Use of Precast Hollow Core Slabs in High Rise Buildings

DOI : 10.17577/IJERTV3IS100397

Download Full-Text PDF Cite this Publication

Text Only Version

Use of Precast Hollow Core Slabs in High Rise Buildings

Supriya T J

    1. ech student, Department of Civil Engineering, Sri Siddhartha Academy Of Higher Education, Tumkur, India.

      Praveen J V

      Asst. professor, Department of Civil Engineering, Sri Siddhartha Academy Of Higher Education, Tumkur, India.

      Abstract – Precast prestressed hollow core flooring is used extensively around the world because of economical, light weight, faster assembling etc. This type of slabs is generally used in the construction of floors for high-rise apartments or multi- storey buildings in low-seismic regions.

      The present study is on the analysis of seismic behaviour of precast hollow core slabs in high rise buildings using ETABS software. Comparision of behaviour of hollow core slab building and solid slab building for different seismic zones keeping the member size same for all models. Comparision of quantity of concrete and quantity of steel for hollow core slab building and solid slab building. A 33 storey commercial office building with precast hollow core slabs have been analyzed for seismic zone IV with type two medium soil. Structural system used for these buildings are taken as concrete special moment-resisting frame with ductile shear walls. Five different models of hollow core slab building with different member sizes have been performed. Static analysis has been carried out by equivalent static method and dynamic analysis has been carried out by response spectrum method as per recommendation of IS: 1893(Part 1):2002.Based on analysis results of five models it has been concluded that model 5member sizes shows better performance when compared to other four models member sizes. Keeping model 5 member sizes constant, 4 models of hollow core slab building and 4 models of solid slab building have been performed for different seismic zones and compared with various factors such as base shear, storey drift. Thus hollow core slab building shows better performance when compared to solid slab building. Hollow core slab building and solid slab building have been analyzed for seismic zone IV based on analysis and design results, quantity of steel and quantity of concrete required are calculated and compared. Based on the analysis results it can be concluded that hollow core slab building consumes less material when compared to solid slab building. Therefore hollow core slab building is best compared to solid slab building.

      Keywords: precast hollow core slab; high rise building; finite ETABS Software; seismic zones.

      1. INTRODUCTION

A hollow core slab refers to a precast slab that is prepared using prestressed concrete with tubular voids which run through the full length of the slab. Prestressing gives concrete longer spanning capacity, shallow depth and the ability to carry heavy loads. Precast hollow core slabs are typically 1200mm in width and about 20m in length. This type of slabs are cost-effective, quick to assemble and build, have lower self-weight, use less raw materials etc.

The prestressed hollow core slabs are tender, light weight products which help in construction of thinner floor. The thinner the flooring much is the space saved for construction which can be translated in to additional floors in the high rise structure that too with controlled costs and lesser joints. The precast prestressed hollow core units are very easy to install and offer an immediate working platform after completion of installment and can be implemented with lesser labour or workforce in lesser time. This greatly reduces the construction delay to a minimum thereby enabling for faster construction of the high rise projects.

With hollow core slabs, thermal activated flooring can be installed in the high rise constructions. In high rise building hollow core flooring offers better fire resistance and ensures better protection of inhabitants or people within building at the time of fire incidents. Costs of construction are greatly reduced with use of hollow core floors in high rise constructions. The presence of longitudinal voids leads to about 45% saving in concrete compared with normal in-situ reinforced slab flooring.

    1. Definition of High Rise Building

      A building is an enclosed structure that has walls, floors, a roof, and usually windows. A tall building is a multi-storey structure in which most occupants depends on elevators [lifts] to reach their destinations. The most prominent tall buildings are called high-rise buildings in most countries. The terms do not have internationally agreed definitions. However, a high rise building can be defined as follows:

      Generally, a high rise structure is considered to be one that extends higher than the maximum reach of available fire-fighting equipment. In absolute numbers, this has been set variously between 75 feet(23 meters) and 100 feet(30 meters) or about seven to ten stories (depending on the slab-to-slab distance between floors).

      The exact height above which a particular building is deemed to be a high rise is specified by fire and building codes for the country, region, state, or city where the building is located. When the building exceeds the specified height, then fire, an ever-present danger in such situation facilities, must be fought by fire personnel from inside the building rather than from outside using fire hoses and ladders.

    2. Definition of earthquake

An earthquake is the series of vibration on the earths surface caused by the generation of seismic waves due to sudden rupture within the earth.

