Unbalanced Radial Distribution System Load Flow and Voltage Profile Enhancement in the presence of Distributed Generators

DOI : 10.17577/IJERTV4IS051314

Download Full-Text PDF Cite this Publication

Text Only Version

Unbalanced Radial Distribution System Load Flow and Voltage Profile Enhancement in the presence of Distributed Generators

1Ishan Gupta, Vivek Gupta Department of Electrical Engineering, National Institute of Technology, Warangal

Abstract This paper presents the siting and sizing of Distributed Generators (DGs) in a three-phase unbalanced radial distribution system. This method exploits the radial structure of the network and solves the distribution load flow. Mutual coupling between the phases has been included in the mathematical model. The concept of finding the bus with maximum deviation from standard voltage profile is used to site a DG with suitable size in order to maintain the voltage profile of system as close as possible to standard voltages i.e 1p.u. Forward/Backward sweep method is used for the load flow studies. The proposed method is tested on a practical unbalanced three phase distribution feeder emanating from Pathardhi 132/11KV Grid substation in India and the results are presented in agreements with the literature and show that the proposed methodology is valid and reliable.

Keywords unbalanced distribution load flow, radial network, voltage profile, optimal placement, distributed generation, Indian bus system.

  1. INTRODUCTION

    with the advent in technology and emerging trends in the area of power generation, renewable sources are gaining more popularity. As we all know that the renewable technology is more eco-friendly and cost effective, hence we are trying to harness these sources locally through wind turbines, PV modules, DG sets etc.[1]. By incorporating DG technology in our distribution system we can achieve reduction in system losses, improvement in voltage profile, system reliability etc.

    An Electrical system consists of two parts- i. Power system

    ii. Distribution system. Power system is considered to be balanced while Distribution system is unbalanced in nature. Power system is highly mesh connected and distribution system is highly radial in nature. Due to radial nature, there is consecutive increase in voltage drop from source bus to end buses. Voltage collapse usually occurs in heavily loaded systems that do not have sufficient local reactive power support and consequently cannot provide secure voltage profile for the system. This reactive power shortage may lead to wide-area blackouts and voltage-stability problems as has occurred in many countries[2]. The shortage can be alleviated by an increased share of DGs in low-voltage (LV) distribution systems to improve voltage

    stability. For analysis of system we carry out load flow studies. Load flow studies are used to study the electrical power transfer from generators to consumers through the grid system[3]. The main objective of the load flow analysis is to find out the power flow in each line along with the voltage at each bus of the system for the specific loading conditions. Chiang [4] has presented a distribution load flow method by iterative solution of three fundamental equations representing real power, reactive power and voltage magnitude. Das, et al. [5]have proposed a load flow method by writing an algebraic equation for bus voltage magnitude. Distribution system with their radial structure and wide ranging resistance and reactance values are inherently ill-conditioned, hence the conventional load flow methods like Gauss-Seidel, Newton-Raphson and fast decoupled techniques are inefficient in solving such networks. For this reason we go for other techniques of distribution load flow. The load flow methods proposed for distribution systems considering the unbalance operation can be grouped into two basic categories. The first category is Forward Backward Sweep (FBS) / Ladder Network based methods, Loop Impedance Method and Implicit Zbus Gauss method or its modified versions[6]. The second category is composed of methods which require information on the derivatives of the network equations. Newton like methods involving formation of Jacobian and computation of power mismatches at the end of the feeder and laterals and other fast decoupled methods. Here in this paper we have opted Forward/Backward approach for the load flow studies.

  2. UNBALANCED THREE-PHASE LINE

    Fig.1 shows a typical section of the distribution system between bus i and j. The line parameters can be obtained by the method developed by Carson and Lewis[7]. A 4×4 matrix, which takes into account the self and mutual coupling effects of the unbalanced three phase line section, can be expressed as:

    Zaa

    Zba

    Zabcn=

    Zca

    Zna

    Zab Zbb Zcb Znb

    Zac Zbc Zcc Znc

    Zan Zbn

    . (1)

    Zcn Znn

    1. Constraints:

      For proper system operation certain constraints must be satisfied. These constraints are as follows:

      1. Active and reactive power equality:

    Total generated power must be equal to the power

    This equation can be reduced to 3×3 matrix, by applying demand given as (5), (6)

    Krons reduction[8], still considering effects of neutral and n n

    ground wire as shown in (2).

