Theoretical Aspects of Optimization using FACTS Devices

DOI : 10.17577/IJERTV3IS100524

Download Full-Text PDF Cite this Publication

Text Only Version

Theoretical Aspects of Optimization using FACTS Devices

Onyegbadue Ikenna A

Department of Electrical Engineering Igbinedion University

Okada,Nigeria

Madueme T.C

Department of Electrical Engineering University of Nigeria

Nsukka.

Abstract- This paper presents the theoretical aspects of the optimization using FACTS devices. Various FACTS devices such as the voltage source converter types were considered. The conventional compensation technique such as the use of capacitor banks in series and parallel were treated in this paper. Their modes of operation as well as short comings were investigated. Finally, various model equations showing the operation of the FACTS devices especially in power transfer and voltage improvement in the receiving end of the transmission line were presented.

Keywords: Optimization, FACTS Devices, Power Transfer, Voltage Improvement.

  1. INTRODUCTION

    Generally, the main objectives of FACTS are to increase the use able transmission capacity of lines and control the power flow over designated transmission routes. There are two generations for realization of power electronics-based facts controllers: the first generation employs conventional Thyristor-switched capacitors and reactors, and quadrature tap-changing transformers, the second generation employs

    gate turn-off (GTO) thyristor-switched converters as voltage source converters (VSCS).The first generation has resulted in the Static VAr Compensator (SVC), the Thyristor- controlled series capacitor(TCSC), and the Thyristor-controlled phase shifter (TCPS)[1][2].The second generation has produced the static Synchronous Compensator (STATCOM), the Static Synchronous Series Compensator (SSSC), the Unified Power Flow Controller (UPFC), and the Interline Power Flow Controller (IPFC) [3].

    The number of publications discussing facts applications to different power system studies has been recorded. The results of the survey are shown in Fig.1.0. It is clear that the applications of facts to different power system studies have been drastically increased in years 2000-2004. Generally, both generations of FACTS have been applied to different areas in power system studies including economic power dispatch, voltage stability, power system security and power quality [3].

    Fig. 1.0 Statistics for FACTS Applications to different Power System Studies Source:[3]

    Flexible AC Transmission Systems, called FACTS, became in the recent years a well-known term for higher controllability in power systems by means of power electronic devices [4]. Several FACTS devices have been introduced for various applications worldwide. The concept of using series/shunt capacitors/inductors to control the line power flow

    and to support the load bus voltage derived from the fundamental equations of power transfer has been used for long to control and optimize power flow in transmission systems, mechanically switched devices (phase shifters, series and shunt VArs compensators) have been implemented. These devices have been successfully used, but proved to be very slow [5].

    Another problem with the mechanically switched devices is that control cannot be initiated frequently, because switches tend to wear out quickly.

    FACTS-devices are usually perceived as new technology, but hundreds of installations worldwide,

    especially of SVC since early 1970s with a total installed power of 90000 MVA, show the acceptance of this kind of technology [4]. Table 1.0 shows the estimated number of worldwide installed FACTS devices and the estimated total installed power.

    TABLE 1.0 Estimated number of worldwide installed FACTS-devices and their estimated total installed power.

    S/NO

    TYPE

    NUMBER

    TOTAL POWER INSTALLED (MVA)

    1

    SVC

    600

    90000

    2

    STATCOM

    15

    1200

    3

    SERIES COMPENSATION

    700

    350000

    4

    TCSC

    10

    2000

    5

    HVDC B2B

    41

    14000

    6

    HVDC VSC B2B

    1+(7 WITH

    CABLE)

    900

    7

    UPFC

    2-3

    250

  2. CLASSIFICATION OF FACTS CONTROLLERS

    The three main ways of categorizing the FACTS controllers according to the connection of the devices within a transmission system are [6]:

    1. Series Devices

      Series devices have been further developed from fixed or mechanically switched.Compensations to the thyristor controlled series compensation (TCSC) or even Voltage source converter based devices. The main applications are:

      Source:[4]

      • Reduction of series voltage decline in magnitude and angle over a power line

      • Reduction of voltage fluctuations within defined limits during changing power

        t.ransmissions.

      • Limitation of short circuit currents in networks or substations.

      • Avoidance of loop flows. Power flow adjustments.

        P= V1V2 Sin X X series

        Fig. 2.0 A series controlled power system.

        According to [6], the power transferred in the network of Fig. 2.0 is

        ..1.0

        Where V1 and V2 are the bus voltages, X series is the reactance of the series device; X is the reactance of the line. P is the transferred power along the transmission line.

