Study of Fire Fighting System in Public Building

DOI : 10.17577/IJERTV11IS030181
Download Full-Text PDF Cite this Publication

Text Only Version

 

Study of Fire Fighting System in Public Building

¹Tejas Kadam, ²Darshan Khambale, ³Suraj Kunke, Sainath Dhadam,

Nikhil More, Prof. K. A. Joshi ¹²³(Students), (Head of Department) ¹²³(Department of Civil Engineering)

¹²³(B.R.Harne College of Engineering And Technology), Vangani,Thane, Maharashtra, India

Abstract:- Among different types of occupancies, a commercial highrise building presents a greater challenge to fire protection due to its functionality, complexity and economic value. The key objective of the present paper was to examine the situation of physical (as opposed to non-physical)fire protection systems in fourteen randomly selected commercial highrise buildings in the Nairobi CBD for fire safety optimization. Methods used include; physical observations, document review andinterviews. A multi-attribute evaluation model/approach was applied to establish sufficiency and/or suitability of fire protection systems in the light of the national regulations and approved standards. The study findings show that, save for the facilities of the disabled and the firefighting/evacuation lifts, other fire protection systems are mainly provided in the buildings. However, insufficient maintenance and/or unsuitable elements renders their safety performance low. The results of the analysis showed that portable fire extinguishers had the highest performance with 78.57% of the buildings sufficiently and suitably in terms of number, locations, servicing etc., while 0% of the building was sufficiently and/or suitably installed with a sprinkler system i.e. they all exhibited some deficiency in terms of coverage and maintenance issues. This could be associated with the cost factor. The results of other systems were as follows: Fire detection and alarm (14.29%); Escape route (50%); Emergency lighting (64.29%); Smoke control System (50.00%); Compartmentation (64.29%), Riser mains, hose reels and hydrants (64.29%); Fire Brigade access and facilities (64.29%); Safety signs and notices (7.14%); Portable fire extinguishers and Fire assembly points (28.57%). In view of the findings, its recommended that increased efforts in inspection and maintenance of fire protection systems are considered to address the identified shortfalls throughout the project life. Provision for firefighting/evacuation lifts and facilities for the disabled persons should be consideredduring design of the commercial high-rise buildings.

Keywords:- Fire Protection Systems, Maintenance, Provision, Optimization, High rise buildings.

  1. INTRODUCTION

    Fire and smoke are among the major reasons of the accidental casualties [1]. Fire detection is important as the fire causes serious damages to both human life and non-living assets. Most of houses lack the fire alarm systems that causes the resident a serious risk on fire breakout in homes [2]. The fire breakout can also occur in absence of the residents. Most of fire alarm system, available in market, are in wired connection mode. This type of system needs installation and investment and have its own limitations. It also does not meet the new automatic smart homes requirements [3]. Thus, an intelligent wireless fire alarm system is needed to be developed with lower maintenance along with safer and easier. The methodology is discussed in the next section.

  2. FIRE PROTECTION SYSTEMS

Conceptually, optimal fire protection can only be achieved through integration of three key fire safety elements. These are fire prevention, protection, and suppression. The concept in figure 1.0 below is used to demonstrate how an integrated fire safety planning and management system can be used to offer an overall fire safety in commercial high-rise buildings as illustrated below.Fire prevention and suppression are concerned with control of fire from taking place and extinguishment respectively. Fire protection is a mechanism involving both fire prevention and suppression at design and occupation of a building. Normally, each of the three fire safety elements exhibit three critical safety controls i.e. physical control, management control and human control infire safety management.

Automatic water sprinkler: The legal provision for provision of automatic water suppression system is contained in the National Planning and Building Regulations, 2014, regulation SS 37. The Regulation requires that, with some exceptions, any building exceeding 30 meters in height or a basement storey more than 500m 2 or in any other storey which exceeds 500 m2 in total floor area and such storey is not provided with breakable or openable panels be installed with an approved sprinkler system.

Fire detection and alarm system: The key statutory requirements for fire detection and alarm systems are found in the provisions of Fire Risk Reduction Rules, 2007, under rule No. 26 and No 28 and in the National Planning and Buildings 2014, regulation SS32.

Escape route: In the National Planning and Building Regulation, 2014 the requirement for provision escape route is contained in regulation SS18.1. The regulation requires that all buildings be provided with one or more escape routes that can be used in case of fire or other emergencies. The regulations also provide for the specifications for appropriate lighting and ventilation of such escape routes and stairways. The escape route should be well maintained, free of any obstructions, well light and provided with essential furniture to aid in movement and visibility of the route.

Emergency lighting: The building regulations require that, an independent supply of power is provided to provide energy for lighting during emergencies as per Reg.SS31 in the National Planning and Building Regulations, 2014.

Smoke control system: The Factories and Other Places of Work (Fire Risk Reduction) rules, Rule No 18 and regulation SS43 of the National Planning and Building, 2014 provide for provision of such facilities for control of smoke and/or fumes in workplaces or occupancies.

mains, hose reels and hydrants: The provision for riser mains, hose reels and hydrants for fire purposes are contained in various regulations in the National Planning and Building Regulations, 2014. Regulation SS34.1 requires that rational design of a fire installation make provision for water to be supplied in the quantity andat the pressure and rate of flow in accordance with BS 5306: Part1 to 7 of Regulation SS35.1 provides for hoses installation in any building of two or more storeys in height or in any single storey building of more than 250m2 in floor area at a rate of 1 hose reel for every 500m2 or part thereof of floor area of any storey. Regulation SS36.1 requires that they are provided in any building exceeding 12 m in height. The Fire Risk Reduction rules, Rule No 29 (1) requires that occupiers provide means of extinguishing fire at the workplace,while Section (4) requires that, where fire hose reels are provided and occupiers ensure that there is at least one fire hose reel are within the radius of 30 meters.