Seismograph is used to find strength and location of earth quake.

1.2.1 Definitions in earthquake resistant structures:

  1. Design Basis Earthquake (DBE): It is the earthquake which can reasonably be expected to occur at least once during the design life of the structure.

  2. Design Horizontal Acceleration Coefficient (Ah): It is a horizontal acceleration coefficient that shall be used for design of structures.

  3. Design Lateral Force: It is the horizontal seismic force prescribed by this standard that shall be used to design a structure.

  4. Design Seismic Base Shear (VB): It is the total design lateral force at the base of a structure.

  5. Height of Structure (h): It is the difference in levels, in metres, between its base and its highest level.

  6. Importance Factor (I): It is a factor used to obtain the design seismic force depending on the functional use of the structure, characterized by hazardous consequences of its failure, its post-earthquake functional need, historic value, or economic importance.

  7. Natural Period (T): Natural period of a structure is its time period of undamped free vibration.

  8. Response Reduction Factor (R): It is the factor by which the actual base shears force that would be generated if the structure were to remain elastic during its response to the Design Basis Earthquake (DBE) shaking, shall be reduced to obtain the design lateral force.

  9. Seismic Weight (W): It is the total dead load plus appropriate amount of specified imposed load.

  10. Shear Wall: It is a wall designed to resist lateral forces acting in its own plane.

  11. Special Moment-Resisting Frame: It is a moment resisting frame specially detailed to provide ductile behaviour and comply with the requirements given in IS 4326 or IS 13920 or SP 6 (6).

  12. Storey Drift: It is the displacement of one level relative to the other level above or below.

  13. Structural Response Factors (Sa/g): It is a factor denoting the acceleration response spectrum of the structure subjected to earthquake ground vibrations, and depends on natural period of vibration and damping of the structure.

  14. Zone Factor (Z): It is a factor to obtain the design spectrum depending on the perceived maximum seismic risk characterized by Maximum Considered Earthquake (MCE) in the zone in which the structure is located. The basic zone factors included in this standard are reasonable estimate of effective peak ground acceleration.

2. DESCRIPTION OF ANALYZING MODELS

    1. Modeling

      A commercial office building of 33 storeys with precast hollow core slabs of plan dimension 24mx18m is considered for analysis. Height of each storey is 3m and total height of the building is 99m. Structural system used for these building is taken as concrete special moment-resisting frame with ductile shear walls and type-II medium soil has been considered.

    2. preliminary data

      Plan of the building are shown in figure 2.1. Five models of hollow core slab buildings of different member sizes have been analyzed. For all models beam dimensions have been assumed as 230x260mm, 300x600mm, 300x750mm, and hollow core slab thickness have been assumed as 260mm and column dimensions and shear wall thickness have been shown in table 2.1.

      Figure 2.1-Plan of the commercial office building with precast hollow core slabs

      Table 2.1: Schedule of Member Sizes

      Name

      Column Dimensions

      Shear Wall Thickness

      Storey

      1-10

      Storey

      11-20

      Storey

      21-33

      Storey

      1-10

      Storey 11-

      33

      C1

      C2

      C3

      Sw1

      Sw2

      Model 1

      450×900

      450×750

      450×600

      400

      300

      Model 2

      450×1000

      450×750

      450×600

      400

      300

      Model 3

      600×1200

      400×800

      300×600

      400

      300

      Model 4

      600×900

      450×750

      300×600

      500

      450

      Model 5

      450×1200

      450×750

      450×600

      500

      450

      Note: All dimensions are in mm.

      Model 1-Column dimensions and shear wall thickness have been changed.

      Model 2-Column dimensions have been changed.

      Model 3-Column dimension have been changed and shear wall length has been increased.

      Model 4-Column dimensions and shear wall thickness have been changed.

      Model 5-Column dimensions have been changed.

    3. Material properties

      The strength of a structure depends on the strength of the materials from which it is made for this purpose material strength is specified in standardized ways as a step to proceed the design of a structure.

      1. Analysis property data

        Material name – Concrete

        Grade of concrete-M25 has been considered for beams and slabs.

        Grade of concrete-M40 has been considered for columns and shear walls.

