step response of the gas turbine system using PID controller

      Fig 6: Graph for error signal

      According to Tyreus – luyben frequency response tuning criteria Kp = 0.45Kcu , Ti = 2.2T, Td = 0.158T

      For the PID controller in the heat exchanger, the values of tuning parameters obtained are Kp = 0.7636, Ti = 3.6407, Td = 0.2626 and P = 0.7636, I = 0.4614 , D = 0.4411.

      Fig 7: Step response comparison between Z-N, M Z-N& T L methods

  4. FUZZY-LOGIC CONTROLLER

    By relating to the conventional PID control theory, a new fuzzy logic controller structure namely scaling factor type fuzzy logic controller is implemented.Inorder to improve the performance of the transient state and the steady state of the PID type controller, here developed a method to tune the scaling factor of the PID type fuzzy logic controller online. This self-tuning scaling factor shows a better performance in the transient and steady-state response. The main contribution of these variable gains in improving the control performance is that they are self- tuned gains and can adapt to rapid changes of the errors and rate of change of error caused by time delay effects, nonlinearities and uncertainties of the underlying process. The controller has to make decisions based on external temperature condition. The variable temperature which is inputted on the system can be divided into a range of states such as Cold, Cool, Moderate, Warm, Hot, Very hot. Defining the bounds of these states is a bit tricky. An arbitrary threshold might be used to separate warm from hot, but this would result in a discontinuous change when the input value passes over that threshold. The way to make the states fuzzy is to allow them change gradually from one state to the next. The input temperature states can be defined using membership functions.

    Fuzzy-based control process consists of an input stage, processing stage and an output stage. The input stage maps sensor or other inputs such as switches, thumbwheels and so on, to an appropriate rule and generates a result for each. The processing stage then combines the results of the rules; and finally the output stage converts the combined result back to a specific control output value.

    Fig8: Fuzzy inference system

    The processing stage is based on a collection of logic rules in the form of If-Then statements, where the IF part is called the antecedent and the THEN part is called the consequent. These rules are used for to control the temperature in a boiler.

    In this paper we have considered different linguistic variables and details of these variables are shown in table1.

    At last defuzzified output is obtained from the fuzzy inputs. In this research work centroid method of de fuzzification is used. It is given as below.

    Table 1: IF-THEN rule base for fuzzy logic control

    Fig 9: Mamdani fuzzy inference system developed for fuzzy controller

    Fig10: Membership functions for ERROR &CHERROR

    Fig11: Membership functions for CONTROLLER

    =

    4.1 DESIGN OF FUZZY – LOGIC CONTROLLER

    Fig 12: Simulink representation of system with fuzzy logic controller

    Fig 13: Step response of system with fuzzy logic controller

  5. PARTICLE SWARM OPTIMIZATION

    Fig 14: Concept of modification of a searching point by PSO

    The modification of the particles position can be mathematically modeled according the following equation:

    Vik+1 = wVik +c1 rand1 () x (pbesti – sik) + c2 rand2 () x (gbest-sik) .. (1)

      1. Realization of Optimal PSO-PID Controller parameters

          • Implementation of PSO Algorithm:

            The optimal values of the conventional PID controller parameters Kp, Ki & Kd, is found using PSO. All possible sets of controller parameter values are particles whose values are attuned so as to minimize the objective function; here in this case is the error criterion. For the PID controller design, it is ensured the controller settings predictable results in a stable closed loop system.

            • Performance Indices for the PSO Algorithm:

        The objective function considered is based on the error performance criterion. The performance of a controller is best evaluated in terms of error criterion. A number of such criteria are available and in the proposed work, controllers performance is evaluated in terms of Integral of Absolute Error criterion, Integral of time and absolute error & Integral of square error, given by

        IAE | r(t) y(t) | dt e(t) dt

        The PSO methods have been employed successfully to solve complex optimization problems. PSO first introduced by Kennedy and Eberhart is one of the modern heuristic algorithms; it has

        ITAE t | e | dt

        & ISE

        | e2 (t) | dt

        been motivated by the behavior of organisms, such as fish schooling and bird flocking. Generally, PSO is characterized as a simple concept, easy to implement, and computationally efficient. In this paper, Scheduling PSO for PID Controller parameters for a boiler temperature control is proposed. This section describes how PSO is used to design the PID controller values optimally for a boiler temperature control.