Facilities for the disabled: The National Building Regulations, 2014 provide for provision of firefighting and evacuation lifts and specifies the requirements for stretchers that can be used by persons with disability or the injured during emergency as provided under regulation SS50.1. Further, regulation SS 67.4 requires that every owner or occupier of a building shall have shall have arrangements for the evacuation of persons with special needs from a building in the event of a fireor other hazardous materials emergency. The Persons with Disabilities Act, 2003 provide for accessibility and movement of the disabled in workplaces and public buildings such as hand rails, visual signs etc.

Fire brigade access and facilities: The provision for fire brigade access and facilities are provided in regulation SS57, Section

(1) of the regulation requires that no building should be erected on any site unless such site is provided with suitable access for the purposes of firefighting and rescue by the Fire Services of the local authority.

Fire safety signs and notices: The National Planning and Building Regulations, 2010 provide clear guidelines on requisite specification for fire safety signs and notices under regulation SS30and regulation SS46. Regulation SS30.1 subsection (a) requires that any building having emergency routes be clearly marked and signposted to indicate the direction to be travelled in the case of any emergency.

Fire Extinguishers: These are first-aid fire extinguishers which are installed in the building for emergency purposes. They include among other portable CO2, dry chemical and powder, foam and water extinguishers strategically sited within the building premises. It is a legal requirementunder the Fire Risk Reduction, rule 29 (1) to provide firefighting appliances includes, among others, fire extinguishers. Rule 30 subsection (1) requires that every occupier ensure that all means of extinguishing fire are properly maintained and provides the requirements for inspection and testing, record keeping and timing of examination and testing. Rule 31 provides specific requirements for distribution of the various types of fire extinguishers in workplace.

Fire assembly point: The essence of a fire assembly point for emergency is to provide a place where head count of the persons who are involved in the fire is done. It also used as a temporary station where people who are injured can be offered first aid or can be picked for more attention to the hospital by rescue personnel. The requirement for fire assembly point is provided in Rule No 24 of the Factories and Other Places of Work (Fire Risk Reduction) rules, 2007.The rule requires every occupier identify a location in the workplace where every worker shall assemble in the event of a fire.

III . RESULTS

SR.NO DISCRIPTION PUBLIC BUILDINGS RESIDENTIAL BUILDINGS
1 overhead tank capacity 3000 litre 25000 litres
2 Booster pump capacity 1000lit/min 900lit/min
3 Sprinkler Required, if area ismore than 200m

2

Required, if area is moreThan 200m 2
4 First aid horse reel Required Required
5 Side and rear open space (setback)

to be left around a building ( minimum)

6m 4.5 m
6 Number of staircase Mini. 2 Mini. 2
7 Minimum width of stair 2 m 1.5 m

IV.CONCLUSION

communities can and will self-organize to take action to reduce the risk of catastrophic wildfire, if appropriate support is provided. In addition to defensible space around homes, shaded fuel breaks are needed to extend greater fire safety for neighborhoods. A network ofshaded fuel breaks will extend greater fire safety for our communities, cities, and towns.

Building shall be planned, designed and constructed to ensure fire safety and this shall be donein accordance with fire protection of national code of India, unless otherwise specified in theserules.

A fire alarm is a device that detects the presence of fire and atmospheric changes relatingto smoke. In some cases, a firm alarm is a part of a complete security system, in addition to aburglary protection system. The fire alarm operates to alert people to evacuate a location in which a fire or smoke accumulation is present

V. REFERENCES

[1] C.R Kothari (2014), RESEARCH METHODOLOGY: METHODS AND TECHNIQUES, 2nd Ed,new Age International Publishers [2] C.Ray Astahi and David W. Rieski (2010), Industrial Safety and Health Management, 6th Ed.person Education Inc, New Jersey

[3] Ed Soja et al (2011), Fire protection in Highrise Buildings; BCC, Melbourne, Victoria

[4] FPA, (2009), Fire Prevention, Fire Engineers Journal: The international journal for fireprofessionals, FPA

[5] Furness and Muckett (2010), INTRODUCTION TO FIRE SAFETY MANAGEMENT, Elsevier Ltd,professionals, FPA

[6] Grim wood, P., & Sanderson, I. A. (2015). A performance based approach to defining and calculating adequate firefighting water using s. 8.5 of the design guide BS PD 7974: 5: 2014 (fire service intervention). Fire Safety Journal, 78, 155-167.

[7] Chow, C. L., & Ki Chow, W. (2009). Fire safety aspects of refuge floors in supertall buildings with computational fluid dynamics. Journal of Civil Engineering and Management, 15(3), 225-236.

[8] Neal, A. J. (2012). Tips for Selecting DC Motors for Your Mobile Robot.

[9] National Instruments RF & Communications Handbook, National Instruments Germany GmbH Konrad Celtis-Str. 79 81369 München. 10] Jim Muccioli, DC Motor EMI Suppression, Ford Motor Company July 27, 2004.