        Type of material – Isotropic Mass per unit volume-2.4 kN/m3

        Modulus of elasticity-25 kN/mm2 Poissons ratio- 0.2

      2. Design property data

        Concrete cube compressive strength for M25 grade of concrete, fck-25 N/mm2

        Concrete cube compressive strength for M40 grade of concrete, fck-40 N/mm2

        Bending reinforcement yield stress for steel reinforcement, fy 415 N/mm2

        These are the material properties which have been considered for all the models.

    4. Load considerations

Dead load, live load and earthquake load are considered in the design as per Indian standard codes.

Table 2.2 represents dead load and live load data considered for analysis.

Wall load

12kN/m2

Super imposed

dead load

2.5 kN/m2

Super imposed

live load

4 kN/m2

Table 2.2: Dead load and live load data

can therefore work well for low to medium-rise buildings without significant coupled lateral-torsion modes, in which only the first mode in each direction is of significance. Tall buildings (say, over, 75 m), where second and higher modes can be important, or buildings with torsion effects, are much less suitable for the method, and require more complex methods to be used in these circumstances.

2.5.2 Manual equivalent static analysis design procedure as per IS 1893(PART 1):2002

The total design lateral force or design base shear along any principal direction is given in terms of design horizontal seismic coefficient and seismic weight of the structure. Design horizontal seismic coefficient depends on the zone factor of the site, importance factor of the structure, response reduction factor of the lateral load resisting elements and the fundamental period of the structure. The procedure generally used for the equivalent static analysis is explained below:

  1. Determination of fundamental natural period (Ta) of the buildings.

    For moment resisting RC frame building without brick infill wall.

    Ta = 0.075h0.75

    For moment resisting steel frame building without brick infill wall.

    Ta = 0.085h0.75

    For all other buildings including moment resisting RC frame building with brick infill walls.

    Ta =0.09h/d

    Table 2.3 represents earthquake load data for seismic zone-IV considered for analysis of five models.

    Table 2.3: Earthquake load data

    Where,

    h- The height of building in m.

    d- The base dimension of building at plinth level in m, along the considered direction of lateral force.

  2. Determination of base shear (VB) of the building.

    VB = Ah x W

    Where,

    Seismic zone

    Zone IV

    Soil type

    Medium(Type-2)

    Each storey height

    3m

    Zone factor, Z

    0.24

    Importance factor, I

    1.0

    Response reduction factor, R

    5.0

    Analysis type

    Dynamic analysis

    Ah =

    2.5 Methods of static analysis

    The method of static analysis used here is equivalent static method.

    2.5.1 Equivalent static analysis

    All design against earthquake effects must consider the dynamic nature of the load. However, for simple regular

    Ah = Design horizontal seismic coefficient. Z = Zone factor.

    I = Importance factor.

    R = Response reduction factor.

    Sa/g = Average response acceleration coefficients.

    Sa/g in turn depends on the nature of foundation soil (rock, medium or soft soil sites), natural period and the damping of the structure.

  3. Distribution of design base shear.

The design base shear VB thus obtained shall be distributed along the height of the building as per the following expression:

2

structures, analysis by equivalent linear static methods is

Q V

Wihi

often sufficient. This is permitted in most codes of practice for regular, low to medium-rise buildings and begins with an estimate of peak earthquake load calculated as a function of the parameters given in the code. Equivalent static analysis

i B n

Wihi2 i1

Where,

Qi = The design lateral force. Wi = The seismic weight.

hi = The height of the ith floor measured from base. n = The number of stories in the building.

2.6 Methods of dynamic analysis

IS: 1893(Part 1):2002 presents two methods of dynamic analysis. They are:

  1. Time-history analysis.

  2. Response spectrum analysis.

    Out of these two methods, response spectrum analysis is more convenient than time history analysis.

    2.6.1 Response spectrum analysis

    A response spectrum is the graphic representation of maximum response i.e. displacements, velocity and acceleration of a damped single-degree-of-freedom system to a specified ground motion, plotted against the frequency or modal periods.

    Five models of different member sizes have been done considering above member sizes, material properties, and load Consideration and they have been analyzed for seismic zone IV. By considering gravity loads such as dead load, live load data shown in table 2.2 static analysis has been carried out by equivalent Static method and by considering earthquake load data shown in table 2.3 dynamic analysis has been carried out by response spectrum method as per recommendation of IS 1893(Part 1):2002.The results of base shear, time period and storey drift have been collected and compared with different models.