        Series compensation is used in order to decrease the transfer reactance of a power line at rated frequency. A series capacitor installation generates reactive power that in a self-regulating manner balances a fraction of the line's transfer reactance. The result is that the line is electrically shortened, which improves angular stability, voltage stability and power sharing between parallel lines [7].

    2. Shunt devices

      Their main applications in transmission, distribution and industrial networks are [7]:

      • Reduction of unwanted reactive power flows and therefore reduced network losses.

      • Keeping of contractual power exchanges with balanced reactive power.

      • Compensation of consumers and improvement of power quality especially with huge demand fluctuations like

        industrial machines, metal melting plants, railway or underground train systems,

      • Compensation of thyristor converters e.g. In conventional HVDC lines

      • Improvement of static or transient stability.

      Industrial, commercial and domestic groups of users require good power quality. Flickering lamps are no longer accepted, nor are interruptions of industrial processes due to insufficient power quality.

      P= V1V2 Sin

      X

      Fig. 3.0 A shunt controlled power system

      According to [6], the power transfer equation for Fig. 3.0 is represented thus;

      …2.0

      Where V1 and V2 are the bus voltages, X is the reactance of the line and is the power angle. P is the transferred power along the transmission line.

    3. Hybrid devices

    These devices combine the features of both shunt and series converters. Classification is according to the concept of operation, that is, the function and operating principles of the power electronics implemented in the FACTS controllers. There are two distinctly different aproaches to the realization of power electronics based FACTS controllers, each resulting in a comprehensive group of controllers able to address specific transmission problems.

    1 .Thyristor Controlled FACTS devices This group employs reactive impedances or tap-changing transformer with thyristor switches working as the control elements. This group includes the Static Var Compensator (SVC), Thyristor Controlled Series Compensator-Switched capacitor (TCSC) and Thyristor controlled phase shifter (TCPS). They employ conventional thyristors in circuit arrangements which allow fast control response compared to the corresponding mechanical system [8]. Each device can control one of the three power transmission control variables (bus voltage, transmission impedance and phase angle).

    1. StacticVAr Compensator (SVC)

      Fig. 4.0 Thyristor controlled FACTS devices

      angle control [8]. It may be controlled to improve the

      The SVC is effectively a variable shunt reactance which is able to produce a compensating reactive current. The device is operated to regulate the voltage at a selected terminal of the transmission system by a proper coordination of the capacitor switching and reactor phase

      transient and dynamic stability of the transmission system [9]. SVC may be controlled to damp power oscillation by adjusting its output between appropriate capacitive and inductive values to oppose the angular acceleration and deceleration of the involved synchronous machine.

      Fig. 5.0a Thyristor Controlled reactor

      Fig. 5.0b Thyristor Switched Capacitor

      Fig. 6.0 Static VAr Compensator.

    2. Thyristor Controlled Series Compensator (TCSC).

    The TCSC is used to control the voltage across the series impedance of a given transmission line that ultimately determines the line current and transmitted power [8]. Many different techniques have been reported in the literature pertaining to investigating the effect of TCSC on power system stability [10-13].

    Several approaches based on modern control theory have been applied to TCSC controller design. A state feedback controller for TCSC was presented by using a pole

    placement technique. However, the controller requires all system states which reduce its applicability [4]. A control scheme of TCSC for power flow control has been proposed [14].

  3. Modelling of the Conventional Compensators.

    The circuit diagram for an uncompensated line is shown in Fig. 7.0.

    Fig .7.0 Circuit diagram for an uncompensated line.

    The phasor diagram of the circuit is shown in Fig. 8.0.

    Fig. 8.0 Phasor diagram for an uncompensated line.

    Where Vs is the voltage at the sending end, VR is the voltage at the receiving bus, is the phase angle between the voltage

    VD=IRR + IXXL

    3.0

    at the sending bus and the voltage at the receiving bus.Voltage drop in the line with lagging power factor can be approximated as

    Fig. 9.0 Line with Shunt compensator.

    The phasor diagram for the shunt compensation is shown in Fig. 10.0.

    For a shunt compensated line with capacitors, a capacitor bank is connected in parallel to the receiving bus. Fig. 9.0 shows a shunt compensated line.

    Fig. 11.0 Circuit diagram for series compensation

    The phasor diagram is shown in Fig. 12.0.

    Fig. 12.0 Phasor diagram

    When a load with lagging power factor is connected at the end, voltage drop (Vd) in the line

    is sinØ)

    Fig. 10.0 Phasor diagram for a shunt compensated line

    The voltage drop can be approximated as VD = I1R + I1XL – ICXC

    4.0

    The difference between the voltage drops is the voltage rise due to the installation of the shunt capacitor.