        PSO is a robust stochastic optimization technique based on the movement and intelligence of swarms.PSO applies the concept of social interaction to problem solving. It uses a number of agents (particles) that constitute a swarm moving around in the search space looking for the best solution .Each particle is treated as a point in a N-dimensional. Each particle keeps track of its coordinates in the solution space which are associated with the best solution (fitness) that has achieved so far by that particle. This value is called personal best, pbest .Another best value that is tracked by the PSO is the best value obtained so far by any particle in the neighborhood of that particle. This value is called gbest. The basic concept of PSO lies in accelerating each particle toward its pbest and the gbest locations, with a random weighted accelaration at each time step as shown in Fig14.

        In this paper a time domain criterion is used for evaluating the PID controller. A set of good control parameters P, I and D can yield a good step response that will result in performance criteria

        minimization in the time domain. These performance criteria in the time domain include the overshoot and settling time.

      2. Scheduling PSO for PID Controller parameters

    The structure of the PID controller with PSO algorithms is shown in flowchart.

    Figure 15: The flowchart of the PSO-PID control system

    To control the temperature in boiler, according to the trials, the following PSO parameters (table 2) are used to verify the performance of the PSO-PID controller parameters

    TABLE 2: PARAMETERS OF PSO ALGORITHMS

    Population size

    30

    No. of iterations

    30

    Wmax

    0.6

    c1,c2

    2

    TABLE 3: LISTS THE Kp, Ki AND Kd OF PSO-PID CONTROLLER

    CONTROLLER

    Kp

    Ki

    Kd

    PSO-PID(IAE)

    8.6829

    0.0922

    3.1538

    PSO-

    PID(ITAE)

    27.5182

    0.3598

    10.8551

    PSO-PID(ISE)

    11.9190

    0.0065

    2.3954

    Fig 16: Step response of the PID controller tuning parameters using PSO strategy

  6. RESULTS COMPARISON OF CONVENTIONAL PID CONTROLLER AND FUZZY-LOGIC CONTROLLER

    WITH PSO-PID CONTROLLER

    To show the effectiveness of the proposed approach, a comparison is made with the designed conventional PID, Fuzzy logic controller and PSO-PID controller. These controllers are also simulated under different disturbances using MATLAB/Simulink and results are successfully verified. Finally, the steam flow parameters temperature, pressure are controlled and it is represented by using performance criteria.The performances of these controllers are listed in Table 4. It is clearly observed that PSO-PID having no overshoot, Short settling time & performance indices showing better values where conventional PID having longer settling time, higher in overshoot and also fuzzy logic controller having longer settling time, no overshoot and both of them having higher values of performance indices(IAE,ITAE&ISE).

    Fig17: Step response comparison between Conventional PID & PSO-PID

    Fig18: Comparison between FLC & PSO-PID

    Fig19: Comparison between Conventional PID & PSO-PID (with disturbance +0.1)

    Fig20: Comparison between Fuzzy & PSO-PID (with disturbance -0.05)

  7. CONCLUSION

    In this paper, a process control case study taking boiler has been implemented using PSO-PID. The flow of high pressure steam to

    the turbine is controlled by electronic governor. First of all a mathematical model of the system is developed and a conventional PID controller is implemented in it. The boiler flow control is controlled by PID-controller and fuzzy-logic controller. It has been observed that the control parameters obtained by the methods may not satisfy the performance indices such asIAE, ITAE&ISE.Then PSO-PID strategy is proposed to design and determine the optimal controller parameters for different performance indices. By comparison with PSO-PID controller, it shows that this method have improved the dynamic performance of the system in a better way. The PSO-PID controller is the best which presented satisfactory performances and possesses good robustness (such as No overshoot and shorter settling time, optimal performance indices when compared to the Conventional PID and fuzzy logiccontroller)