      1. Comparision of hollow core slab building with solid slab building for different seismic zones

        By varying member sizes seismic analysis have been carried out by response spectrum method on Model 1, Model 2, Model 3, Model 4, and Model 5.Thus based on analysis results it can be concluded that Model 5 member size perform better when compared to other 4 Models member sizes.

        A 33 storey commercial office building of plan dimension 24mx18m is considered for analysis. Keeping the Model 5 member size constant, different hollow core slab buildings and solid slab buildings have been performed for seismic zone II, seismic zone III, seismic zone IV and seismic zone V. Table 2.4 represent schedule of member sizes for hollow core slab buildings and solid slab buildings. Structural system used for these building is taken as concrete special moment-resisting frame with ductile shear walls and type-II medium soil is considered.

        By considering gravity loads such as dead load, live load data shown in table 2.2 static analysis has been carried out by equivalent static method and by considering earthquake load data for different seismic zones shown in table 2.5. Dynamic analysis has been carried out by response spectrum method as per recommendation of IS 1893(Part 1):2002.The results of base shear and maximum storey drift have been collected and compared with different models.

        Table 2.4: Schedule of member sizes

        Type of buildings

        Name

        Hollow core slab

        building

        Solid Slab building

        Beam Dimensions

        B1

        230 x 260

        B1

        230 x 600

        B2

        300 x 600

        B2

        300 x 600

        B3

        300 x 750

        B3

        300 x 750

        Column Dimensions

        Storey 1-10

        C1

        450x 1200

        C1

        450 x 1200

        Storey 11-20

        C2

        450 x 750

        C2

        450 x 750

        Storey 21-33

        C3

        450 x 600

        C3

        450 x 600

        Slab

        Thickness

        260

        150

        Shear Wall

        Thickness

        Storey 1-10

        SW1

        500

        SW1

        500

        Storey 11-33

        SW2

        450

        SW2

        450

        Note: All dimensions are in mm.

        Table 2.5: Shows earthquake load data for different seismic zone

        Type of buildings

        Type of model

        Seismic zone

        Zone factor, Z

        Importance factor,

        I

        Response reduction factor,

        R

        Hollow core slab buildings

        Model

        A

        Zone II

        0.10

        1.0

        5.0

        Model

        B

        Zone III

        0.16

        1.0

        5.0

        Model

        C

        Zone IV

        0.24

        1.0

        5.0

        Model

        D

        Zone V

        0.36

        1.0

        5.0

        Solid slab buildings

        Model

        A1

        Zone II

        0.10

        1.0

        5.0

        Model

        B1

        Zone III

        0.16

        1.0

        5.0

        Model

        C1

        Zone IV

        0.24

        1.0

        5.0

        Model

        D1

        Zone -V

        0.36

        1.0

        5.0

      2. Comparision of total quantity of concrete and total quantity of steel in hollow core slab building and solid slab building

    Model C hollow core slab building and Model C1 solid slab building have been considered for the determination of total quantity of concrete and total quantity of steel. Model C hollow core slab building and Model C1 solid slab building have been analyzed and designed for seismic zone IV. Design details such as longitudinal reinforcement details and shear reinforcement details of Model C and Model C1 have been collected. Detail calculation of quantity of steel and quantity of concrete have been done in excel sheet and the total quantity have been compared by graphical representation.

  3. RESULTS AND DISCUSSIONS

    The results of each building models have been presented. The analysis carried out is static analysis by equivalent static method and dynamic analysis by response spectrum method.

    The result of Base shear, storey drifts and time period for different models were presented. Comparision of hollow core slab building and solid slab building results have been presented. Comparision results of total quantity of concrete and total quantity of steel in hollow core slab building and solid slab building have been presented.

    .

      1. Analysis results of five hollow core slab building models of different member sizes

        The results of five models such as base shear, time period, and maximum storey drift are represented in table 3.1.

        Table 3.1: Results of five hollow core slab building models of different member sizes

        Name

        Base Shear,(kN)

        Time period,

        (Sec)

        Max Storey Drift,(mm)

        EQX

        EQY

        Drift x

        Drift y

        Model 1

        3664.12

        3664.12

        4.785067

        0.000754

        0.0022

        Model 2

        3671.55

        3671.55

        4.757858

        0.000745

        0.002245

        Model 3

        3709.72

        3709.72

        4.723347

        0.000699

        0.002239

        Model 4

        3819.93

        3819.93

        4.6438

        0.00068

        0.002135

        Model 5

        3839.71

        3839.71

        4.60538

        0.000656

        0.00207

        Based on analysis results of five hollow core slab building models presented in table 3.1 graphs have been drawn as shown below.