    Vd=I(RcosØ+XL

    6.0

    If a capacitance C with reactance Xc is connected in series with the line, then the reactance will be reduced to (XL-XC) and hence the voltage drop is reduced.

    It can be observed from the phasor diagram that the line voltage drop is

    VR = ICXL.

    V =I(RcosØ+(X X

    )sinØ)

    5.0

    For the series compensation, the capacitor is connected in series to the line resistance and line inductive reactance. Fig.

    11.0 shows the circuit diagram for the series compensation.

    d L C

    7.0

    Thus the use of series capacitors is to reduce the voltage drop in the lines with low power factor and improve the voltage at the receiving end particularly with low power factor loads.

    For variable load conditions, the voltage can be controlled by switching in suitable series capacitors in the line.

  4. Modelling Of STATCOM.

According to [7] an equivalent circuit of a STATCOM model is as shown in Fig. 13.0.

Fig. 13.0 Equivalent circuit diagram of the STATCOM model.

The equivalent circuit of the STATCOM is now shown in Fig. 13.0. Suppose

Vsh= Vshsh,Vi= Vii, then the power flow constraints of the STATCOM are to be specified.

The operating constraint of the STATCOM is the active power exchang)e=v0ia the DC-link as described by:

PE=Re(VshIsh*

8.0

For the bus voltage control, the control constraint is as follows:

ViVispec=0 9.0

whereVispecis the bus voltage control reference.

V.CONCLUSION

The theoretical aspects of FACTS devices have been considered in this paper. Different FACTS devices were presented and discussed. The conventional compensation technique such as the use of capacitor banks in series and parallel were treated in this work. Their modes of operation as well as short comings were highlighted. Various model equations showing the operation of the FACTS devices especially in relation to power transfer and voltage improvement in the receiving end of the transmission line were also presented. The application of FACTS devices in a physical power system will be handled in an accompanying paper.

REFERENCES

  1. R. Billinton and R.N. Allan, Reliability Evaluation of Engineering Systems,Concept and technique,Longmans London (England),Plenumpress,Newyork,1992, pp. 22- 35.

  2. Steve KwakuAdzanu, Reliability Assessment of Non-Utility generation and Demand-side management in Composite Power System University ofSaskatchewanSaskatoon,1998, pp. 30-37.

  3. Y. H. Song and A. T. Johns, Flexible A.C Transmission Systems (FACTS), the Institute of Electrical Engineers, London. 2000.

  4. M.A. Abido, Power System Stability Enhancement Using FACTS Controllers: A Review, Journal for Science and Engineering, Vol. 34, 2009, pp. 153-172.

  5. IEEE Power Engineering Society, FACTS Overview.IEEE Special Publication 95TP108, 1995.

  6. Dr Ahmed Massoud FACTSFlexible AC TransmissionSystem.Retrieved July 7, 2013, http://www.people.qatar.tamu.edu/FACTS.pdf .

  7. Xiao-Ping Zhang,ChristianRehtanz and Bikash Pal, Flexible AC Transmission Systems:Modelling andcontrolSpringer- verlag Berlin heidelberg printed in Germany, 2006, pp. 1- 26..

  8. A.F. Mohamed EmadEldin, Investigation of Advanced Control for the Unified

    Power Flow Controller (UPFC) Published Project, Northumbria University, Newcastle, 2002, pp.

    11-39.

  9. M. Noroozian, Application of Shunt and Series Compensators for Damping Electromechanical

    Oscillation, IEE Colloquium on Power System Dynamic Stabilisation,1998,pp4/1-4/3.

  10. X. Chen , N. Pahalawaththa , U. Annakkage , and C. Kumble , Controlled Series Compensation for Improving The Stability Of Multimachine Power Systems, IEE Proc., 1995,pp. 361366.

  11. J. Chang and J. Chow, Time Optimal Series Capacitor Control For Damping Inter area Modes in Interconnected Power Systems, IEEE Trans. Pwrs, 12(1)

    ,1997, pp. 215221.

  12. T. Lie, G. Shrestha , and A. Ghosh , Design and Application of Fuzzy Logic Control Scheme for Transient Stability Enhancement in Power Systems, Electric Power Systems Research, 1995, pp. 17- 23.

  13. Y. Wang, R. Mohler , R. Spee, and, W. Mittelstadt ,Variable Structure Facts Controllers for Power System Transient Stability, IEEE Trans. Pwrs,1992, pp. 307313.

  14. PriyankaKathal and ArtiBhandakkar, Power Flow Control in Power System using FACTS device Thyristor Controlled Series Capacitor (TCSC): A Review, International Journal for Research andDevelopment in Engineering(IJRDE),2003,pp 82-91.