    TABLE 4: TIME-DOMAIN SPEPICIFICATIONS & PERFORMANCE INDICES OF SYSTEM RESPONSES WITH VARIOUS CONTROLLERS

    S. No

    TYPE OF DISTURBANCE

    DYNAMIC PERFORMANCE SPECIFICATION & PERFORMANCE INDICES

    CONVENTIONAL PID CONTROLLER

    FUZZY LOGIC CONTROLLER

    PSO-PID CONTROLLER

    Z-N

    MZ-N

    T-L

    IAE

    ITAE

    ISE

    1

    No Disturbance

    Peak Overshoot (MP) in %

    46.3013

    44.62

    27.2681

    0

    0

    0

    0

    Settling Time (TS) in Sec

    13.9345

    38.5521

    13.7766

    4.1352

    1.052

    1.14

    0.505

    IAE

    2.109

    4.178

    12.3

    17.44

    0.012

    ITAE

    10.48

    51.24

    2.206

    96.51

    0.02725

    ISE

    0.1894

    0.0645

    0.0048

    0.0003974

    0.0003352

    2

    A Step Disturbance of

    -0.1R

    Peak Overshoot (MP) in %

    44.361

    44.956

    28.63

    0

    0

    0

    0

    Settling Time (TS) in Sec

    15.70

    44.24

    14.64

    1.763

    1.045

    1.13

    1.512

    IAE

    2.221

    4.372

    2.311

    4.721

    0.07348

    ITAE

    10.91

    50.59

    12.43

    28.81

    0.1973

    ISE

    0.7699

    0.8668

    0.7632

    2.78

    0.05024

    3

    A Step Disturbance of

    +0.1R

    Peak Overshoot (MP) in %

    44.36

    44.352

    29.91

    0.6775

    0

    0

    0

    Settling Time (TS) in Sec

    15.69

    15.68

    14.63

    1.7684

    1.046

    1.12

    1.613

    IAE

    2.043

    2.043

    2.187

    0.7516

    0.08499

    ITAE

    10.1

    10.01

    12.42

    1.594

    0.2258

    ISE

    0.6415

    0.6957

    0.6136

    0.3665

    0.04693

    4

    A Step Disturbance of

    -0.05R

    Peak Overshoot (MP) in %

    44.98

    44.961

    24.36

    0

    0

    0

    0

    Settling Time (TS) in Sec

    15.722

    44.24

    17.43

    1.629

    1.047

    1.198

    1.6147

    IAE

    2.165

    49.283

    2.253

    2.47

    0.06972

    ITAE

    10.169

    4.247

    12.34

    13.44

    0.1134

    ISE

    0.7353

    0.82

    0.7145

    0.9044

    0.04891

    5

    A Step Disturbance of

    +0.05R

    Peak Overshoot (MP) in %

    46.10

    45.59

    28.96

    0.5973

    0

    0

    0

    Settling Time (TS) in Sec

    18.76

    44.26

    17.475

    2.103

    1.999

    1.1989

    1.1639

    IAE

    2.075

    4.025

    2.192

    0.6166

    0.08863

    ITAE

    10.29

    46.8

    12.33

    0.8541

    0.1494

    ISE

    0.6711

    0.7344

    0.6397

    0.354

    0.04725

  8. REFERENCES

  1. Rahul malhotra, Rajinder Sodhi. Boiler flow control using PID and Fuzzy logic controller, IJCSET, ISSN: 2231-0711, Vol 1, Issue6,315-319, july2011.

  2. B.Hemalatha, Dr. A.Vimala Juliet, N.Natarajan Boiler Level Control Using Lab view, International Journal of Computer Applications (0975 – 8887), Volume 1 No. 17, March 2010.

  3. Farhad Aslam, Gagandeep Kaur, Comparative Analysis of Conventional, P, PI, PID and Fuzzy Logic Controllers for the Efficient Control of Concentration in CSTR, International Journal of Computer Applications (0975 8887), Volume 17 No.6, March 2011.

  4. B.G. Hu, G.K.I Mann and R.G Gosine, New methodology for analytical and optimal design of fuzzy PID controllers, IEEE Transaction of fuzzy systems, vol. 7, no. 5, pp. 521-539, 1999.

  5. Mohammad Shahrokhi and Alireza Zomorrodi, Comparison of PID Controller Tuning Methods. International Journal of Advanced Technology in Engineering and Science, Volume No.02, Issue No. 11, November 2010.

  6. Isizoh A. N, Okide S.O, Anazia A.E,Ogu C.D Temperature Control System Using Fuzzy Logic Technique,International Journal of Advanced Research in Artificial Intelligence, Vol. 1, No. 3, October 2012.

  7. Ritu Shakya1, Kristina Rajanwal, Sanskriti Patel and Smita Dinkar4

    Design and Simulation of PD, PID and Fuzzy Logic Controller for Industrial Application, International Journal of Information and Computation Technology, ISSN 0974-2239 Volume 4, pp. 363-368,

    November 2013.

  8. S.N. Sivanandam1 S.N.Deepa2 A Comparative Study Using Genetic Algorithm and Particle Swarm Optimization for Lower Order System Modelling, International Journal of Engineering Research & Technology (IJERT), ISSN: 2278-0181, Vol. 3 Issue 11, November 2014.

  9. Manish Rathore , Preeti Verma , Dr Rajeev Gupta. Tuning of PID Controller Using GA and PSO Optimization Technique and Compare with Integral Errors International Journal of Science, Engineering and Technology Research (IJSETR), Volume 2, Issue 4, April 2013.