Preliminaries Comparison Based on Performance of 400KV and 750KV Double Circuit Transmission Line

DOI : 10.17577/IJERTV3IS030104

Download Full-Text PDF Cite this Publication

Text Only Version

Preliminaries Comparison Based on Performance of 400KV and 750KV Double Circuit Transmission Line

Rohit G. Kanojiya Pranay S. Shete Nirajkumar S. Maurya Nitin P. Choudhary Asst. Professor Asst. Professor Asst. Professor Asst. Professor

Dept. of Electrical Engg. Dept. of Electrical Engg.

Dept. of Electrical Engg.

Dept. of Electrical Engg.

YCCE, Nagpur YCCE, Nagpur DBACER, Nagpur DBACER, Nagpur

Abstract In this paper, A Comparison based on Standard Transmission Line Voltages is evaluated. An Overhead Double circuit Transmission Line of 400KV and 750KV has been compared based on average values of Line Parameters. Both Lines are taken as 400Km Long. The main focus of this paper is on Power handling capacity and line losses. A precise values of different parameters such as, No. of Towers required, average height of Tower, Phase spacing of Conductor, Bundle conductor spacing, and X/R ratio are also calculated. Calculation of Line and ground parameters, depending on properties of Bundle conductor has been implemented in MATLAB. An Important point based on mechanical consideration in Line performance is also highlighted.

Keywords Transmission Line; Line Parameters; Double circuit; Bundle conductor; Tower.

  1. INTRODUCTION

    Due to day by day increment in requirement of electrical energy, two types of transportation are greatly affected. The first one is natural gas or oil transportation by roadway or by railways and the second one is the bulk power transportation. For transmission line, as the bulk power transmission is not feasible by overhead transmission lines, varying lower voltage ratings (kV rating below 400 kV). Now a days, there are requirement for using 400kV or more just like having four way or six ways roads used for transportation. Thus EHVAC and HVDC transmission line plays a very important role in bulk power transmission. To fulfil these ever increasing bulk power consumptions, many developing and developed countries are using EHVAC, UHVAC and HVDC transmission systems [1-2].

    The limitations of HVDC are in maintenance, conversion, control, switching, availability and terminal investment. The required static inverters are very expensive and have limited overload capacity. At smaller transmission distances the losses in the static inverters are bigger as compared to an AC transmission line. The cost of the inverters required at terminals may not be offset by reductions in line construction cost and lower line loss. In contrast to AC systems realizing multiterminal systems are complex. Controlling of power flow in a multiterminal DC system

    requires good communication between all the terminals and power flow must be actively regulated by the inverter control system. The application of multi-terminal lines are not inherently used in todays world. Thus HVDC is less reliable and has lower availability than AC systems, mainly due to the extra conversion equipment. Single pole systems are still having the availability of about 98.5%, and.with much unscheduled down time due to fault. Fault redundant bipole systems provide high availability for 50% of the link capacity, but availability of the full capacity is about 97%.High voltage DC circuit breakers are challenging to build because some mechanism must be included in the circuit breaker to force current signal to zero, otherwise arcing and contact wear would be too great to allow reliable switching. Operating a HVDC scheme requires many spare parts to be kept, often exclusively for one system as HVDC systems are less standardized than AC systems and technology changes faster.

    According to inter regional transmission capacity for 11th five year plan (2007-2012), the total power of new inter regional link that must be added by National Power Grid of India is foreseen to be 20700 MW.In North Eastern Region (NER) from Biswanath Chariyali to North Region (NR) Agra, A 4000MW, HVDC Bipole system of +- 600kV is to be installed. From North Eastern Region (NER) of Bongaigon to Eastern Region (ER) Silliguri 400kV D/C is 1000MW are still under initial stage. In Eastern Region (ER) to North Region (NR) total capacity is 3500MW (i.e Barh to balia 400 kV D/C (Quad Moose) is 1200MW and Sasaram to Fatehpur 765 kV is 2300MW) are under developing stages.In ER to Western Region (WR) total capacity is 5700MW (i.e Rourkela Raipur 400kV, D/C is 1400MW, North Karanpura – Sipat 765kV is 2300MW, Hirma Sipat 400kV, D/C, 1000MW and Hirma Raipur 400kV D/C is 1000MW). In NR to WR total capacity is 5500MW (i.e Agra-Gwalior 765kV is1200MW, Agra-Gwalior 765kV, S/C, line-2 2300MW, Kankroli – Zerda 400kV, D/C, 1000MW and RAPP-Nagda 400kV, D/C, 1000MW). In Western Region (WR) from Parli to South Region (SR) Raichur the total power is of1000MW. Thus the installation need study and comparison between two different ratings towers.

    The steady state voltage limits according to central electrical authority that may be used in India are given according to following table I.

    The power handling capacity for a double circuit is usually given by

    TABLE I. VOLTAGE LIMITS

    P V 2Sin / Lx

    (2)

    Voltages (KV) in R.M.S

    Nominal Rating

    Emergency Rating

    Nominal

    Maximum

    Minimum

    Maximum

    Minimum

    66

    72.5

    60

    72.5

    59

    110

    123

    99

    123

    97

    132

    145

    122

    145

    119

    220

    245

    198

    245

    194

    230

    245

    207

    245

    202

    275

    300

    261

    300

    255

    345

    362

    324

    362

    317

    400

    420

    380

    420

    372

    500

    525

    470

    525

    460

    750

    765

    705

    765

    693

    765

    800

    728

    800

    713

    And the power loss in a six phase transmission line can be given as

    Ploss 6I 2rL V 2 Sin2.r / Lx2

    (3)

    The comparison based on system parameters between 400Kv and 750Kv, 400Km long transmission line is shown in table II.