        TIME PERIOD

        1. Comparision of type of model v/s time period Figure 3.1: Graph of type of model v/s time period

          TYPE OF MODEL V/S TIME PERIOD

          4.8

          4.75

          4.7

          4.65

          4.6

          4.55

          4.5

          TYPE OF MODEL V/S TIME PERIOD

          TYPE OF MODEL

          The comparative study of maximum time period values for different type of models are represented in figure 3.1. In comparison of time period at different storey levels, it is observed that the time period are steadily increased i.e., minimum at top storey and maximum time period at bottom storey. The maximum time period value of Model (1) is 1.005 times greater than that of Model (2), 1.013 times greater than that of Model (3), 1.031 times greater than that of Model (4),

          1.039 times greater than that of Model (5) at storey 1.Thus maximum time period in building have been steadily decreased as the member size increases.

        2. Comparision of type of model v/s base shear in x direction

          Figure 3.2: Graph of type of model v/s base shear in x direction

          The comparative study of base shear values in x direction for different type of models are represented in figure 3.2.The base shear values of Model (1) is 1.002 times less than that of Model (2), 1.012 times less than that of Model (3), 1.042 times less than that of Model (4), 1.047 times less than that of Model (5) in x direction. Thus base shear in building steadily increased as the member size increases.

        3. Comparision of type of model v/s base shear in y direction

          Figure 3.3: Graph of type of model v/s base shear in y direction

          The comparative study of base shear values in y direction for different type of models are represented in figure 3.3. The base shear value of Model (1) is 1.002 times less than that of Model (2), 1.012 times less than that of Model (3), 1.042 times less than that of Model (4),1.047 times less than that of Model (5) in y direction. Thus base shear in structure will be steadily increased as the member size increases.

        4. Comparision of type of model v/s max storey drift in x direction

          Figure 3.4: Graph of type of model v/s max storey drift in x direction

          The comparative study of maximum storey drift values in x directions for five different models is represented in figure 3.4.The maximum storey drift value of Model (1) is

          1.012 times greater than that of Model (2), 1.072 times greater than that of Model (3), 1.078 times greater than that of Model (4),1.108 times greater than that of Model (5).Thus maximum storey drift will decreases as the member size increases and storey drift values of all models lies within the limits as per IS:1893(Part 1):2002 (clause-7.11.1).

        5. Comparision of type of model v/s max storey drift in y direction

    Figure 3.5: Graph of type of model v/s max storey drift in y direction

    The comparative study of maximum storey drift values in y direction for five different models is represented in figure 3.5. The maximum storey drift value of Model (1) is

    1.006 times greater than that of Model (2), 1.009 times greater than that of Model (3), 1.058 times greater than that of Model (4), 1.091 times greater than that of Model (5) in y direction. Thus maximum storey drift will decreases as the member size increases and storey drift values of all models lies within the limits as per IS:1893(Part 1):2002 (clause- 7.11.1).

    3.2 Comparision of hollow core slab building with solid slab building for different seismic zones

    Analysis results of hollow core slab building and solid slab building for different seismic zones are shown in table 3.2 and 3.3. The results of models such as base shear and maximum storey drift are given below.

    Table 3.2: Represents results of hollow core slab building for different seismic zones

    Seismic

    Zone

    Name

    Base Shear,(kN)

    Max Storey

    Drift,(mm)

    EQX

    EQY

    Drift X

    Drift Y

    Zone II

    Model A

    1599.88

    1599.88

    0.000273

    0.000862

    Zone III

    Model B

    2559.80

    2559.80

    0.000437

    0.001380

    Zone IV

    Model C

    3839.71

    3839.71

    0.000656

    0.002070

    Zone V

    Model D

    5759.56

    5759.56

    0.000984

    0.003105

    Table 3.3: Represents results of solid slab building for different seismic zones

    Seismic Zone

    Name

    Base Shear,(kN)

    Max Storey Drift,(mm)

    EQX

    EQY

    Drift X

    Drift Y

    Zone II

    Model A1

    1394.19

    1394.19

    0.000238

    0.000750

    Zone III

    Model B1

    2230.71

    2230.71

    0.000381

    0.001201

    Zone IV

    Model C1

    3346.06

    3346.06

    0.000571

    0.001801

    Zone V

    Model D1

    5019.10

    5019.10

    0.000856

    0.002702

    Based on analysis result values presented in table

      1. and table 3.3 graphs have been represented as shown below. Base shear, maximum storey drift have been compared for different zones between hollow core building and solid slab building.