    PGi PDG PDi 0

    (5)

    Zaa

    Zabc= Zba

    Zca

    Zab Zbb

    Zcb

    Zac

    Zbc . (2)

    Zcc

    i1

    n

    i1

    QGi

    n

    i1

    QDi

    i1

    0

    (6)

    Ila

    a Zaa

    WhereGi, Gi are active and reactive power generated at bus i, , are active and reactive loads at bus i, is active power injected by DG.

    a 2) Distribution Line Capacity Limits:

    Va Va

    Zab

    Ilb

    Zac

    Power flow of lines should be less than the allowed flow constrained by its thermal limit.

    b

    Vb Zbc

    Zbb

    b Vb

    S(i, j) S(i, j)

    max

    (7)

    Ilc

    c Zcc c

    Vc Vc

    Fig.1. Typical Three Phase Feeder

    Now, the receiving end voltages can be linked with the

    Where S(i,j) is MVA flow in the line connecting

    bus i and j, S(i,j)max is MVA capacity of line connecting i and j.

    3) Voltage Drop limits:

    Bus voltages should be in the range of minimum and maximum voltage.

    sending end voltages of the feeder shown in Fig.1 as

    below:

    Vmin

    V Vmax

    (8)

    Va Va' Zaa

    Zab

    Zac Ia

    Where Vmin and Vmax are minimum and maximum allowable voltage at buses.

    Vb = Vb' + Zba

    Zbb

    Zbc Ib

    . (3)

    Vc Vc' Zca

    Zcb

    Zcc Ic

    IV. SOLUTION METHODOLOGY

    These days, most DG technologies, such as synchronous machines, power-electronic interface devices (e.g.,

    The same approach will be used for two phase system as well as single phase system. In a two phase system the phase which is not connected will have the corresponding Impedance matrixs row and column zero.

  3. PROBLEM FORMULATION

In this paper we are determining the optimal location and size of the DGs such that voltage profile is improved which further reduces the system losses.

A. Objective Function:

The objective function aims at minimizing the Bus Voltage Deviation Index (BVDI).

photovoltaic cells and micro turbines), and even new induction generators [e.g., doubly fed induction generators (DFIGs)], are capable of providing a fast, dynamic reactive power response[9]. This capability can be used by the system operators to enhance system security and stability. Since a generatr location affects the system voltage stability, finding the best position for its installation becomes inevitable, as improper placement may further deteriorate the system performance. To identifying the most effective bus for DG installation following procedure is followed:

  1. DG unit positioning algorithm:

    F(i) min(BVDIi )

    (4)

    • Calculate the average voltage of all buses in each phase.

      1 n

      BVDI is the average voltage deviation of all the three phases calculated at each bus.

      Vavg(m) V (i, m)

      n

      i1

      (9)

      Where n is number of buses in the system, m is

      the phase number.

      • Calculate the deviation of each bus voltage from Vavg for all phases.

        VD(m,i) V (m,i 1) Vavg(m) (10) Where m=1 to 3 and i=1, 2, 3.n-1.

      • Now, calculate bus voltage deviation index BVDI which is the average of Voltage deviation of all the three phases.

      • Compute the branch currents starting from end nodes using (15).

      • Use the (13) to calculate the updated bus voltageViter+1.

      • Compare the present value of the voltage with that of the previous iteration, if converge, go to next step, otherwise iter=iter+1 and go to step-5.

      • Calculate losses after the converged voltages are obtained using (16).

        1 3 Sloss (Vp * Ilpq* ) (Vq * Ilpq* )

        (16)

        3

        BVDI (i) VD(m, i)

        m1

        i=1, 2, .n-1. (11)

        Where Vp is the sending end voltage and Vq is the

        Now determine the order with the least value of BVDI, i. The bus next to i is considered as the best location for DG

        receiving end voltage and Ilpq is the current flowing in the respective line.

        placement of proper size given as DGpos.

        DGpos i 1

  2. Forward/Backward Sweep Load Flow:

(12)

Ploss real(Sloss)

Qloss imag.(Sloss)

(17)

(18)

The distribution system is very much different from the transmission system as it is more of radial system with low X/R ratio. Thus the conventional load flows like N.R, Gauss Siedel [10][11]etc. fails to converge or are not reliable. Hence in this paper forward backward (FB) sweep load flow is used [12] to compute load flow.

D. DG unit size allocation algorithm:

For DG sizing, first we will fix the maximum limit of DGs based on the number of DGs k we want install.