    System Parameters

    400KV

    750KV

    Average height (m)

    49

    77.5

    Phase spacing (m)

    12

    16.8

    Conductor

    ACSR Moose, Twin

    Bundle 2*31.77mm

    ACSR Moose, Quad

    Bundle 4*30mm

    Bundle spacing (m)

    0.4572

    0.4572

    Bundle diameter (m)

    0.4889

    0.5172

    r (ohm/ Km)

    0.03177

    0.0136

    x (ohm/Km)

    0.327

    0.272

    x/r

    10.292

    20

    No. of circuits reuired

    5

    2

    Current/circuit (KA)

    1.76

    3.97

    Resistance for 400 Km

    (ohm)

    12.7

    5.44

    Total Power loss (MW)

    590

    308

    TABLE II. SYSTEM PARAMETERS COMPARISON

  2. EHVAC TRANSMISSION LINE

    1. Line Parameters

      A detail calculation of line parameters has been done. For getting the estimation of how much power a double circuit line at a given voltage can handle, it is mandatory to know the value of positive sequence line inductance and its reactance at power frequency. The line loss caused by I2R heating of a conductor is more important for conservation of energy. Therefore, in order to lower the i2r heating losses we need not require to lower the current I that may be transmitted but we can lower the conductor resistance R using bundled conductors comprising of several sub conductors in parallel. We will utilizes this average value of line parameter for given tower configuration as shown in table a for preliminary data estimation.

    2. Power Handling Capacity

      As we know by neglecting the line resistance the power which is to be transmitted depends upon the magnitude of voltage at sending end Vs and receiving end voltage Vr, the phase difference del and the last parameter i.e. total positive sequence reactance x per phase.

      Therefore,

    3. Long Transmission Line

    In modern world, civilization depends heavily on the consumption of electrical energy for industrial, commercial, agricultural, domestic and other purposes. As we know, electrical power is generated in large by thermal, hydro, nuclear power station. The energy transfer from these generating stations to distant distribution networks is done via mean of transmission line. Now a days modern electrical power system is in the form of a large interconnected network with constant frequency in the grid. All the generating stations, transmission and distribution systems are interconnected by means of 3 phase AC system operating synchronously at the common single frequency. (In India 50 Hz and USA 60 Hz). The basic function of a transmission system is to transfer electrical power from one location to

    another location or from one network to another network which is connected in the grid or outside the grid.

    P VsVrSin / Lx

    Where,

    P= Power in MW;

    Vs and Vr are voltages in kV (line-line);

    L= length of line in km.

    (1)

    Transmission system is necessary for bulk power transfer from generating station up to the main transmission line (network). As the thumb rule, higher the power rating higher is the requirements of transmission voltage. Longer the lines, higher are the required transmission voltage. This will give lesser current, lesser I2 R line losses, higher power transferability. In the ending-end substation, the voltages are stepping up and then transmitted. At the receiving end the voltage may be appropriately stepped down by using power transformer.

    Figure 1. Matlab model for 300Km Long 400kV D/C Line.

  3. TOWER DESIGN

    The purpose of Tower is to support the conductors [1]. The material used to build up the tower is usually steel. Figure 1 shows typical pylons in a 400kV route. Figure 1(a) is for

    that can happen when a tree fault on line. This means that the selected tower must have a defined width of the right of the way [3-4]. The specified right of way of self supporting tower is as shown in figure 4.

    Suspension Tower, 1(b) is 250 deviation Tower, 1(c) is deviation Tower and 1(d) Terminal Tower design.

    Figure 2. Types of Tower for 400kV D/C Line.

    900

    Sag of span also affects the selection of tower. There are standards which defines distances from construction and trees to the conductor. However, it is a difficult situation when the span between the towers is long, tower must be higher. These ensure that the conductor does not touch the ground or not even close to the ground. Thus the height of the towers depends on voltage rating, no. of conductors, sag and weight of the conductor. There are mainly four types of tower that may be used for a 400 kV double circuit transmission line shown ion figure 1. Out of which the suspension tower is the cheapest and mostly used worldwide. The purpose of this tower is to sustain the conductor because they are not affected by external forces. Figure 2 shows a typical 750 kV double circuit transmission tower used in China.

    Figure 3. 750kV Tower.

    A. Right of way

    As we know that the line clearing is one of the main task of civil engineering, it includes felling i.e too large trees must be cut down under the circumstance of fault situation

    Figure 4. Right of way for Tower design.

  4. CONCLUSION

Different types of tower structures have been studied for analysis purpose. The double circuit transmission line for

400 kV and 750 kV has been implemented in MATLAB simulation software. In the comparison between 750 kV and 400 kV transmission line on the basis of mechanical structure, amount of steel required (in terms of weight), Right of Way and the total power loss, it was found that for 400 km long transmission system, 750 kV system should be well preferred over 400 kV system. Also, in terms of future aspect 750 kV transmission line would be more suitable for execution purpose over 400 kV system considering bulk amount of power transmission.

REFERENCES

  1. WUJing,Structural Analysis on 750kV Double Circuit and Single Circuit Compact Towers, IEEE conf. on IEEE T&D Asia 2009,pp. 1-3, April 2009.

  2. Rakosh Das Begamudre, Extra High Voltage AC Transmission Engineering, 3rd ed.,New age international Publishers, 2009.

  3. Juho Yli-Hannuksela, The Transmission Line Cost Caculation, Thesis.

  4. Lars Weimers, Bulk power transmission at extra high voltages, a comparison between transmission line for HVDC at voltages above 600kV DC and 800kVAC, Unpublished.

  5. L. Ekonomou

Leave a Reply