        1. Comparision of seismic zone v/s base shear for hollow core slab building and solid slab building

          Figure 3.6: Graph of seismic zones v/s base shear

          The comparative study of base shear values for different seismic zones is represented in figure 3.6. In comparision of base shear values for different seismic zones, base shear value are increased steadily and maximum base shear are found in seismic zone V. The base shear values of hollow core slab building in seismic zone II, zone III, zone IV and zone V is 1.147 times less than that of solid slab building in seismic zone II, zone III, zone IV, and zone V. Thus hollow core slab building produce less base shear compared to solid slab building.

        2. Comparision of seismic zone v/s max storey drift along x direction for hollow core slab building and solid slab building

          Figure 3.7: Graph of seismic zones v/s maximum storey drift along x direction

          The comparative study of max storey drift values in x direction for different seismic zones is represented in figure

            1. In comparision of max storey drift values for different seismic zones, storey drift value are increased steadily and maximum storey drift are found in seismic zone V. The maximum storey drift values of hollow core slab building in seismic zone II is 1.1470 times greater than that of solid slab building in seismic zone II, 1.1469 times greater than that of solid slab building in seismic zone III, 1.1488 times greater than that of solid slab building in seismic zone IV, 1.1495 times greater than that of solid slab building in seismic zone

              V. Thus hollow core slab building produce greater storey drift values in x direction compared to solid slab building.

        3. Comparision of seismic zone v/s max storey drift along y direction for hollow core slab building and solid slab building

          Figure 3.8: Graph of seismic zones v/s max storey drift along y direction

          The comparative study of max storey drift values in y direction for different seismic zones is represented in figure

            1. In comparision of max storey drift values for different seismic zones, storey drift value are increased steadily and maximum storey drift are found in seismic zone V. The maximum storey drift values of hollow core slab building in seismic zone II is 1.1490 times greater than that of solid slab building in seismic zone II, 1.1490 times greater than that of solid slab building in seismic zone III, 1.1493 times greater than that of solid slab building in seismic zone IV, 1.1491 times greater than that of solid slab building in seismic zone

          V. Thus hollow core slab building produce greater storey drift values in y direction compared to solid slab building.

      2. Comparision of total quantity of concrete and total quantity of steel in hollow core slab building and solid slab building

        Model C hollow core slab building and Model C1 solid slab building design details such as longitudinal reinforcement details and shear reinforcement details of beams, columns and slabs have been collected. Detail calculation of quantity of steel and quantity of concrete of all storeys have been done in excel sheet and the results of total quantity of steel and total quantity of concrete for beams, columns, slabs in solid slab building and in hollow core slab building are represented in table 3.4.

        Table 3.4: Total Quantity of concrete and steel in Hollow core Slab building and Solid Slab building

        Sl. No.

        Hollow core Slab building

        Solid Slab building

        Total Quantity of

        Concrete, (m3)

        Total Quantity of Steel, (Tonnes)

        Total Quantity of

        Concrete, (m3)

        Total Quantity of steel, (Tonnes)

        Beams

        976.734

        151.403

        1131.57

        187.461

        Columns

        2204.265

        217.776

        2204.265

        191.109

        Slabs

        1612.05

        91.424

        2138.40

        146.239

        Total

        4793.30

        460.603

        5474.23

        524.809

        Total quantity of concrete and total quantity of steel in hollow core slab building and solid slab building have been compared in graph as shown below based on results presented in table 3.4.

        1. Comparision of type of buildings v/s total quantity of steel

          Figure 3.9: Graph of type of building v/s total quantity of steel

        2. Comparision of type of buildings v/s total quantity of concrete

          Figure 3.10: Graph of type of building v/s total quantity of concrete

          The comparative study of total quantity of concrete and total quantity of steel for different type of building are represented in figure 3.9 and 3.10. Hollow core slab building consume less material when compared to solid slab building because of the presence of longitudinal voids in the cross section of hollow core slabs leads to saving in concrete as compared to solid slabs and at the same time cuts the amount of prestressing steel because of lower self-weight. Therefore hollow core slab building is best compared to solid slab building.