PDG max 100 / k . (19)

The maximum size of DG considered can be up to PDGmax. The equivalent aggregated load is calculated as follows:

Vabc Vabc' ZabcIabc. (13)

n

Pload Pi

n

i 1

(20)

Ii (Pi Qi) Vi *

i=2, 3, n (14)

Qload Qi

(21)

The FB sweep considers the complex load at each bus to be constant. The load is then converted into equivalent current injection at each bus using equation 14. The FB sweep method takes two steps in each iteration[13]. The first step is called backward sweep wherein starting from the last bus we calculate the branch current till the first bus, given by (14)]. Now the second step is called forward sweep wherein starting from the first bus, voltage is calculated for all the buses using equation (13).

i1

Where Pload is the equivalent active power component of the aggregated load; Pi is the active power component of the load at bus number i; Qload is the equivalent reactive power component of the aggregated load; Qi is the reactive power component of the load at bus number i; and n is the total number of buses.

To determine the size of DG to be applied at DGpos

obtained from (12) certain steps are followed:

Il j =Current of jth branch= Ili

Where i=all subsequent buses to 'j'

  1. Algorithm for Load Flow:

    (15)

    1. At the obtained DGpos we will apply generation in steps of 1% of Total load to the PDGmax and calculate the voltages at each bus.

    2. Check for the violation of any constraint.

    3. If YES then STOP at this generation. If No then

      Using the above equation (13), (14) and (15) we develop the load flow algorithm for three phase radial distribution system:

      • Input the data about the distribution system.

      • Assume the initial voltage magnitude at all buses to be 1p.u and voltage phase to be 0,-120 and 120 for phase-a, b and c respectively.

      • Construct the Z-bus matrix of the system as per the given data considering mutual inductances[15].

      • Set iter=1.

      • Calculate load current at each bus using (14).

        return to step 1.

    4. DG generation, for which the violation occurs, is stored and the generation previous to it is considered as the optimal size.

    5. This is the optimal size of DG generation, to be applied at DGpos for improving the voltage profile at each bus.

TABLE I

BASE CASE LOAD FLOW RESULTS

Bus

No.

Phase A

Phase B

Phase C

Magn.

Angle

Magn.

Angle

Magn.

Angle

1

1.0000

0.0000

1.0000

2.0944

1.0000

-2.0944

2

0.9860

0.0009

0.9879

2.0951

0.9865

-2.0943

3

0.9849

0.0012

0.9876

2.0951

0.9856

-2.0945

4

0.9803

0.0011

0.9821

2.0954

0.9810

-2.0940

5

0.9802

0.0011

0.9819

2.0954

0.9809

-2.0940

6

0.9769

0.0013

0.9786

2.0956

0.9777

-2.0938

7

0.9765

0.0013

0.9783

2.0956

0.9774

-2.0938

8

0.9697

0.0015

0.9708

2.0959

0.9703

-2.0934

9

0.9620

0.0018

0.9620

2.0960

0.9617

-2.0927

10

0.9512

0.0024

0.9503

2.0962

0.9497

-2.0919

11

0.9498

0.0026

0.9490

2.0962

0.9478

-2.0918

12

0.9495

0.0024

0.9484

2.0964

0.9482

-2.0918

13

0.9495

0.0027

0.9485

2.0961

0.9472

-2.0918

14

0.9492

0.0026

0.9485

2.0962

0.9473

-2.0918

15

0.9473

0.0024

0.9455

2.0964

0.9456

-2.0915

16

0.9488

0.0023

0.9471

2.0964

0.9474

-2.0916

17

0.9483

0.0027

0.9479

2.0963

0.9467

-2.0919

18

0.9489

0.9481

2.0962

0.9469

-2.0918

19

0.9466

0.0023

0.9447

2.0965

0.9451

-2.0914

Start

Read System

Calculate Vdev=Vavg-V in each phase

Data

Read the no of Dg user want to install NDG

Max single DG can

generate=100/NDG

No

Run Load Flow

Calculate Vavg of

each phase a,b & c.

Calculate mean of Vdev

among three phase at each bus

Find the bus with minimum

deviation.

