- Open Access
- Total Downloads : 437
- Authors : Hiren V. Patel, Jay H. Ladani
- Paper ID : IJERTV3IS090535
- Volume & Issue : Volume 03, Issue 09 (September 2014)
- Published (First Online): 20-09-2014
- ISSN (Online) : 2278-0181
- Publisher Name : IJERT
- License: This work is licensed under a Creative Commons Attribution 4.0 International License
The Sub Cooled Air-conditioning System using Evaporative Condenser
Hiren V. Patel
Mechanical Engineering Dept., C.K.Pithawalla College of Engineering and Technology
Surat, India
Jay H. Ladani Mechanical Engineering Dept., Government Engineering College
Modasa, India
AbstractThe paper is the analysis of improvement of coefficient of performance of Refrigeration and Air Conditioning Test System. The most used method to increase the coefficient of performance of system is sub cooling of refrigerant [1]. Here paper indicates the set up used for experimental analysis to improve the COP of the system.
The key components selected for experimental analysis of COP are mainly evaporator, hermetically sealed compressor, air cooled condenser, thermo static expansion valve etc. The function of condenser in refrigeration system is to desuperheat and condense the compressor discharge vapour, frequently to sub cool the refrigerant.
Here the set up includes the evaporative condenser instead of air-cooled condenser. The comparative analysis shows there is an increase in COP of the system by 9.5%
KeywordsSubcooling, Evaporative condenser, COP
-
INTRODUCTION
In conventional set up, air-cooled condenser is used. In the modified set up, instead of air cooled condenser, evaporative condenser is used. Sub cooling is used to increase the refrigeration effect. In Technical terms, Sub cooling is simply the amount of heat removed below the refrigerants condensing temperature at a particular pressure or it can defined as the process by which a saturated liquid refrigerant is cooled below the saturation temperature, forcing to change its phase completely.
The modified condenser consists of condenser tubes, which are already in air-cooled mode. Cold water is circulated all over the tubes carrying the refrigerant. The refrigerant within the tubes is desuperheated and then it quickly reaches the saturation temperature where the gas is condensed into liquid.
-
METHODS TO IMPROVE COP OF AIR-CONDITIONING SYSTEM
The commonly used methods to improve coefficient of performance of systems are:
-
Sub cooling
-
Adding additives to refrigerant
-
Liquid Pressure Amplification
Among all these methods, Sub cooling is used in the experimental analysis of improvement of COP of the system [5]. The process of sub cooling is carried out by circulating more quantity of cooling water over the condenser tubes [4].
-
-
EXPERIMENTAL METHOD SELECTED TO IMPROVE COP
OF AIR CONDITIONING SYSTEM
As shown in Fig. 1 evaporative condenser is used to improve the COP of the system. It consists of a coil in which refrigerant is flowing and condensing inside, and the other surface is wetted with water and exposed to steam of air to which heat is rejected principally by evaporation of water. The coils are made of copper in multiple circuits and passes. The coil has arrangement for cleaning water under fouling water condition
The wetting of coil is done with the help of re-circulating of water pan due to assembly of submersible pump. The water distribution mainly comprises of nozzles for spray of atomized water on the coils.
Figure 1: Line diagram of Evaporative condenser
Modified evaporative condenser utilizes forced circulation of air with a fan to either blow or to guide air through unit. Effective elimination of moisture from the leaving air steam by plates is essential to prevent projection of rust, which can deposit moisture on the surrounding surfaces.
-
COMPARISON OF P-H DIAGRAMS
P-h diagram for conventional refrigeration cycle is shown in the Fig. 2
While Fig. 4 shows P-h diagram for refrigeration cycle with sub cooling. This indicates that the refrigerating effect is improved by sub cooling method. Sub cooling is taken placed when the refrigerant is cooled through some more degrees before entering the throttle valve
The Fig. 3 shows the refrigerant, during condensation process 2-3 is cooled below the saturation temperature before expansion by throttling. Such a process is called sub cooling of refrigerant and is generally done along the liquid line. The ultimate effect of sub cooling is to increase the COP under the same set of condition.