  4. CONCLUSION

    The thesis attempts to study the behaviour of precast hollow core slabs in high rise buildings.Five models of hollow core slab buildings of different member sizes is analyzed using equivalent static method and Response spectrum method for seismic zone IV. From the above analysis results following conclusions can be made in this respect:

          • Maximum storey drift, storey drifts in X and Y direction of model 5 is less than that of other four models.

          • Time period of model 5 is less than that of other four models.

          • Storey shear in X and Y direction of model 5 is greater than that of model 1, 2, 3, 4.

            From the above study it has been conclude that model 5 shows better performance when compared to other models.

            Keeping model 5 member size constant Hollow core slab building and solid slab building have been performed for different seismic zones and it has been analyzed using equivalent static method and Response spectrum method according to code provisions, considering the effect of base shear, storey drift the results obtained by hollow core slab building and solid slab building for different seismic zone has been compared. Following broad conclusions can be made in this respect:

          • Base shear is less for hollow core slab building compared to solid slab building for different seismic zones.

          • Storey drift is higher for hollow core slab building as compared solid slab building.

          • Thus hollow core slab building consumes less material when compared to solid slab building. Therefore hollow core slab building is best compared to solid slab building.

  5. REFERENCES

  1. Maher K. Tadros, Amin Einea and Say-Gunn Low, Rafael A. Magana, Arturo E. Schultz, Seismic Behavior of a Six-Story Precast Office Building Federation International de la Precontrainte (FIP), Proceedings of the 12th Congress, Washington May29-June2 Vol.1,1994,PP.E16-E22

  2. P.C.J.Hoogenboom, Analysis of Hollow Core Slab FloorsHERON,Vol.50,No3 (2005),pp.173-185

  3. Renee A Lindsay, John B Mander and Des K Bull, Experiments on the Seismic Performance of Hollow Core Floor Systems in Precast Concrete Buildings13th World Conference on Earthquake Engineering Vancouver,B.C.,Canada August 1-6,2004,pp.585

  4. Liberato Ferrara, Antonella Colombo, Paolo Negro and GiandomenicoToniolo,Precast vs. Cast-in-situ Reinforced Concrete Industrial Buildings Under Earthquake Loading: An Assessement via Pseudodynamic Tests 13th World Conference on Earthquake Engineering Vancouver,B.C.,Canada August 1-6,2004,pp.743

  5. JorisFellinger, Jan Stark, JoostWalraven, Shear and Anchorage Behavior of Fire Exposed Hollow Core Slabs HERON,Vol.50,No4 (2005),pp.279-301

  6. L.J. Woods, D.K. Bull and R.C. Fenwick, The Seismic Performance of Hollow Core Flooring: The Significance of Negative Bending Moments The 14th World Conference on Earthquake Engineering Beijing, China, October 12-17, 2008.

  7. J. Chang, A. H. Buchanan, R. P. Dhakal& P. J. Moss, Simple Method for Modeling Hollow Core Concrete Slabs Under Fire 2008.

  8. Jeremy Chang, Andrew H. Buchanan, Rajesh Dhakal and Peter J.Moss, Analysis of Hollow Core Concrete Floor Slabs Under Fire 2008.

  9. Izni S. Ibrahim, Kim S. Elliott, Long-Term Behavior of Precast Prestressed Hollow Core Slabs with Concrete Toppings 2008, pp.391- 400.

  10. Wijesundara K.K., Mallawaarachchi R. S and SendanayakeS,Shear Strength of Precast Prestressed Concrete Hollow Core Slabs,SAITM Research Symposium on Engineering Advancements 2012 ,pp. 53- 56.

  11. IS: 456-2000, Indian Standard Plain and Reinforced Concrete Bureau of Indian Standards, New Delhi.

  12. IS: 1893 (Part-1): 2002, Indian Standard Criteria for Earthquake Resistant Design of Structures Bureau of Indian Standards, New Delhi.

  13. S Unni Krishna Pillai and Devdas Menon Reinforced Concrete Design

  14. Pankaj Agarwal and Manish Shrikhande Earth Quake Resistant Design of Structures

  15. IS: 875 (Part-1): 1987, Indian Standard Code of Practice for Design Loads (Other than Earthquake) for Buildings and Sructures Bureau of Indian Standards, New Delhi.

  16. IS: 875 (Part-2): 1987, Indian Standard Code of Practice for Design Loads (Other than Earthquake) for Buildings and Structures Bureau of Indian Standards, New Delhi.