Dgbus=bus+1

Apply DG at this Dgbus and increase the generation in steps starting with jj=1

If

Pgen(Dgbus)=Pload(Dgbus)-0.01*size*Pload

(size<NDG) Yes

TABLE II OPTIMIZATION RESULTS

Phase

W/o DG

With One DG

With Two DG

Ploss (KW)

Qloss (KVar)

Ploss (KW)

Qloss (KVar)

Ploss (KW)

Qloss (KVar)

A

16.596

7.033

7.222

2.738

6.202

2.324

B

16.479

7.173

6.185

2.878

5.326

2.513

C

16.972

7.312

7.211

3.247

6.216

2.791

If size==50

Run Load flow and check Voltages at each bus in each phase

Calculate losses and store the size of this first Dg

Yes No

size=1 and re-run same

process for next Dgbus

size=size+1

If(V>Vmax) No

Yes

Calculate losses and store the size of Dg from previous iteration

Print the Voltages, size of size of Dg

Pgen(Dgbus)=Pload+(Dgbus- 0.01*size*Pload)

Stop

Fig.2. Flowchart for optimal DG placement.

Fig.3 Voltage profile before DG placement

Fig.4 Voltage profile with single DG placed.

  1. RESULTS AND DISCUSSION

    Fig.5 Voltage profile with two DGs placed.

    algorithm, following optimum DG locations and sizes have been calculated. Fig.5 shows the effectiveness of the

    The proposed algorithm is tested on practical unbalanced three phase distribution feeder emanating from Pathardhi 132/11KV Grid substation in India. Using the proposed

    proposed algorithm on system performance in comparison with base case (without DG) in Fig.3. The optimum DG size and position when only one DG is placed are found to

    be 56% of total load with DG placed at 19th bus. When two DGs are placed first DG size is inferred to be 50% of total load placed at 19th bus and the second DG size is inferred to be 19% of remaining load placed at 17th bus. The base case voltages of each phase for the given loading are shown in Table I. From the figures we can see that DGs had improved the voltage profile to great extent. Thus reducing the system losses without exceeding the line limits. From Table I we see that the minimum voltage in the absence of any DG was 0.9447 p.u. at 19th bus for phase B while as given in Table V, we can see with two DGs optimally placed the minimum system voltage has risen to 0.9815 p.u at 13th bus for phase B.

    TABLE V

    FINAL VOLTAGE PROFILE AFTER PLACEMENT OF TWO DG

    Bus No.

    Phase A

    Phase B

    Phase C

    Magn.

    Angle

    Magn.

    Angle

    Magn.

    Angle

    1

    1.0000

    0.0000

    1.0000

    2.0944

    1.0000

    -2.0944

    2

    0.9931

    0.0036

    0.9940

    2.0975

    0.9931

    -2.0913

    3

    0.9919

    0.0039

    0.9937

    2.0975

    0.9922

    -2.0915

    4

    0.9909

    0.0052

    0.9912

    2.0990

    0.9909

    -2.0895

    5

    0.9907

    0.0052

    0.9911

    2.0990

    0.9908

    -2.0895

    6

    0.9898

    0.0062

    0.9898

    2.1000

    0.9898

    -2.0884

    7

    0.9894

    0.0062

    0.9895

    2.1000

    0.9895

    -2.0884

    8

    0.9884

    0.0087

    0.9871

    2.1024

    0.9879

    -2.0854

    9

    0.9876

    0.0118

    0.9844

    2.1050

    0.9859

    -2.0817

    10

    0.9884

    0.0170

    0.9828

    2.1094

    0.9848

    -2.0759

    11

    0.9876

    0.0174

    0.9820

    2.1095

    0.9835

    -2.0756

    12

    0.9897

    0.0181

    0.9834

    2.1105

    0.9859

    -2.0745

    13

    0.9873

    0.0174

    0.9815

    2.1094

    0.9829

    -2.0755

    14

    0.9875

    0.0176

    0.9819

    2.1097

    0.9833

    -2.0755

    15

    0.9969

    0.0220

    0.9888

    2.1140

    0.9923

    -2.0701

    16

    0.9889

    0.0180

    0.9822

    2.1105

    0.9852

    -2.0744

    17

    0.9878

    0.0181

    0.9824

    2.1102

    0.9840

    -2.0750

    18

    0.9871

    0.0176

    0.9816

    2.1097

    0.9829

    -2.0754

    19

    1.0000

    0.0234

    0.9913

    2.1155

    0.9954

    -2.0683

    TABLE III LOAD DATA

    Pload(KW)

    Qload(KVar)

    Phase A

    421.100

    204.100

    Phase B

    387.800

    187.800

    Phase C

    410.900

    199.000

    VI FUTURE SCOPE

    This method is presently tested on practical unbalanced three phase distribution feeder emanating from Pathardhi 132/11KV Grid substation in India, which can further be extended to even larger bus system present in literature. Here, DGs are considered to generate only active power however it can be extended to DGs operating at different power factors. The loads are considered to be constant which can be extended to time varying loads. We have considered BVDI as our objective for siting the location which can be extended to multi-objective optimization.