-
SPECIFICATION OF EXISTING EXPERIMENTAL SET UP
Fig. 4 shows the line diagram for existing experimental set up with following specification:
Figure 4: Line diagram of existing experimental set up
-
Compressor : Kirloskar, R22 refrigerant, 1.5 ton
-
Condenser : Air cooled system
-
Evaporator : Cooling coil, fin type
-
Expansion valve : TXV type
-
-
MODIFICATION IN EXISTING SET UP
Fig. 5 shows the modified experimental set up.
Figure 5: Modified experimental set up
The mofication are as follows:
-
Water cooling system: Evaporative condenser
-
Pump: Submersible pump is attached to the base of water filled tube to circulate water over the condenser coils.
-
PVC pipes: 2 nos, Length- 2 ft, Diameter- 1.5 inch
-
Clamps: Various fittings like clamps, nuts, bolts were used to told the set upin place
-
-
COP COMPARISON
The comparison of COP of air cooled and water cooled
condensing system
Sr.N
o
COP (Air cooled Condenser)
COP (Water cooled Condenser)
1
1.64
1.78
2
1.82
1.98
3
1.94
2.09
The comparitive analysis of COP shows that it increases by nearly around 9 to 9.5 % for water cooled condenser which is quite outstanding.
-
FUTURE SCOPE
There are so many limitations for evaporative condenser like the construction of water cooled condenser is complicated and thus design is not quite compact. The initial cost of the system is high so does the maintenance cost. The corrosion may take place in the pipes which carrying water inside, therefore fouling effect are high.
-
CONCLUSION
The main aim of any system is to get maximum possible output using least possible input. Experimental analysis shows that, the evaporator condenser has high COP nearly about 9 to 9.5 % compare to air cooled condensing system. The sub cooling can be used more effectively to improve the
refrigeration effect. Though there is an enough future work can still be done to improve the performance of the system.
REFERENCES
-
Dossat, R.J.1997, Principles of Refrigeration, 4th Edition, Prentice-hall International, USA.
-
Heydari A., Minimature vapor compression refrigeration systems for active cooling of high performance computers, Proceedings of Inter Society Conference on Thermal Pheomena , IEEE, 2002, 371-378.
-
Peeples J., :Vapor Compression Cooling for High Performance Applications, Electronics Cooling 7,3(2001).
-
Incropera F.P., DeWitt D.P., Fundametals of Heat and Mass Transfer. (John Wiley and Sons, Inc,2002), 670-690.
-
Vineyard, E.A. The Alternative Refrigerant Dilemma for Refrigerator- Freezers: Truth or Consqeunces ASHRAE Transactions, 1991,Vol.97,Part2955-299.
-
Whitman, W.C., Johanson, W.M.1995. Refrigeration and Air Condition Technology. 3rd Edition, Delmar Publishers Inc., USA.
-
ASHRAE Handbook Fundametals, SI Edition.1993. American Society of Heating , refrigeration and Air-Conditiong Engineers Inc., Atlanta, USA.
-
Phelan P.E., Swanson J., Chiric F., Chiric V., Designing a mesoscalevapor compression refrigerator for cooling high power microelectonics, Proceedings of the Inter Society Conference on Thermal Phenomena , IEEE, 2004, 218-223.
-
ARI Guideline. 1990, Air conditioning and Refrigeration Institute,USA
-
Clark,Earl M. et al. Retro-fitting Existing Chillers with Alternative Refrigerants. ASHRAE Journal, April 1991. Vol. 33, No.2,38-41.
-
Vineyard, E.A.; Sand, J.R.; Miller, W.A. Refrigerator-Freezer Energy Testing with Alternative Refrigerants. ASHRAE Transactions, 1989, Vol. 95, Part 2, 295-299.
-
Zholin Gu, Hongjuan Liu, Yun Li, Thermal energy recovery of air condtioning sytem-heat recovery system calculation and phase change materials development Applied Thermal Engineering, 24 (2004), 2511-2526.