    TABLE IV DISTRIBUTED GENERATION INPUT

    One DG

    Two DG

    Location

    19th

    19th

    17th

    Phase A

    235.82

    210.550KW

    40.005KW

    Phase B

    217.17

    193.900KW

    36.841KW

    Phase C

    230.10

    205.450KW

    39.036KW

    1. CONCLUSION

      In this paper new Bus voltage deviation algorithm has been proposed for optimal placement A systematic simple approach to allocate multiple DG units in radial unbalanced distribution network is proposed, based on voltage deviation index a straightforward algorithm for sizing and locating multiple DG units is developed[16]. The proposed technique is applied to radial test systems. Results show that installing the decided DG units achieves great reduction in power loss and keep node voltages between Vmin and Vmax. This method is easy to implement and the results obtained are found to be good, as the optimal locations and size of DGs have improved the voltage profile as can be seen by graphs and the system losses are also.

    2. REFERENCES

  1. M. Esmaili, Placement of minimum distributed generation units observing power losses and voltage stability with network constraints, vol. 7, no. October 2012, pp. 813821, 2013.

  2. M. Ettehadi, H. Ghasemi, and S. Vaez-Zadeh, Voltage stability-based DG placement in distribution networks, IEEE Trans. Power Deliv., vol. 28, no. 1, pp. 171178, 2013.

  3. S. Kaur, A. Singh, and R. S. Khela, Load Flow Analysis of IEEE-3 bus system by using Mipower Software, vol. 4, no. 03, pp. 916, 2015.

  4. S. Ghosh and D. Das, Method for load-flow solution of radial distribution networks, IEE Proc.

    – Gener. Transm. Distrib., vol. 146, no. 6, p. 641, 1999.

  5. K. Prakash and M. Sydulu, Topological and primitive impedance based load flow method for radial and weakly meshed distribution systems, Iran. J. Electr. Comput. Eng., vol. 10, no. 1, pp. 1018, 2011.

  6. P. Aravindhababu, A New Fast Decoupled Power Flow Method for Distribution Systems, Electr. Power Components Syst., vol. 31, no. 9, pp. 869 878, 2003.

  7. W. H. Kersting, Dristribution System Modeling and Analysis. 2008.

  8. F. Dorfler and F. Bullo, Kron Reduction of Graphs, pp. 128, 2011.

  9. V. Safavi, B. Vahidi, and M. Abedi, OPTIMAL DG PLACEMENT AND SIZING IN DISTRIBUTION NETWORK WITH, vol. 26, no. 3, pp. 10711077, 2014.

  10. S. Kumar Injeti and N. P Kumar, Optimal Planning of Distributed Generation for Improved Voltage Stability and Loss Reduction, Int. J. Comput. Appl., vol. 15, no. 1, pp. 4046, 2011.

  11. O. P. Mahela, S. Ram, and O. Lalit, Optimal Capacitor Placement for Loss Reduction in Radial Distribution Feeder, vol. 4, no. 6, pp. 4348, 2013.

  12. S. Paul, A Simple Algorithm for Distribution System Load Flow with Distributed Generation, no. 2, 2014.

  13. J. Subrahmanyam, Load flow solution of unbalanced radial distribution systems, J. Theor. Appl. Inf. Technol., vol. 6, no. 1, pp. 4051, 2009.

  14. N. Ghosh, S. Sharma, and S. Bhattacharjee, A Load Flow based Approach for Optimum Allocation of Distributed Generation Units in the Distribution Network for Voltage Improvement and Loss Minimization, Int. J. Comput. Appl., vol. 50, no. 15, pp. 1522, 2012.

  15. B. Liu and B. Li, A general algorithm for building Z-matrix based on transitional matrices, 3rd Int. Conf. Deregul. Restruct. Power Technol. DRPT 2008, no. April, pp. 794797, 2008.

  16. T. Ramana, V. Ganesh, and S. Sivanagaraju, Distributed Generator Placement And Sizing in Unbalanced Radial Distribution System, Cogener. Distrib. Gener. J., vol. 25, no. 1, pp. 5271, 2010.